Eight Channel Digital
Hydrometer Kit
Eight Channel Digital Hydrometer Kit
DESCRIPTION
The digital hydrometer kit accurately and quickly
determines specific gravity of flooded cells. Simply draw
the electrolyte into it; the specific gravity and temperature
are determined in five seconds. It provides memory for
both temperature and specific gravity for eight tests of
256 cells each. The stored data can be easily transferred to
the accompanying data-logger. The data-logger can hold
8 separate sets of test data. The data can then be easily
imported directly into a Megger Power DB battery report
from the data-logger.
SPECIFICATIONS
DMA 35
Measuring range
Density: 0 g/cm³ to 3 g/cm³
Temperature: 0 °C to 40 °C (3°F to
104°F)*
Viscosity: 0 mPa·s to 1000 mPa·s
Accuracy
Density: 0.001 g/cm³ **
Temperature: 0.2 °C (0.4 °F)
Repeatability, s.d.
Density: 0.0005 g/cm³
Temperature: 0.1 °C (0.2 °F)
Ambient temperature
-10 ��C to +50 °C (14 °F to 122 °F)
Supported measuring units
Specific gravity
Alcohol tables
Sugar/extract tables
API functions
H2SO4 tables
Ten programmable custom functions
Sample volume
2 mL
Dimensions (L x W x H)
140 mm x 138 mm x 27 mm
(5.5 x 5.4 x 1.0 inches)
Data memory
1024 measured results
Power supply
Two 1.5 V alkaline batteries
Weight
345 g (12.2 ounces)
Intrinsically safe
no
* Filling at higher temperatures possible
** Viscosity < 100 mPa·s, density < 2 g/cm³
*** Sample must not freeze within the measuring cell
n
Measure Electrolyte Specific Gravity and
Temperature
n
5 Second Measurements
n
Save up to 8 tests in the 8 channel data
logger
n
Import the specific gravity data directly
into Power DB
Eight Channel Digital Hydrometer Kit
UK
Archcliffe Road, Dover
CT17 9EN England
T +44 (0) 1 304 502101
F +44 (0) 1 304 207342
UKsales@megger.com
UNITED STATES
4271 Bronze Way
Dallas, TX 75237-1019 USA
T 1 800 723 2861 (USA only)
T +1 214 333 3201
F +1 214 331 7399
USsales@megger.com
OTHER TECHNICAL SALES OFFICES
Valley Forge USA, College Station
USA, Sydney AUSTRALIA, Täby
SWEDEN, Ontario CANADA, Trappes
FRANCE, Oberursel GERMANY, Aargau
SWITZERLAND, Kingdom of BAHRAIN,
Mumbai INDIA, Johannesburg SOUTH
AFRICA, and Chonburi THAILAND
ISO STATEMENT
Registered to ISO 9001:2000 Cert. no. 10006.01
HYDROKIT_DS_en_V01
www.megger.com
Megger is a registered trademark
ORDERING INFORMATION
Item (Qty) Cat. No.
Hydrometer Kit 2001-692
Includes:
Anton Paar Hydrometer
8 Channel Data Logger
Custom Carrying Case
Communications Cable
Software CD
Hydrometer data logger kit - For use with Anton Paar Hydrometers 2001-693
Includes:
8 Channel Data Logger
Custom Carrying Case
Communications Cable
Software CD
ERRATA Sheet (Configuration Instructions)
BATTERY TEST
1
1
10/11/2012 6:34 AM
Production Floor
LEAD ANTIMONY
25
°C
%
30
ASSET ID
HUMIDITY
AMBIENT TEMP.
JOB #
DATE
PAGE
POSITION
SUBSTATION
Repair Alcove
EQUIPMENT LOCATION
10750, REVISED 12/4/2014COPYRIGHT © 2002-2014 POWERDB, INC.
w
ww.powerdb.com
TESTED BY:TEST EQUIPMENT USED: Darryl Evans
1for
DUTY CYCLE: 17.8
Amps
STRING NAME:
NUMBER OF STRAPS:
1to
LEAD ANTIMONY
23
1.88
1
7/10/2012
/1
VPC
24
Hours
NUMBER OF CELLS / JAR:
HYDROMETER. START/SKIP CELLS:
NOMINAL: 2.2VOLTS PER CELL:
NUMBER OF CELLS:
STRING
NSTALLATION DATE:
Show Battery Equipment Inspection Show NERC Charger Nameplate Show Second NERC Charger NameplateShow Second Charger
Amps
Volts
EQUALIZATION VOLTAGE: Volts
MANUFACTURER:
MODEL:
TEST AC CURRENT:
CHARGER
CHARGER CURRENT:
CHARGER VOLTAGE:
BATTERY FLOAT CURRENT:
BATTERY RIPPLE CURRENT:
DIAGRAM:
2.3
V
ARIATION WARNING (%):
VARIATION ALARM (%):
10.0
20.0
D
EVIATION WARNING (%):
DEVIATION ALARM (%):
15.0
20.0 CHANGE ALARM (%):
C
HANGE WARNING (%): 5.0
10.0
STRAP WARNING (%):
STRAP ALARM (%): 20.0
LIMITS:
10.0
L
OW VOLTAGE LIMIT (V):
HIGH VOLTAGE LIMIT (V):
2.2
IMPEDANCE (milli-ohms)
NOTES
VALUE
% DEVIATION
(Baseline)
% VARIATION
(String)
% CHANGE
(Prev.)
VOLTAGE
(volts)
TIME MODEL
SPECIFIC
GRAVITY
#
CELL DATAJAR DATA
#
2.21Min. Voltage:2.67 Total String Voltage: Dev. from Charger: 0.2 % 2.1752.87
TEMP.
Milli-OhmsDisplay Impedance:
2.6743Baseline Impedance: Avg. Impedance: Max. Voltage: Avg. Temp: 70.1
2.591 2.201 1 1.214 70.506:35-2.91 -3.1
2.686 2.195 206:360.72 0.4
2.647 2.204 3 1.214 70.306:37-0.83 -1.0
2.667 2.208 406:380.04 -0.3
2.721 2.200 5 1.214 70.406:392.05 1.7
2.500 2.211 606:40-6.36 -6.5
2.592 2.201 7 1.213 70.406:40-2.87 -3.1
2.774 2.210 806:414.08 3.7
2.652 2.205 9 1.214 70.306:42-0.69 -0.8
2.657 2.209 1006:43-0.410 -0.6
2.636 2.206 11 1.214 70.306:44-1.211 -1.4
2.616 2.213 1206:45-1.912 -2.2
Power DB Battery report with imported hydrometer data.