Name
Name in Interface
(web/menu) Description OID Sample Output
Actual
Value
tlpATSDeviceMainLoadControllable Indicates whether the main output is controllable/if the
UPS can be turned off and on.
.1.3.6.1.4.1.850.1.1.3.4.2.1.1.2.1 true (1)
tlpATSDeviceMainLoadState The current state of the main output of the device. .1.3.6.1.4.1.850.1.1.3.4.2.1.1.1.1 on (2)
tlpATSDeviceOutputCurrentPrecision Output Current Precision The measurement precision--use as a divisor to obtain the
true output current.
.1.3.6.1.4.1.850.1.1.3.4.2.1.1.11.1 hundredths (2)
tlpATSDeviceOutputPowerTotal The AC output total power for all circuits. .1.3.6.1.4.1.850.1.1.3.4.2.1.1.9.1 0
tlpATSDevicePowerOnDelay The amount of time a given device will wait before it
connects to a valid AC source.
.1.3.6.1.4.1.850.1.1.3.4.2.1.1.4.1 0
tlpATSDeviceTotalInputPowerRating The total input power rating of all phases on the device. .1.3.6.1.4.1.850.1.1.3.4.2.1.1.5.1 2880 288.0
tlpATSIdentNumATS The number of ATS devices that this agent is currently
managing.
.1.3.6.1.4.1.850.1.1.3.4.1.1.0 1
tlpATSIdentNumBreakers The number of bank breakers supported by the ATS. .1.3.6.1.4.1.850.1.1.3.4.1.2.1.7.1 2
tlpATSIdentNumCircuits The number of circuits supported by the ATS. .1.3.6.1.4.1.850.1.1.3.4.1.2.1.6.1 3
tlpATSIdentNumHeATSinks The number of heatsink thermistors supported by the
ATS.
.1.3.6.1.4.1.850.1.1.3.4.1.2.1.8.1 0
tlpATSIdentNumInputs The number of inputs supported by the ATS. .1.3.6.1.4.1.850.1.1.3.4.1.2.1.1.1 2
tlpATSIdentNumOutletgroups The number of receptacle groups supported by the ATS. .1.3.6.1.4.1.850.1.1.3.4.1.2.1.5.1 0
tlpATSIdentNumOutlets The number of receptacles supported by the ATS. .1.3.6.1.4.1.850.1.1.3.4.1.2.1.4.1 25
tlpATSIdentNumOutputs The number of outputs supported by the ATS. .1.3.6.1.4.1.850.1.1.3.4.1.2.1.2.1 1
tlpATSIdentNumPhases Number of Phases The number of phases per input supported by the ATS. .1.3.6.1.4.1.850.1.1.3.4.1.2.1.3.1 1
tlpATSInputBadTransferVoltage The minimum line voltage allowed before the unit
disconnects the AC input connection.
.1.3.6.1.4.1.850.1.1.3.4.3.1.1.1.4.1 750 75.0
tlpATSInputCurrentLimit The capacity of each phase conductor, limited by the AC
input cord or other factors.
.1.3.6.1.4.1.850.1.1.3.4.3.1.1.1.15.1 24
tlpATSInputHighTransferVoltage The maximum line voltage allowed before the unit
disconnects the AC input connection.
.1.3.6.1.4.1.850.1.1.3.4.3.1.1.1.7.1 1390 139.0
tlpATSInputLineIndex.1.1.1 The table row index for the input line on the ATS. .1.3.6.1.4.1.850.1.1.3.4.3.1.2.1.1.1.1.1 1
tlpATSInputLineIndex.1.1.2 Same description as above. .1.3.6.1.4.1.850.1.1.3.4.3.1.2.1.1.1.1.2 2
tlpATSInputNominalVoltage.1 The nominal value of the input line voltage. .1.3.6.1.4.1.850.1.1.3.4.3.1.1.1.1.1 230
tlpATSInputNominalVoltagePhaseToPhase The nominal value of the input line voltage as measured
from phase to neutral.
.1.3.6.1.4.1.850.1.1.3.4.3.1.1.1.3.1 1200 120.0
tlpATSInputPhaseFrequency.1.1.1 Input Frequency 1 (Hz) The present input frequency for a given phase. .1.3.6.1.4.1.850.1.1.3.4.3.1.2.1.4.1.1.1 599 59.9
tlpATSInputPhaseFrequency.1.1.2 Input Frequency 2 (Hz) Same description as above. .1.3.6.1.4.1.850.1.1.3.4.3.1.2.1.4.1.1.2 0
tlpATSInputPhaseIndex.1.1.1 The table row index for the input phase for the input line. .1.3.6.1.4.1.850.1.1.3.4.3.1.2.1.2.1.1.1 1
tlpATSInputPhaseIndex.1.1.2 Same description as above. .1.3.6.1.4.1.850.1.1.3.4.3.1.2.1.2.1.1.2 2
tlpATSInputPhaseVoltage.1.1.1 Input Voltage 1 (V) The magnitude of the present input voltage for a given
phase.
.1.3.6.1.4.1.850.1.1.3.4.3.1.2.1.5.1.1.1 2470 247.0
tlpATSInputPhaseVoltage.1.1.2 Input Voltage 2 (V) Same description as above. .1.3.6.1.4.1.850.1.1.3.4.3.1.2.1.5.1.1.2 0
tlpATSInputPhaseVoltageMax.1.1.1
Maximum Input Voltage (V)
The maximum input voltage value since the last reset of
this value for a given phase.
.1.3.6.1.4.1.850.1.1.3.4.3.1.2.1.7.1.1.1 2570 257.0
tlpATSInputPhaseVoltageMin.1.1.1 The minimum input voltage value since the last reset of
this value for a given phase.
.1.3.6.1.4.1.850.1.1.3.4.3.1.2.1.6.1.1.1 0
tlpATSInputSourceAvailability.1 Input Source Available The determination as to which of two AC input lines are
available.
.1.3.6.1.4.1.850.1.1.3.4.3.1.1.1.12.1 inputSourceA (1)
tlpATSOutletBank.1.1 Indicates on which bank the given outlet is located. .1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.15.1.1 1