Data sheet
''''DRIW-E16, 24 V AC/DC''''
Page 2/6
P/N
1101501322
EAN 4250184120308
2021/08/09
Technical Data
Supply
Operating voltage 24 V AC/DC -10% ... +10%
Frequency range 50 ... 60 Hz
Duty cycle relative 100 %
Recovery time 400 ms
Inputs
Release time typical 85 ms
Outputs
Contacts 2 changeover contacts
Contact material AgNi
Switching voltage (max.) 250 V
Continuous Current 6 A
Switching frequency 1200 switching cycles/h
Mechanical life 1x10
7
switching cycles
Electrical life 1x10
5
switching cycles
Indicator green and red LED
Insulation coil - contact set
Nominal voltage of the power supply system 230 / 400 V AC
Overvoltage category III | II
Degree of pollution 2 | 2
Rated test voltage 4 kV | 2.5 kV
Type of insulation basic insulation | reinforced insulation
Housing
Dimensions
Dimension (W x H x D) 22.5 mm x 61.3 mm x 60 mm
Dimension (W x H x D) 0.886 in. x 2.413 in. x 2.362 in.
Weight 70 g
Mounting style Standard rail TH35
Mounting position any
Apposition without distance
Connection type Screw type terminal blocks