Product Specifications
“NEW GENERATION”
Guide Specification for FirstLine
®
PLT
10kVA, 15kVA, 20kVA, 30kVA, 40kVA
Three-Phase, On-Line
Uninterruptible Power Supply
5/10/16
1229 Byers Road, Miamisburg, OH 45342, USA
Telephone: (866) 261-1191, (937) 253-1191 Fax: (937) 253-1723
~ 2 ~
SECTION 1.0
SCOPE
1.1 Summary
A. This Specification defines the electrical and mechanical characteristics and requirements for the FirstLine PLT Series UPS as
manufactured by Staco Energy Products Co. located in Dayton, OH.
B. The UPS shall be a continuous duty; three-phase, uninterruptible power system, hereafter referred to as the UPS designed to
operate with the building supply to provide conditioned power as well as power back up for the critical loads.
C. The UPS shall use
Adaptive Feed Cancellation (AFC) Technology that provides advanced control with AFC forward
cancellation circuit for low harmonic distortion.
1.2 Qualifications
The manufacturer shall have a minimum of 20 years of experience in the design, manufacture, and testing of solid-state
transistorized UPS systems of similar capacity.
1.3 Standards
A. The UPS shall be designed in accordance with the applicable sections of the current revision of the following documents. Where
conflict arises between these documents and statements made herein, the statements in this specification shall prevail.
1. UL Standard 1778
2. CSA 22.2, No. 107.3
3. NEMA PE-1
4. FCC PT 15, Subpart J, Class B
5. National Electric Code
6. OSHA
7. ANSI C62.41
8. ISO 9001
1.4 System Description
A.
The UPS shall be a true double conversion, “On-Line” system consisting of the following major components:
1. Rectifier complete with power factor correction
2. Battery charger
3. PWM Inverter utilizing IGBT’s (Insulated Gate Bipolar Transistor)
4. Continuous duty rated Static Switch
5. Input Isolation switch (SWIN)
6. Output Isolation switch (SWOUT)
7. Maintenance Isolation switch (SWMB)
8. Bypass Isolation switch (SWBY)
9. DSP Control and Monitoring Panel with Graphic display
1.5 Warranty
A. UPS Warranty
The UPS warranty shall be in effect for 24 months after initial start-up but no more than 30 months after shipment,
whichever occurs first. The warranty shall cover all parts and labor for units commissioned by manufacturer’s approved
service representative.
B. Battery Limited Warranty
Three (3) Year full limited warranty passed through from the battery manufacturer, controlled environment required @ 77ºF
(25ºC).