TEMPEST/COTS AC EMI Power Line Filter
RPT5500
TEMPEST/ COTS TO 35A
PERFORMANCE TO 10GHZ
100dB
RPT5500
-X
(Amps)
-T
Weight
LBS (KG)
Typ.
5 S 3.2 (1.5)
10 3.2 (1.5)
15 6.0 (2.7)
25 6.0 (2.7)
30 6.0 (2.7)
35 6.0 (2.7)
PART NUMBER/ ORDERING
RADIUS POWER
Your Power Partner
RP
RPT5500 Series
SCHEMATIC
177
Operating Freq. : 50/60/400Hz
Max. Operating Voltage : 300VAC
Ambient Temperature : -40 to 70C
Hipot Rating (L-G) : 1500VDC
Terminals (-T) : S: M5
Applications : TEMPEST/Mil-461/
DO-160
Leakage Current : 3.5mA/ Line
(250V/60Hz)
Note:
Call for other termination types (e.g. Circular Mil
Connectors, etc.)
Leakage current is directly related to the line-ground
caps in the lter. If higher leakage current is al-
lowed, the caps can be increased to improve the low
frequency insertion loss
SPECIFICATIONS
Typical CM Insertion Loss, 50ohm
14KHz 20dB
100KHz 60dB
500KHz 80dB
1MHz-10GHz 100dB
Reference purposes only.
Specications are subject to change.
Consult factory to verify specications.
www.astrodyne.com
Email:Emiltercs@astrodyne.com
www.radiuspower.com
RADIUS POWER
Your Power Partner
RP
RPT5500
Mechanical Dimensions
178
5/10/Amp
15/25/30/35Amp
TYPICAL TOLERANCE: +/-0.02 (0.50)
Reference purposes only.
Specications are subject to change.
Consult factory to verify specications.
www.astrodyne.com
Email:Emiltercs@astrodyne.com
www.radiuspower.com