1
Vega Series
Vega_Datasheet_69537 - v21.0
Vega Series
Medical
450W - 900W
Modular power supply.
https://emea.lambda.tdk.com/vega
https://product.tdk.com/en/power/vega
Features Benets
•Industryleadingexibility Suits your application
•Screw, Fast-on or IEC connection Simpliesdesignintosystem
•Worldwide safety approvals Supports global use
•Up to 11 outputs Eliminates need for additional supplies
•3 year warranty
Low cost of ownership
Industrial
Test
Broadcast
Comms
Renewable
Input
Vega 450, 650 and 900 Vega dc (450W)
Input Voltage /
Frequency
90-264Vac / 47 - 63 Hz (440Hz with reduced PFC)
900W version is 150-264Vac only, 650W below 150Vac
34 - 75Vdc
derate linearly below 44V to 340W at 34V
Input Fuse 16A / 250Vac HBC Fast acting (not user accessible) 20A Fast acting (not user accessible)
Inrush Current <40A at 25°C and 264Vac (cold start) <40A at 25°C, ETSI EN300 132-2
Leakage Current See ‘How To Create A Product Description’ for details n/a
How To Create A Product Description
a) Not available for Vega 900
b) Thermocoupled sample recommended to ensure adequate
cooling - consult sales
c)xFXandxEWoptionsincreaseleakagecurrentby90µA.Re-
place‘x’withrequiredoutputvoltage(5FW=5Vstandbysupply)
d) Not available for Vega dc
The extensive range of output modules and options make it possible to achieve almost any combination of Volts and Amps. You can create
your own Vega conguration online at https://cong.emea.tdk-lambda.com/. This method checks your conguration and oers the optimum
solution. Alternatively, you can do this manually by using the guide below.
1. Calculate total output power to select the appropriate converter, then select required Cooling, Connection, Leakage Current and Controls/
Signals from the following table:
2. Select Output Modules and options from the output voltages tables.
Example - if you require 5.2V / 18A with output inhibit :-
a) Select B1H as closest match for voltage & current and prex with voltage (eg 5.2B1H)
b) add sux ‘S’ or ‘F’ for Screw or Fast-on output connection (eg 5.2B1HS)
c) add sux ‘N’ for output inhibit if required (eg 5.2B1HSN)
d) Repeat for other outputs.
Ensure you do not select more than a total of 5 slots width of modules. This will create a complete product description eg V6FSSF 5L1SN
12/12H3/3S 24C5S which represents a four output 650W Vega with Forward air, Screw terminal input, 1.5mA leakage, ac Fail, Global
inhibit & 5V/100mA standby supply with the following outputs:
Output 1 = 5V/35A (with output inhibit, module good and current share option). Output 2 = 12V / 10A, Output 3 = 12V / 6A, Output 4 = 24V
/ 10A, all with screw terminal outputs.
3. Contact TDK-Lambda to validate conguration and issue a part number.
Converter
V0 450W (dc in)
V4 450W
V6 650W
V9 900W
V4 F S S F
Cooling
F Forward air - standard
Q
d
Forward air - Quiet
R
a
Reverse air
P
ad
Reverse air - Quiet fan
C
b
Customer air - no fan
Input
Connection
S Screw
F
d
Fast-on terminal
I
d
IEC320 with switch
Primary
Option
F ac fail, psu+fan inhibit, 5V/100mA standby
FV ac fail, psu+fan inhibit, 5V/300mA standby
xFW
cd
ac fail, psu+fan inhibit, 5-15V/1A standby
E ac fail, psu+fan enable, 5V/100mA standby
EV ac fail, psu+fan enable, 5V/300mA standby
xEW
cd
ac fail, psu+fan enable, 5-15V/1A standby
Leakage
Current
(max leakage
current at 264Vac,
63Hz)
S Standard 1.5mA
M 650µA
L 290µA
R 175µA
T 60µA
2
Vega Series
Vega_Datasheet_69537 - v21.0
a) F1, F2 and W2 modules not for Vega 900
b)38Vmaxfor900W
c) Only available for Vega 900
d)5.1Vmaxfor900W
e)3.4Vmaxfor900W
f)8Vmaxfor900W
g)15Vmaxfor900W
h)28Vmaxfor900W
i)18Vmaxfor900W
j)30Vmaxfor900W
k)7.5Vmaxfor900W
l)12.5Vmaxfor900W
m)19Vmaxfor900W
n)3.4Vmaxfor900W
OUTPUT VOLTAGES (single output modules) OUTPUT VOLTAGES (twin output modules)
Module
Adjustment Range
(Volts)
Current
(Amps)
Slots Module
V1 Adjustment Range
(Volts)
Current
V2 Adjustment Range
(Volts)
Current
(Amps)
Slots
B1L 1.8 - 3.8
e
20 1 H1L/1L
1.8 - 3.8
n
12
1.8 - 3.8
n
8 1
C1 1.8 - 4.1
e
35 1 H1L/1H 3.9 - 5.5
d
8 1
C1Y 1.8 - 4.1
e
40 1 H1L/2 5.6 - 9
f
6 1
D1L 1.8 - 3.8 50 1.5 H1L/3 9.1 - 16.2
u
6 1
E1 1.8 - 3.8
e
60 2 H1L/4 16.3 - 25
p
4.5 1
F1
a
1.8 - 3.8 80 2 H1H/1L
3.9 - 5.5
d
12
1.8 - 3.8
n
8 1
Z2 1.8 - 3.8
e
95 3 H1H/1H 3.9 - 5.5
d
8 1
Z3 1.8 - 3.8
e
114 4 H1H/2 5.6 - 9
f
6 1
B1H 3.9 - 5.5
d
20 1 H1H/3 9.1 - 16.2
u
6 1
L1 4.2 - 5.5
d
35 1 H1H/4 16.3 - 25
p
4.5 1
D2 3.8 - 9
k
45 1.5 H2/1L
5.6 - 9
f
10
1.8 - 3.8
n
8 1
D1H 3.9 - 5.5
d
50 1.5 H2/1H 3.9 - 5.5
d
8 1
E2 3.8 - 8
k
60 2 H2/2 5.6 - 9
f
6 1
Z18 4.2 - 5.5 66 2 H2/3 9.1 - 16.2
u
6 1
F2
a
3.8 - 8 75 2 H2/4 16.3 - 25
p
4.5 1
Z4 3.9 - 5.5
d
95 3 H3/1L
9.1 - 16.2
u
10
1.8 - 3.8
n
8 1
Z6 3.9 - 5.5
d
104 3.5 H3/1H 3.9 - 5.5
d
8 1
B2 5 - 9
f
25 1 H3/2 5.6 - 9
f
6 1
B3 9.1 - 16.2
g
12 1 H3/3 9.1 - 16.2
u
6 1
C3 9.1 - 16.2
g
18 1 H3/4 16.3 - 25
p
4.5 1
D3 8 - 16.5
g
24 1.5 H5/1L
16.2 - 28 5
1.8 - 3.8
n
8 1
E3L 8 - 13.9
l
40 2 H5/1H 3.9 - 5.5
d
8 1
Z7 8 - 16.5
g
45 3 H5/2 5.6 - 9
f
6 1
EE2 7.6 - 16
g
45 4 H5/3 9.1 - 16.2
u
6 1
D4 14 - 21.5
i
18 1.5 H5/4 16.3 - 25
p
4.5 1
E4 14 - 19.9
m
30 2 Wide Range Programmable Modules
E3H 14 - 15 36 2 Module Voltage Range Current Slots
C4 16.3 - 21.5
i
14 1 W2
a
0.25
w
- 7.5 30 1
Select features from table below
CC3 18.2 - 32.4
j
18 2 W5 0.25
x
- 32 8.5 1
E5L
v
20 - 24 27 2
B5 21.6 - 31
h
6 1 Follow by F or T Fixed or Tracking Overvoltage protection
C5 21.6 - 31
j
10 1 F or S Fast-on or Screw output terminals
D5 21 - 28 15 1.5 R or V Resistance (0-32kΩ) or Voltage (0-5V) programming
E5H
v
24 - 28 25 2
1, 2, 3
or 4
1 Inhibit, Fixed Current Limit
Z19
co
24 - 28 36 3.5 2 Inhibit, Programmable Current Limit (0-5V)
HH5/3 25.3 - 44.2
b
5 1 3 Enable, Fixed Current Limit
DD4 28 - 43
s
18 3 4 Enable, Programmable Current Limit (0-5V)
EE4
c
28 - 38 22.5 4
HH5/4 32.5 - 53
t
4.5 1 Follow non wide range modules by F (Fast-on) or S (Screw) output terminals
BB4 32.6 - 43
q
10 2
EE5L
co
40 - 48 18 4 Options - Single output Modules* Options - Twin output Modules*
C5B4 43 - 48 10 2
N
Output Inhibit, Module Good &
Current Sharing
N Output Inhibit, Module Good &
Remote Sense
EE5H
o
48 - 56 18 4
CC5 48.1 - 62
r
10 2 R Remote Sense only
DD5 42 - 56 15 3 * see conguring guide
o)‘N’optionnotavailable
p)24Vmaxfor900W
q)40Vmaxfor900W
r)60Vmaxfor900W
s)36Vmaxfor900W
t)52Vmaxfor900W
u)15.5Vmaxfor900W
v)‘N’optionnotavailableifmore
than1moduletted
w)500mAminloadbelow1V
x)100mAminimumloadbelow2V