1
Data Bulletin
7400DB0301
July 2003
Nashville, TN, USA
Harmonic Mitigating Transformers
Application Guide
Class 7400
ABOUT THIS DOCUMENT This document is a guide for applying Harmonic Mitigating Transformers
(HMT). The Low Voltage Dry Type Distribu tion Transformer Produ ct
Support Group is also available as a resource. If the harmonic issue is
severe, contact Square D for support. Square D’s Power System Analysis
group can provide a complete analysis of your electrical distribution system
and make recommendations to match your specific application criteria.
INTRODUCTION Harmonic Mitigating Transfo rmers (HMT) accompli sh harmonic mitigation
(attenuation) (see “What are Harmonics?” on page 6) by providing good
source impedance and through sine wave recombination. Sine wave
recombination occurs within the transformer itself at the nodes, the
connection points, of the windings. Sine wave recombin ation also occurs
when the sine waves are phase shifted using multiple transformers. All of
these methods may help reduce harmonics in electrical distribution
systems.
While not intended as a complete technical analysis, this bul letin will
highlight the appropriate application of HMTs. It is interesting to note that
none of this is new technology. In variable frequency drive applications,
harmonic mitigation has been accomplished with transformers for more than
50 years. Additional information regarding some of the theory of harmonic
mitigation using transformers is included in th e appendices.
INDUSTRY TRENDS Harmonic mitigation is a topic of high interest among North American
industry users and manufacturers. Howe ver, the European community has
established guidelines to control the maximum level of harmonics that
equipment can introduce onto a system. Computer and business equipment
manufacturers, in response to the European Community guidelines, created
power supplies that do not burden an electrical system with harmonics. It is
likely that North America will soon follow the limited harmonic path.
STANDARDS The standard for evaluating transformers serving non-linear loads is IEEE
C57.110. This standard recognizes the effects of harmonic attenuation
(reactive effect on harmonic levels) and harmonic diversity (cancellation
effect of multiple non-linear loads). C57.110 is often ignored by some HMT
vendors.
EXCEPTIONS IEEE Standard 1100-1992 (the Emerald Book) is not appropriate for
evaluating transformer loading with non-linear loads. Any such
references should be ignored.
IEEE Standard 519-1992 is not intended for use with in a facility. The
standard sets the maximum harmonic voltage distortion level allowed at
the point of common coupling between the utility and the customer. The
point of 519 is to insure that one customer’s power usage profile does
not negatively impact another customer.
Harmonic Mitigating Transformers 7400DB0301
July 2003
© 2003 Schneider Electric All Rights Reserved2
PROPER APPLICATION OF THE
TRANSFORMER METHOD OF
HARMONIC MITIGATION
The installation of any Square D HMT transformer -- delta-wye, delta-
zigzag, or wye-zigzag – provides an effective means of preventing triplen
(3
rd
, 9
th
, 15
th
, etc.) harmonics from passing to the source side of the
transformer. The standard conservative design practice of using delta-wye
transformers automatically results in electrical distribution systems with
some inherent harmonic mitigation (see Figure 1 ).
With a standard delta-wye transformer installed, the triplen harmonics are
not trapped in the transfo rme r, but nor do they pass through the
transformer. The sine waves induced on the windings are recombined at the
nodes of the delta into new sine wave shapes that do not contain triplen
components (see “Combining Sine Wave T heory” on page 8).
The transformer’s reactance causes some attenuation of the harmonics and
limits the crest factor allowe d downstream (see “Source Impedance” on
page 8).
Figure 1: Standard Delt a-w y e Tra nsforme r Fe e din g a Compu te r Pa nel From a Distri bu tion Pan el bo ard.
Computer
Panel
A
B
C
N
208Y/120
480V
Panel
Delta -Wye Transformers
‘Cancel’ 3rd, 9th, 15th Harmonics