Megger LT320 and Megger LT330
Automatic derivation of R1 + R2 values
Traditionally the sum of the resistance of the
phase conductor R1 and the circuit protective
conductor R2 have always been obtained by
disconnecting the supply and connecting the
phase conductor to the protective conductor
at the distribution board, followed by a test
between phase and earth terminals at the
circuit’s extremity.
If the inspection is an initial verification of an
new electrical installation, then the value for
R1+R2 should be obtained by the above
method and using a continuity tester (i.e.
Megger MIT320) as per BS7671.
However, for a periodical inspection where
there is an existing previous report, after
verifying the protective conductor, R1+R2
values can be acquired using the Megger LT320
or LT330 loop impedance testers.
These instruments are able to calculate the
R1+R2 values from tests conducted on a live
circuit.
Basically a reference loop impedance reading is
saved from the distribution board (i.e. Ze), then
the instrument is switched to R1+R2 setting, then
all following loop tests, made at the extremity of
each circuit, will have the reference reading
subtracted and the instrument will display the
R1+R2 in ohms.
These readings can then be checked against the
previous report.
Note: Caution should taken with boiler radials &
circuits feeding bathrooms since parallel earth
paths via any bonding will affect readings.
Megger LT320 downloading loop tester
Megger LT320 and Megger LT330
MaxZ function
The MaxZ setting on these instruments is
very useful for finding the maximum Zs
reading in any circuit.
Simply the instrument does a loop test and
stores the highest reading, any higher
readings from other tests on the same circuit
are held, lower readings are only displayed
momentarily, ideal for finding the maximum
Zs of a ring main quickly.
LT320 Loop tester like all Megger loop testers it is 3-phase safe