Industry’s smallest fused disconnect
offers superior circuit protection
New snap-together,
modular photovoltaic
ferrule fuse blocks
speed up installation,
increase exibility
and enhance safety.
Product description:
Eaton’s Bussmann
®
series
ferrule fuse blocks feature a
modular, low prole design
that allows assembly of the
required poles at point of
use.
The industry-rst open style
PV fuse blocks are available
for 10x38mm (13/32” x
1-1/2”) photovoltaic fuses.
They are available in
1-, 2- and 3-pole
congurations and feature
a compact footprint,
consuming minimal panel
space.
Additionally, their low
temperature rise makes
them ideal for installation in
high ambient environments.
Features and benefits:
• Listed to UL 4248-18
for photovoltaic
applications.
• Modular, snap-together
design provides tool-less
assembly of multiple
pole blocks to save
inventory and reduce
assembly time.
• DIN-Rail and panel
mount versatility allows
one product to be used
for multiple applications
and lowers inventory
cost.
• Optional see-through
cover enhances safety
with IP20 nger-safe
protection, lockout/
tagout capability and
open circuit indication.
• Easy circuit identication
with available universal
marker labels for fuse
block covers.
BUSSMANN
SERIES
1000Vdc modular ferrule fuse blocks for
photovoltaic applications
Modular PV fuse blocks simplify design
and installation while reducing footprint
Eaton is a registered trademark.
All other trademarks are property
of their respective owners.
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
Bussmann Division
114 Old State Road
Ellisville, MO 63021
United States
Eaton.com/bussmannseries
© 2015 Eaton
All Rights Reserved
Printed in USA
Publication No. 10308
July 2015
Clear IP20 nger-safe cover
with optional indication
Enhanced safety
Speeds troubleshooting
Fully modular design
Fewer SKUs to manage
Lower inventory cost
Table 1. Terminal specifications
Terminal
type
Wire
range
Wire temp
rating
Torque
AWG Ib-in (N•m)
Box lug
(“CR” Option)
CU 2-14,
AL 2-8
75/90°C
CU 2-3 50 (5.6)
CU 4-6 45 (5.1)
CU 8-14 35 (4.0)
AL 2-6 50 (5.6)
AL 8 40 (4.5)
Screw (S) CU 10-18 75/90°C 10-18 20 (2.3)
Table 2. Recommended covers
Cover part numbers
Indicating Non indicating
CVRI-CCM CVR-CCM
Table 3. Catalog numbers
Terminal type
Poles Fuse class#10-32 Phil-slot screw Box lug
BPVM-1S BPVM-1C 1 10x38 (13/32” x 1-1/2”) gPV and PV
BPVM-2S BPVM-2C 2 10x38 (13/32” x 1-1/2”) gPV and PV
DIN-Rail and panel mount
exibility
More mounting exibility
Easier to install
Compact footprint
Consumes less panel space
Specifications
Ratings:
• Volts 1000Vdc
• Amps up to 30A
• Withstand 33kA
Agency information:
• UL Listed E348242-IZMR
• CSA Component Acceptance
47235-6225-01
• RoHS compliant
Flammability ratings:
• Blocks — UL 94V0,
self-extinguishing
• Covers — UL 94HB,
self-extinguishing
Materials:
• Base — Thermoplastic
• Terminals — Tin-plated bimetallic
copper
• Covers — Thermoplastic
Patented lockout/tagout
Enhanced safety
Ease of maintenance
Universal marker label
Ease of circuit identication
Test probe holes
Ease of maintenance
Operating and storage temperature
range:
• Blocks -40°C to +120°C
• Non indicating covers
-40°C to +120°C
• Indicating covers
-20°C to +90°C
Wire:
• Box lug terminal — CU/AL, 75/90°C
• All other terminals — CU, 75/90°C