High Eciency
Optimized for high temperature chilled water applications, the heat
exchanger design increases the overall eciency of precision cooling
systems.
The Electronically Commuted (EC) Fans design provides variable fan
speed control for optimal speeds in real-time according to load changes,
avoiding unnecessary power waste.
Closely couples to IT heat loads and quickly adapts to load changes for
direct and eective heat removal.
High Availability
Supports dual power feed input and is suitable for any tier level of power
reliability architectures.
Thanks to the inherent redundancy design of the fan system, other fans
automatically increase fan speeds to make up for the required airow if
one of the fans malfunctions.
1+1 redundant design of the power modules increases reliability
(applicable to some models).
Hot-swappable power module and fan design allows replacement without
the need of a power shut down while malfunctioning.
The smart group control function is equipped with rotation, back up,
competition free, and soft start functions.
Comprehensive operation monitoring such as chilled water ow and leakage detection allows full control of machine
operations and the ability to take necessary troubleshooting measures in real-time.
High Flexibility
Top or bottom piping and wiring options are available to satisfy the pipeline design needs for dierent data center
requirements.
Multiple communication interfaces satisfy the surveillance and communication needs of a variety of data centers.
High eciency lter (MERV 8) or washable lters (MERV 1) are available for users to choose according to their needs.
Equipped with casters for easy movement and positioning during installation without the need for additional handling tools.
2.4-meter-high models using the 52U rack are also available to customers. (For special height requirements, please
contact your local Delta oce)
The power behind competitiveness
Delta InfraSuite Precision Cooling
RowCool Series 29/43/70/95kW, Chilled Water
Delta’s RowCool CW oers outstanding performance in high temperature chilled water applications via the optimized
design of its heat exchanger. With industry-leading high cooling capabilities, the RowCool CW increases the overall
cooling eciency of data center precision cooling systems. The cooling capacity of a single unit can reach up to 260kW.
The RowCool CW provides the best cooling solutions for data centers over hundreds of kW, focusing on both high
eciency and high density.
Technical Specications
Model CW 29 kW CW 43 kW
HCH1850 HCH1870
Power Input 1-phase 220-240V, 50/60 Hz
Capacity Total Capacity
(*1)
30.8 kW 43.4 kW
Sensible Capacity
(*1)
30.2 kW 43 kW
Total Capacity
(*2)
37.1 kW 50.4 kW
Sensible Capacity
(*2)
37.1 kW 50.4 kW
Total Capacity
(*3)
28.8 kW 36 kW
Sensible Capacity
(*3)
28.8 kW 36 kW
Fan Type EC
Piping Connection Top / Bottom
Conformance CE
Communication RS-485 x 1, Input dry contact x 2, Output
dry contact x 2, SNMP slot x 1
Dimension Width 300 mm 300 mm
Depth 1090 mm 1090 mm
Height 2000 mm 2000 mm
Weight 185 kg 187 kg
*1. Rating capacity is measured at 40.6 DB / 21.6 WB / Inlet water temperature 7.
*2. Maximum capacity is measured at 48.9 DB / 23.9 WB / Inlet water temperature 7.
*3. High temperature water capacity is measured at 40.6 DB / 21.6 WB / Inlet water temperature 12 / Outlet water temperature 20.
Model CW 70kW CW 70kW CW 95kW CW 95kW
HCH1CB0
HCH1CB0 Humidity
Control
HCH1CD0
HCH1CD0 Humidity
Control
Power Input 3-phase 380-415V, 50/60 Hz
Capacity Total Capacity
(*1)
69.3 kW 69.3 kW 92.6 kW 92.6 kW
Sensible Capacity
(*1)
69.3 kW 69.3 kW 91.6 kW 91.6 kW
Total Capacity
(*2)
83.1 kW 83.1 kW 110.7 kW 110.7 kW
Sensible Capacity
(*2)
83.1 kW 83.1 kW 110.7 kW
110.7 kW
Total Capacity
(*3)
57.4 kW 57.4 kW 79.4 kW 79.4 kW
Sensible Capacity
(*3)
57.3 kW 57.3 kW 79.4 kW 79.4 kW
Fan Type EC
Heater Type None Finned tube reheater None Finned tube reheater
Humidier Type None Electrode None Electrode
Piping Connection Top / Bottom
Conformance CE
Communication RS-485 x 1, Input dry contact x 2, Output dry contact x 2, SNMP slot x 1
Dimension Width 600 mm 600 mm 600 mm 600 mm
Depth 1090 mm 1090 mm 1090 mm*4 1090 mm*4
Height 2000 mm 2000 mm 2000 mm 2000 mm
Weight 368 kg 375 kg 415 kg 422 kg
*1. Rating capacity is measured at 40.6 DB / 21.6 WB / Inlet water temperature 7.
*2. Maximum capacity is measured at 48.9 DB / 23.9 WB / Inlet water temperature 7.
*3. High temperature water capacity is measured at 40.6 DB / 21.6 WB / Inlet water temperature 12 / Outlet water temperature 20.
*4. Depth is 1200 mm for top piping model.
All specications are subject to change without prior notice.
Rear View
Hot-swappable fans
Power Supply Redundancy
Disposable Filter