SF₆ gas solutions
WIKA data sheet SP 63.15
Page 1 of 5
SF₆ service equipment
For lling, cleaning and recovery of SF
6
gas
Models GPU-B-2000 and GPU-B-3000
Description
The right instrument for each application -
The GPU platform
The gas-handling equipment of the GPU platform enable
the complete process from initial lling to processing to be
carried out safely and intuitively.
The platform is available in 4 versions.
Model GPU-B-2000
SF₆ service equipment in fully automated basic version
Model GPU-S-2000
SF₆ service equipment with additional SIL 2 safety control
Model GPU-B-3000
SF₆ service equipment at the highest performance level
Model GPU-S-3000
SF₆ service equipment with additional SIL 2 safety control
and the highest performance level
High standards and quality – model series B
Like the entire product series, the fully automated basic
model oers high-performance components and an optimum
design. The products have a USB port and an Ethernet port
for remote maintenance. The 10" IntelliTouch touchscreen
promises a comfortable and intuitive handling.
All models of the GPU platform are available with a lter
process that allows the SF₆ gas to be brought to a lower
humidity value directly on-site. Optionally, the GPU can be
equipped with a WIKA gas humidity sensor, model GDHT-20,
which enables ltering to a target value.
The SF₆ service equipment is an ecient and reliable solution
that exceeds the current IEC standards for handling SF₆ gas.
Low downtimes through long service intervals of more than
2,000 hours, or two years with a max. running time of 600 hours
per year, make them an extremely durable product that is always
ready for use.
Data sheets showing similar products:
SF₆ service equipment for lling, cleaning and recovering SF₆ gas; model GPU-S-x000; see data sheet SP 63.16
SF₆ service equipment with 300-litre tank
Applications
Filling, cleaning, recovery, evacuation and venting of SF
6
gas-lled switchgear, linear accelerators and other SF
6
gas-lled equipment
Special features
Oil-free compressor and vacuum compressor
Option for on-site gas ltration to the desired humidity
Low maintenance eort
Operation via 10” touchscreen
WIKA data sheet SP 63.15
01/2022
WIKA data sheet SP 63.15 ∙ 01/2022 Page 2 of 5
Specications
Voltage supply
AC 400 V, 3-phase, 50/60 Hz ±10 %
AC 240 V, 3-phase, 50/60 Hz ±10 %
AC 208 V, 3-phase, 50/60 Hz ±10 %
Oil-free compressor (SF₆ gas)
Gas ow rate Output pressure
6 m³/h at 50 Hz
7.3 m³/h at 60 Hz
50 bar abs.
10.2 m³/h at 50 Hz
12.3 m³/h at 60 Hz
50 bar abs.
15 m³/h at 50 Hz
18.5 m³/h at 60 Hz
50 bar abs.
Oil-free vacuum compressor (SF₆ gas)
Gas ow rate Final vacuum
4.8 m³/h at 50 Hz
5.8 m³/h at 60 Hz
< 5 mbar abs.
10 m³/h at 50/60 Hz < 1 mbar abs.
15 m³/h at 50 Hz
18 m³/h at 60 Hz
< 1 mbar abs.
35 m³/h at 50 Hz
42 m³/h at 60 Hz
< 1 mbar abs.
Vacuum pump (air)
1)
Gas ow rate Final vacuum
25 m³/h at 50 Hz
30 m³/h at 60 Hz
< 0.1 mbar abs.
40 m³/h at 50 Hz
48 m³/h at 60 Hz
< 0.1 mbar abs.
63 m³/h at 50 Hz
76 m³/h at 60 Hz
< 0.1 mbar abs.
100 m³/h at 50 Hz
120 m³/h at 60 Hz
< 0.1 mbar abs.
1) Oil-free on request
Integrated tank, storage capacity
Without tank
300 litres
600 litres
Stowage for 6 gas cylinders
Stowage for 10 gas cylinders
Integrated gas cylinder scales
Without scales
Without scales with pull-out. xed to the GPU
Measuring range: 0 ... 120 kg
Accuracy: ±50 g
Mobile scales
Measuring range: 0 ... 136 kg
Accuracy: ±68 g
Connections
GIS 1 valve DN 20, pressure range 0 ... 10 bar abs.
Gas cylinder 2 valves DN 20, pressure range 0 ... 50 bar abs.
Atmosphere
(optional)
1 valve DN 20, pressure range 0 ... 1.2 bar abs.
Filter element
Molecular sieve, aluminium oxide, particle lter 1 μm
Max. water absorption: 75 g
Control element
10" touchscreen
Permissible ambient temperature
Operation: -10 ... +40 °C [14 ... 104 °F]
Storage: -20 ... +60 °C [-4 ... +140 °F]
Permissible air humidity
< 95 % r. h. (non-condensing)
Ingress protection
IP42
Weight
Without tank Approx. 665 kg
With empty 300-litre tank Approx. 1,000 kg
With empty 600-litre tank Approx. 1,300 kg
With empty stowage for 6 gas cylinders Approx. 1,050 kg
With empty stowage for 10 gas cylinders Approx. 1,175 kg
Tyres
Solid rubber, 200 mm, with rollover protection
Options
Humidity sensor to measure the humidity content and
ltering to a target humidity value
Additional process connection for the simultaneous evacua-
tion and recovery or lling
Evaporators