APPLICATION
NOTE
March 2004
Bulletin #MMAP004
EIK WATER COOLING
REQUIREMENTS
1
INTRODUCTION
Water cooled EIK’s operate at high power densities and requires careful attention to the maintenance of adequate water
flow and purity to ensure proper operation and long life. Water with contaminant levels that exceed the purity
requirements will cause corrosion and scaling, this includes ordinary tap water. Unchecked corrosion of the metals in
the EIK coolant passages reduces operating life. Scaling obstructs cooling passages preventing efficient heat transfer
resulting in overheating and permanent damage. Continuous filtering, deionizing and oxygen removal is necessary for
maintaining high water purity.
WATER PURITY REQUIREMENTS
1. Deionized or distilled water
2. Water resistivity shall be maintained at 1 Megohm-cm or higher at 25 °C.
3. Dissolved oxygen should not exceed 0.5 parts per million
4. The particulate matter sized shall not be greater than 50 microns (325 mesh)
Water purity and flow protection must be periodically checked to ensure against excessive degradation. Water can
become contaminated by the cooling system components and from the environment. For example, free oxygen in the
coolant will form copper oxide on the surfaces of the coolant passages, particularly the collector. The oxide compounds
can drastically reduce heat transfer to the water. In extreme cases, heavy oxide deposits can plug up coolant passages
reducing flow. The formation of these oxides is greatly accelerated by elevated temperature within the system.
Corrosion via electrolysis between dissimilar metals may also take place when ions are present in the water and there is
an electric potential across the coolant passages (i.e. as in depressed collector operation). Electrolysis will destroy the
coolant passages.
The presence of either oxidation of electrolysis will result in premature EIK failure.
BASIC SYSTEM DESIGN
Figure 1 shows a typical arrangement of a recirculating cooling system with a purification loop. The main cooling loop
consists of a heat exchanger, water reservoir, particulate filter (10-50 micron), circulation pump, the connection tubing,
valves, pressure gauges, temperature and flow sensing interlocks required to ensure sufficient coolant flow and
temperature whenever the equipment is energized. A nitrogen gas pressurized system as shown is recommended to
reduce oxidation.
The purification loop taps off approximately 10% of the total cooling system flow rate. The purification loop consists of
a purity meter, oxygen, ion and particulate removal cartridges.
Flow and pressure regulating valves should be installed on the inlet lines to the EIK for adjustment of flow rate and
pressure drop. A thermometer interlock should be placed in the inlet line to the EIK and a flow meter interlock should
be placed in the outlet coolant line from the EIK. These interlocks must be wired into the electrical controls, such that
the EIK is completely de-energized in the event of loss of coolant flow or an over temperature condition.
The main circulation pump must be of sufficient size to ensure the flow and pressure throughout the operating range as
specified on the Test Data Sheet. Care must be taken when connecting the coolant lines to the EIK. Be certain that the
flow is in the direction specified. Reversed flow may result in inadequate cooling.
The coolant lines to the EIK inlet and outlet ports should of an insulating flexible material arranged so as to avoid
excessive strain on the coolant ports of the EIK. Many EIK’s are shipped with the collector and body-cooling lines
partially assembled using nylon tubing. Nylon, polypropylene and chlorinated polyvinyl chloride (CPVC) tubing with
adequate wall thickness are acceptable choices for this service.