3-PHASE FILTERS
Specications are subject to change. Consult factory to verify specications.
For more information on our lter products call us at: +1.908.850.5088 or Toll Free at +1.866.641.3310
LCR, Radius Power, and Filter Concepts are now part of Astrodyne TDI
www.AstrodyneTDI.com
Note: Use any combination of -Y with any -X (Amps) rating
e.g. RP380-100-100-S (100 Amps with 100 nF Ycap)
Specications
Electrical Schematic
15 A to 300 A, 600 V
RP380 Series
3-Phase Delta Power Line Filters, 600V
Y-cap, nF
mA,
600 V/60 Hz
0 0.0
10 0.15
100 1.5
1000 15.0
2000 25.0
Leakage Current
Operating Frequency 50/60 Hz
Usable Frequency DC - 400 Hz
Max. Operating Voltage 600 V +10%
Ambient Temperature -25 to 50°C
Climatic Category 25/100/21
Hipot Rating (L-G) 3800 VDC
Terminals (-T)
S: 15/30/50 A (M5)
80/100 A (M6)
150/200 A (M10)
300 A (M12)
Safety Approvals cURus, EN60939
RP380
-X
(Amps)
-Y
(Ycap, nF)
-T
Typ. Weight,
lbs (kg)
15 0 S 5.0 (2.3)
30 10 5.0 (2.3)
50 100 5.0 (2.3)
80 1000 9.0 (4.1)
100 2000 18.0 (8.2)
150 18.0 (8.2)
200 18.0 (8.2)
300 35.0 (16.0)
Part Number/Ordering
3-PHASE FILTERS
Specications are subject to change. Consult factory to verify specications.
For more information on our lter products call us at: +1.908.850.5088 or Toll Free at +1.866.641.3310
LCR, Radius Power, and Filter Concepts are now part of Astrodyne TDI
www.AstrodyneTDI.com
15 A to 300 A, 600 V
RP380 Series
3-Phase Delta Power Line Filters, 600V
Freq (MHz) 0.15 0.5 1.0 10 30
15/30 Amp
CM(dB) 55 65 65 52 40
DM(dB) 55 65 70 70 60
50 Amp
CM(dB) 50 65 65 52 40
DM(dB) 50 60 65 70 55
80 Amp
CM(dB) 45 55 55 50 40
DM(dB) 50 55 60 50 30
100 Amp
CM(dB) 60 65 65 50 30
DM(dB) 50 60 60 50 30
150 Amp
CM(dB) 55 60 60 50 30
DM(dB) 45 55 60 50 30
200 Amp
CM(dB) 50 55 55 45 30
DM(dB) 45 55 55 50 30
300 Amp
CM(dB) 50 55 55 42 30
DM(dB) 45 50 50 40 30
Typical Insertion Loss, dB (50/50 Ohm)
Mechanical Dimensions
TYPICAL TOLERANCE: +/-0.02” (0.50 mm)
15/30/50 Amp
80 Amp
100/150/200 Amp
300 Amp