Battery specication / Fiche technique
Part No: AMP9020
AGM LEAD ACID BATTERY
2.3-12 General Purpose TU
MAIN INFORMATION / INFORMATIONS GÉNÉRALES
TECHNICAL INFORMATION / INFORMATIONS TECHNIQUES
BRAND / MARQUE NX
TECHNOLOGY / TECHNOLOGIE AGM Lead acid
NOMINAL VOLTAGE / TENSION NOMINALE 12V
NOMINAL CAPACITY / CAPACITÉ NOMINALE 2.3Ah (20hr)
DIMENSIONS ( ± 2 mm) / DIMENSIONS ( ± 2 mm)
• Length / Longueur 182 ± 2mm (7.17 inches)
• Width / Largeur 24 ± 2mm (0.94 inches)
• Height / Hauteur 62 ± 2mm 5 (2.44 inches)
• Total height with terminals / Hauteur totale (avec cosses) 62 ± 2mm (2.44 inches)
WEIGHT ( ± 2 %) / POIDS ( ± 2 %) Approx 0.78Kg
TERMINAL / TYPE DE COSSES TU
CASING / TYPE DE BAC UL94 HB (Standard ABS)
COLOUR / COULEUR DE BAC Black top and black case
FLOAT SERVICE LIFE / DURÉE DE VIE EN CHARGE PERMANENTE 5 years (20°C)
CAPACITY / CAPACITÉ 2.3Ah (20hr,1.80V/cell,25°C/77°F)
2.2Ah (10hr,1.80V/cell,25°C/77°F)
2.0Ah
(5hr,1.75V/cell,25°C/77°F)
1.4Ah (1hr,1.75V/cell,25°C/77°F)
MAX DISCHARGE CURRENT / COURANT DE DÉCHARGE 11.5A (5s)
MAX CHARGING CURRENT / COURANT DE CHARGE 0.69A
INTERNAL RESISTANCE / RÉSISTANCE INTERNE Approx 65mΩ
OPERATING TEMPERATURE RANGE / PLAGE DE TEMPÉRATURE -15°~50°C (5 ~122°F)
FLOAT CHARGING VOLTAGE / TENSION DE CHARGE EN FLOATING (25°C) 13.60 to 13.80V
CYCLIC CHARGING VOLTAGE / TENSION DE CHARGE EN CYCLAGE (25°C) 14.50 to 14.90V
SELF DISCHARGE / AUTO-DECHARGE (25°C) Remaining Capacity: 91% (3 months)
Remaining Capacity: 82% (6 months)
Remaining Capacity: 65% (12 months)
NOMINAL OPERATING TEMPERATURE / TEMPÉRATURE D’UTILISATION 25 ± 3°C (77 ± 5°F)
CAPACITY VS TEMPERATURE / CAPACITÉ SELON LA TEMPÉRATURE 40°C (104°F) 102%
25°C (77°F) 100%
0°C (32°F) 85%
APPLICATIONS
All purpose / Tout usage
UPS / Onduleur
Emergency light / Éclairage de secours
Railway signal / Signalisation ferroviaire
Alarm and security system / Alarme et securité
Aircraft signal / Signal d’avion
Electronic devices and equipment / Appareils et équipements électroniques
Emergency backup / Alimentation de secours
Power supply / Réserve d’énergie
n Terminal
Unité : mm / Unit: inches
AGM
General
purpose
AGM
standby
AGM
ups
AGM
cyclic
AGM
long life
OUTLINE SAFETY WARNING: USE ONLY WITH IN THE ALLOWED PARAMETERS. Do not short circuit or over-load the battery. Charge only using an approved charger designed specically to charge this battery. Do not heat above maximum temperatures indicated. Never
crush, mutilate, puncture or abuse the battery. Do not dismantle the pack or disable any of the protective devices or circuits. DO NOT USE THE BATTERY IF YOU SUSPECT IT MAY BE FAULTY OR DAMAGED.
© Copyright Enix Energies 2005. NB: This document and the product design are the intellectual property of Enix Energies. No document or design may be copied or used for commercial purposes without written permission of Enix Energies. Users must satisfy themselves, by means of
testing etc, that products are suitable for their application. Data in this document is for general guidance only; consult cell manufacturers data for denitive information. Information is given free of charge and in good faith, but no responsibility can be accepted for any errors or omission
or costs or losses or liabilities arising from the use of this information. All business is conducted to Enix Energies terms and conditions only.
www.enix-energies.com
•
Date: 2018/011/09
l 1/2
TMD 1 Description, classe : UN 2800 – accumulateurs inversables remplis d’électrolyte liquide, 8, none, (E))
ADR : Not regulated IMDG Not regulated
IATA : Exempt Procédure TMD PROC 2 : UN 2800