Panduit
®
StructuredGround
Telecommunications Bonding
Increases reliability by minimizing the risk to network equipment
and interconnecting cabling from electrical hazar
ds
Facilitates communications by improving immunity fr
om
electromagnetic interference (EMI)
Complete solution available, designed for 
exibility and ease of
installation with virtually any racks or cabinets
*One ESD wrist strap port can be used effectively for up to three open-faced racks, however it is recommended to use one port for
each enclosed cabinet because the doors may interfere.
Five Steps to Bonding Data Centers and Telecommunications Spaces
Part Number Part Description Quantity Required
RGESD2-1
ESD wrist strap docking port kit for threaded rail racks and cabinets (#12-24 and M6). 1 per rack with
active equipment*
RGESD2B-1
ESD wrist strap docking port kit for cage nut rail racks and cabinets. 1 per rack with
active equipment*
RGESDWS
Wrist strap with 6' (2M) coil cord. 1 per ESD wrist strap
docking port kit*
Step 1. Protect against electrostatic discharge (ESD)
Part Number Part Description Quantity Required
For equipment with a grounding pad (e.g. core switch es), use an equipment jumper to bond the equipment to the rack
or busbar.
RGEJ657PFY
Equipment jumper kit (also known as a Unit Bonding Conductor); 57" (1.4M);
#6 AWG (16mm
2
) jumper; pre-terminated on one end.
1 per piece
of equipment
CNBK
Bonding cage nut for cage nut rail racks and cabinets. 1 per piece
of equipment
For equipment that bonds through its mounting fl anges (no grounding pad) (e.g. top of rack switches), use bonding
hardware to connect the equipment to the rack.
RGTBSG-C
Bonding screw for threaded rail racks. 1 per piece
of equipment
CNBK
Bonding cage nut for cage nut rail racks and cabinets. 1 per piece
of equipment
Step 2. Bond the equipment to the rack or cabinet
Part Number Part Description Quantity Required
RGRB19Y
Busbar for threaded rail racks and cabinets; provided with thread-forming screws. 1 per rack
RGRB19CN
Busbar for cage nut rail racks and cabinets; provided with bonding studs for cage
nut applications.
1 per rack
Step 3. Ensure the rack or cabinet is electrically continuous
Use a busbar to bond the vertical equipment mounting rails together to create continuity in racks/cabinets. A busbar can also be used to
bond multiple equipment jumper kits to a single rack unit (RU).
All Panduit racks and cabinets are designed to be electrically continuous, so they do not require a busbar bonded to the rails.
Part Number Part Description Quantity Required
For small installations with only a few racks/cabinets, bond racks/cabinets directly to the TGB using a
Telecommunications Equipment Bonding Conductor (TEBC).
GJ672UH
TEBC; 72" (1.8M); #6 AWG (16mm
2
) jumper; pre-terminated on both ends.
1 per rack
GJ696UH
TEBC; 96" (2.4M); #6 AWG (16mm
2
) jumper; pre-terminated on both ends.
GJ6120UH
TEBC; 120" (3.0M); #6 AWG (16mm
2
) jumper; pre-terminated on both ends.
GJ6144UH^ TEBC; 144" (3.7M); #6 AWG (16mm
2
) jumper; pre-terminated on both ends.
GJ6168UH
TEBC; 168" (4.3M); #6 AWG (16mm
2
) jumper; pre-terminated on both ends.
GJ6192UH
TEBC; 192" (4.9M); #6 AWG (16mm
2
) jumper; pre-terminated on both ends.
GJ6216UH
TEBC; 216" (5.5M); #6 AWG (16mm
2
) jumper; pre-terminated on both ends.
GJ6240UH
TEBC; 240" (6.1M); #6 AWG (16mm
2
) jumper; pre-terminated on both ends.
GJ6264UH
TEBC; 264" (6.7M); #6 AWG (16mm
2
) jumper; pre-terminated on both ends.
GJ6288UH
TEBC; 288" (7.3M); #6 AWG (16mm
2
) jumper; pre-terminated on both ends.
HDW1/4-KT
Stainless steel hardware for the TGB and thread-forming screws for the rack. 1 per TEBC
CNBK
Bonding cage nut for cage nut rail racks and cabinets. 2 per jumper
GB2B0306TPI-1
TGB; 1/4" x 2" x 12". 1 per room
For large installations, like a computer room, use Rack Bonding Conductors (RBC) for bonding individual racks and
cabinets to a Supplemental Bonding Grid (SBG, a.k.a. MCBN)
RGCBNJ660P22
RBC; 60" (1.5M); #6 AWG (16mm
2
) jumper; provided with HTAP connector for #6
AWG – #2 AWG (16mm
2
– 25mm
2
) SBG.
1 per rack
CNBK
Bonding cage nut for cage nut rail racks and cabinets. 2 per jumper
HTCT250-2-1
HTAP for bonding 1/0 TGB conductor to #6 AWG – #2 AWG SBG. 1 per TGB
LCC1/0-14AW-X
Two-hole copper compression lug for bonding 1/0 conductor to TGB. 1 per TGB
HDW1/4-KT
Stainless steel hardware for bonding the two-hole copper compression lug to the TGB. 1 per TGB
GPQC07-1/0
Access fl oor bonding clamp; works with round pedestals:
3/4" (19.1) – 7/8" (22.2mm).
Use one connector
wherever SBG
conductors cross one
another
GPQC10-1/0^ Access fl oor bonding clamp; works with square pedestals: 7/8" (22.2mm),
works with round pedestals: 1" (25.4mm) – 1 1/8" (28.6mm).
GPQC15-1/0
Access fl oor bonding clamp; works with square pedestals: 7/8" (22.2mm), works with
round pedestals: 1 1/2" (38.1mm).
GB2B0306TPI-1
TGB; 1/4" x 2" x 12". 1 per room
Part Number Part Description Quantity Required
Bond the pathway to the TGB.
GACB-2
Bonding bracket; 1.63" (41.4mm) width, 3.95" (100.3mm) height, 5.22" (132.6mm)
depth; provided with one mounting screw.
1 per pathway
GACB-3
Bonding bracket; 1.88" (47.6mm) width, 4.58" (116.3mm) height, 5.29" (134.4mm)
depth; provided with one mounting screw.
GACBJ618U
Jumper for bonding bracket to the TGB; 18.0" (457mm) length; #6 AWG (16mm²);
pre-terminated on both ends with straight, two-hole, long barrel compression lugs;
provided with .16 oz. (5cc) of antioxidant and four mounting screws.
1 per pathway
HDW1/4-KT
Stainless steel hardware for bonding the GACBJ618U to the TGB. 1 per pathway
Bond pathway sections together.
GACB-2
Bonding bracket; 1.63" (41.4mm) width, 3.95" (100.3mm) height, 5.22" (132.6mm)
depth; provided with one mounting screw.
2 per bond
GACB-3
Bonding bracket; 1.88" (47.6mm) width, 4.58" (116.3mm) height, 5.29" (134.4mm)
depth; provided with one mounting screw.
GACBJ618U
Jumper for bonding pathway sections; 18.0" (457mm) length; #6 AWG (16mm²); pre-
terminated on both ends with straight, two-hole, long barrel compression lugs; provided
with .16 oz. (5cc) of antioxidant and four mounting screws.
1 per bond
Bond alternate wire basket sections.
SBC3-C
Copper split bolt #4 STR – #8 STR. 2 per bond
Step 5. Bond nearby conductive items, such as pathways, to the TGB
^Most popular product.
©2013 Panduit Corp.
ALL RIGHTS RESERVED.
Printed in the U.S.A.
GRFL02--SA-ENG
7/2013
For more information
Visit us at www.panduit.com
Contact Customer Service by email: cs@panduit.com
or by phone: 800.777.3300
All Panduit pathway systems are designed to be electrically continuous, so they do not require bonding of sections.
Step 4. Bond the rack or cabinet to the Telecommunications Grounding Busbar (TGB)