Supported SNMP OIDs
This document identifies Simple Network Management Protocol (SNMP) Object Identifiers (OIDs) for use in configuring, monitoring and controlling network-enabled Tripp Lite devices.
The following charts were compiled using LX Platform devices (e.g. WEBCARDLX) running 15.5.x firmware. These OIDs may not be compatible with SNMPWEBCARD.
Note: OID support will vary by device model.
Name
Name in Interface
(web/menu) Description OID Sample Output
Actual
Value
ATS -- TRIPPLITE-PRODUCTS MIB
This section shows indexed items: Two input sources and two outlets (loads). Additional outlets would be indexed in a similar manner.
tlpATSBreakerIndex The table row index for the ATS bank breaker. .1.3.6.1.4.1.850.1.1.3.4.3.5.1.1.1.1.x 1
tlpATSBreakerStatus Indicates whether the bank breaker is open(0), closed(1)
or not installed.
.1.3.6.1.4.1.850.1.1.3.4.3.5.1.1.2.1.x open (0)
tlpATSCircuitIndex The table row index for the ATS circuit. .1.3.6.1.4.1.850.1.1.3.4.3.4.1.1.1.1.x 1
tlpATSCircuitInputVoltage The input voltage for a circuit. .1.3.6.1.4.1.850.1.1.3.4.3.4.1.1.3.1.x 0
tlpATSCircuitTotalCurrent Total Current Bank 1 (A) The total current for all receptacles in a given circuit. .1.3.6.1.4.1.850.1.1.3.4.3.4.1.1.4.1.x 0
tlpATSCircuitTotalPower The total power for all receptacles in a given circuit. .1.3.6.1.4.1.850.1.1.3.4.3.4.1.1.8.1.x 0
tlpATSCircuitUtilization The percentage of utilization of a given circuit. .1.3.6.1.4.1.850.1.1.3.4.3.4.1.1.10.1.x 0
tlpATSConfigAutoShedOnTransition If enabled(1), the ATS will perform its preconfigured
shed sequence on transfer from primary to secondary
input source.
.1.3.6.1.4.1.850.1.1.3.4.5.1.1.6.1 disabled (0)
tlpATSConfigHighVoltageTransferOld High Transfer Voltage (V) The maximum line voltage allowed before the unit
disconnects the AC input connection.
.1.3.6.1.4.1.850.1.1.3.4.5.5.1.7.1.1 2660 266.0
tlpATSConfigInputVoltage The nominal value of the input line voltage. .1.3.6.1.4.1.850.1.1.3.4.5.1.1.1.1 230
tlpATSConfigLowVoltageTransfer Low Transfer Voltage (V) The minimum line voltage allowed before the unit
disconnects the AC input connection.
.1.3.6.1.4.1.850.1.1.3.4.5.5.1.7.1.x 1440 144.0
tlpATSConfigOutputCurrentHighThreshold The value at which an output current high condition is
declared.
.1.3.6.1.4.1.850.1.1.3.4.5.6.1.3.1.1 200 20.0
tlpATSConfigOutputCurrentLowThreshold The value at which an output current low condition is
declared.
.1.3.6.1.4.1.850.1.1.3.4.5.6.1.4.1.1 0
tlpATSConfigOutputCurrentThresholdTolerance The value used with output current thresholds to evaluate
output current conditions.
.1.3.6.1.4.1.850.1.1.3.4.5.6.1.2.1.1 2
tlpATSConfigVoltageRangeOldTable OBSOLETE The voltage range options for configuring the operating
voltages of an ATS.
.1.3.6.1.4.1.850.1.1.3.4.5.2.1.1.1
tlpATSControlRamp Set to TRUE to initiate the pre-designated ramp sequence
on the ATS.
.1.3.6.1.4.1.850.1.1.3.4.4.1.1.1.1 0
tlpATSControlShed Set to TRUE to initiate the pre-designated shed sequence
on the ATS.
.1.3.6.1.4.1.850.1.1.3.4.4.1.1.2.1 0
tlpATSDeviceMainLoadCommand Set this value to turn the main load off(1), on(2) or cycle
(3); idle (0).
.1.3.6.1.4.1.850.1.1.3.4.2.1.1.3.1 idle (0)
TECHNICAL APPLICATION BULLETIN #95-3565
Name
Name in Interface
(web/menu) Description OID Sample Output
Actual
Value
tlpATSDeviceMainLoadControllable Indicates whether the main output is controllable/if the
UPS can be turned off and on.
.1.3.6.1.4.1.850.1.1.3.4.2.1.1.2.1 true (1)
tlpATSDeviceMainLoadState The current state of the main output of the device. .1.3.6.1.4.1.850.1.1.3.4.2.1.1.1.1 on (2)
tlpATSDeviceOutputCurrentPrecision Output Current Precision The measurement precision--use as a divisor to obtain the
true output current.
.1.3.6.1.4.1.850.1.1.3.4.2.1.1.11.1 hundredths (2)
tlpATSDeviceOutputPowerTotal The AC output total power for all circuits. .1.3.6.1.4.1.850.1.1.3.4.2.1.1.9.1 0
tlpATSDevicePowerOnDelay The amount of time a given device will wait before it
connects to a valid AC source.
.1.3.6.1.4.1.850.1.1.3.4.2.1.1.4.1 0
tlpATSDeviceTotalInputPowerRating The total input power rating of all phases on the device. .1.3.6.1.4.1.850.1.1.3.4.2.1.1.5.1 2880 288.0
tlpATSIdentNumATS The number of ATS devices that this agent is currently
managing.
.1.3.6.1.4.1.850.1.1.3.4.1.1.0 1
tlpATSIdentNumBreakers The number of bank breakers supported by the ATS. .1.3.6.1.4.1.850.1.1.3.4.1.2.1.7.1 2
tlpATSIdentNumCircuits The number of circuits supported by the ATS. .1.3.6.1.4.1.850.1.1.3.4.1.2.1.6.1 3
tlpATSIdentNumHeATSinks The number of heatsink thermistors supported by the
ATS.
.1.3.6.1.4.1.850.1.1.3.4.1.2.1.8.1 0
tlpATSIdentNumInputs The number of inputs supported by the ATS. .1.3.6.1.4.1.850.1.1.3.4.1.2.1.1.1 2
tlpATSIdentNumOutletgroups The number of receptacle groups supported by the ATS. .1.3.6.1.4.1.850.1.1.3.4.1.2.1.5.1 0
tlpATSIdentNumOutlets The number of receptacles supported by the ATS. .1.3.6.1.4.1.850.1.1.3.4.1.2.1.4.1 25
tlpATSIdentNumOutputs The number of outputs supported by the ATS. .1.3.6.1.4.1.850.1.1.3.4.1.2.1.2.1 1
tlpATSIdentNumPhases Number of Phases The number of phases per input supported by the ATS. .1.3.6.1.4.1.850.1.1.3.4.1.2.1.3.1 1
tlpATSInputBadTransferVoltage The minimum line voltage allowed before the unit
disconnects the AC input connection.
.1.3.6.1.4.1.850.1.1.3.4.3.1.1.1.4.1 750 75.0
tlpATSInputCurrentLimit The capacity of each phase conductor, limited by the AC
input cord or other factors.
.1.3.6.1.4.1.850.1.1.3.4.3.1.1.1.15.1 24
tlpATSInputHighTransferVoltage The maximum line voltage allowed before the unit
disconnects the AC input connection.
.1.3.6.1.4.1.850.1.1.3.4.3.1.1.1.7.1 1390 139.0
tlpATSInputLineIndex.1.1.1 The table row index for the input line on the ATS. .1.3.6.1.4.1.850.1.1.3.4.3.1.2.1.1.1.1.1 1
tlpATSInputLineIndex.1.1.2 Same description as above. .1.3.6.1.4.1.850.1.1.3.4.3.1.2.1.1.1.1.2 2
tlpATSInputNominalVoltage.1 The nominal value of the input line voltage. .1.3.6.1.4.1.850.1.1.3.4.3.1.1.1.1.1 230
tlpATSInputNominalVoltagePhaseToPhase The nominal value of the input line voltage as measured
from phase to neutral.
.1.3.6.1.4.1.850.1.1.3.4.3.1.1.1.3.1 1200 120.0
tlpATSInputPhaseFrequency.1.1.1 Input Frequency 1 (Hz) The present input frequency for a given phase. .1.3.6.1.4.1.850.1.1.3.4.3.1.2.1.4.1.1.1 599 59.9
tlpATSInputPhaseFrequency.1.1.2 Input Frequency 2 (Hz) Same description as above. .1.3.6.1.4.1.850.1.1.3.4.3.1.2.1.4.1.1.2 0
tlpATSInputPhaseIndex.1.1.1 The table row index for the input phase for the input line. .1.3.6.1.4.1.850.1.1.3.4.3.1.2.1.2.1.1.1 1
tlpATSInputPhaseIndex.1.1.2 Same description as above. .1.3.6.1.4.1.850.1.1.3.4.3.1.2.1.2.1.1.2 2
tlpATSInputPhaseVoltage.1.1.1 Input Voltage 1 (V) The magnitude of the present input voltage for a given
phase.
.1.3.6.1.4.1.850.1.1.3.4.3.1.2.1.5.1.1.1 2470 247.0
tlpATSInputPhaseVoltage.1.1.2 Input Voltage 2 (V) Same description as above. .1.3.6.1.4.1.850.1.1.3.4.3.1.2.1.5.1.1.2 0
tlpATSInputPhaseVoltageMax.1.1.1
Maximum Input Voltage (V)
The maximum input voltage value since the last reset of
this value for a given phase.
.1.3.6.1.4.1.850.1.1.3.4.3.1.2.1.7.1.1.1 2570 257.0
tlpATSInputPhaseVoltageMin.1.1.1 The minimum input voltage value since the last reset of
this value for a given phase.
.1.3.6.1.4.1.850.1.1.3.4.3.1.2.1.6.1.1.1 0
tlpATSInputSourceAvailability.1 Input Source Available The determination as to which of two AC input lines are
available.
.1.3.6.1.4.1.850.1.1.3.4.3.1.1.1.12.1 inputSourceA (1)