Remove protective wrapping on
panel end of cable. On this end of the
cable, there is no convoluted tubing;
otherwise, the procedure is the same as
just done for the lead end of the cable.
6
FASTENER
26668-A
7 9
Install cable mounting
bracket on rack
Select version needed based
on installation space
considerations.
8
Install the cable on the cable bracket.
Secure the trunk cable fanout to the bracket
using cable ties as shown.
Install the cable in fiber panel
Follow the steps described below to thread cable
into panel and secure it in side plate.
PRODUCT PATENTS: https://www.commscope.com/ProductPatent/ProductPatent.aspx PRODUCT INFORMATION AND TECHNICAL SUPPORT: http://www.commscope.com/SupportCenter
EHD
PANEL
SECURE USING
#12-24 OR
M6 SCREWS
AND LOCK
WASHERS
RACK
760239859
UMB-RMB-LG
760239861
UMB-CMB-LG
Brackets sold
separately;
not provided
with cable.
NOTE:
NOTE:
This document
shows the cable
being installed
with a CommScope
EHD panel.
© 2018, CommScope, Inc. All Rights Reserved.
TC-96247-IP Rev A May 2018
3a
3b
Unfasten and remove panel cover;
and remove gland adapter moldings
from panel
side plate.
Carefully insert MPO connectors into
panel side plate opening.
3c
3d
Pull connectors across into inner area
of the fiber panel.
Continue feeding the connectors into the
fiber panel and position the trunk cable
collar to lock it into the panel side plate.
3f
Lock the collar into the side panel and
loop the cable within the fiber panel.
Install the panel cover on the fiber panel
and secure the fasteners.
ee
REMOVE GLAND
ADAPTER MOLDINGS
FROM TRUNK
SIDE PLATE
3g
Terminate the trunk cable connectors
within the fiber panel following
instructions provided with panel.