METRAFLEX 300M, METRAFLEX 300MXBL
Flexible AC Current Sensors
2 GMC-I Messtechnik GmbH
Influencing Quantities
Output load 100 k for specified accuracy
Frequency range 20 Hz bis 100 kHz ( ( 1 dB / 50 Hz)
Phase angle error < 1° (45 ... 65 Hz)
Position sensitivity 2.5% of reading
External fields 0.25% of measuring range
at a distance of > 100 mm from sensor
Temperature coefficient
0.15% of reading/°K
Reference Conditions
Ambient temperature
+15 C ... +25 C
Relative humidity 20% ... 75%
Operating voltage 3 V 0.5 V
Frequency of
measured quantity 45 Hz ... 65 Hz
Waveshape of
measured quantity Sine
Power-frequency
magnetic field < 30 A/m
Conductor position Conductor vertical in relation to senor level
and at the geometrical center
Measuring loop shape
circular
Output load 100 k
Power Supply of Measuring Amplifier
Power supply two AA MN1500 LR6 alcaline batteries
or
for METRAFLEX 300MXBL
external supply (2...3 V DC/max.100 mA)
Battery life approx. 80 hrs.
External power supply for METRAFLEX 300MXBL
Connection by barrel plug socket
5.5/2.1 mm, minus at center pin
Display Functions
Battery status LED (orange) „LOW BATTERY“ lights up:
– battery voltage too low,
or
– external power supply
Overcurrent LED (red) „OVERLOAD“ lights up
Mechanical Design
Measuring Amplifier
Dimensions 110 (H) x 65 (W) x 23 (D) mm
Output
measuring signal METRAFLEX 300M:
0.5 m coaxial cable connected
with 4 mm safety plug
METRAFLEX 300MXBL:
0.5 m coaxial cable connected
with 4 pin Hypertronics plug
Material ARNITE T06-200SNF double insulation,
UL94 V-0
Protection IP40 per DIN VDE 0470 Part 1/EN 60529
Flexible Rogowski Current Sensor
Sensor length 16 cm, double insulation
(on request: 22 cm or 31,5 cm)
Sensor cross-section
6 mm
Connector cable
between probe and housing, length 2 m
Material Sensor: Alcryn 2070 NC
Lock: LATI LATENE 7H2W V0
Protection IP50 per DIN VDE 0470 Part 1/EN 60529
Ambient Conditions
Operating temperature
–20 °C to +65 °C (–4 °F to +149 °F)
Storage temperature –40 °C to +75 °C (–40 °F to +167 °F)
Humidity 15% to 85%
, no condensation allowed
Electrical Safety
Safety class II, double insulation
Safety standards EN 61010-1:2001
EN 61010-031:2002 +A1:2008
EN 61010-2-032:2002
Measuring category 1000 V
RMS
CAT III, 600 V
RMS
CAT IV
Voltage between
output and ground max. 30 V
Pollution degree
2 (sensor and measuring amplifier)
Electromagnetic Compatibility EMC
Interference emission
EN 61326-2:2006 class B
Interference immunity
EN 61326-2:2006
Applicable Regulations and Standards
DIN EN 61010-2-032
(VDE 0411-2-032)
Safety requirements for electrical equipment for measurement,
control and laboratory use
– Particular requirements for
hand-held and hand-operated current sensors
EN 60529
VDE 0470 Part 1
Test instruments and test procedures
– degrees of protection provided by enclosures (IP code)