WIREMOLD
®
Surface Style Poke-Thru Devices
Bring Power & Communication Services
Directly to the Workstation
Flush Style Poke-Thru Devices are an excellent solution for
bringing power, communication, and audio/video services
to the workstation in an open space, above-grade floor
environment. All Wiremold Flush Style Poke-Thru Devices come
with built-in TopGuard
protection, an industry-leading design
that meets and exceeds UL scrub water exclusion requirements
for tile and carpet floors. Topguard protection prevents water, dirt,
or debris from entering not just the power devices, but also the
communication devices.
All Wiremold Flush Style Poke-Thru Devices can be installed
on tile, carpet, or wood covered floors. Each of these devices
provides an excellent solution for both new or retrofit construction,
with typical applications that include office buildings, airports,
malls, shopping centers, libraries, and schools.
F E A T U R E S & B E N E F I T S
O
AV3 Series is specifically designed to meet the
grow
ing
needs of the audio and video market. AV3
Series accepts
Extron
®
MAAP Series mini architectural
adapter plates.
The MAAP line includes passive A/V connector
plates that
support a wide variety of video, audio, control, voice
and data
connectors, as well as active modules such as VGA
line
drivers, audio buffers and twisted pair transmitters. (Extron
devices sold separately only through authorized Extron dealers.)
O
AMD8 Series is designed to meet the growing need for
more communication capacity at the workstation.
AMD8
Series is a large capacity all communication poke-thru
device, providing up to 8-ports for communication
devices.
AMD8 is a flush style device with individual slide
covers
to prevent water, dirt and debris from entering the
communication devices.
O
TopGuard Protection. Integral design component that prevents
water, dirt and debris from entering power and communication
compartments. Whenever you see the TopGuard protection
icon on any Wiremold product, you’ll know it meets and
exceeds UL scrub water exclusion requirements for tile and
carpet floors.
O
UL Listed and UL Fire Classified to U.S. and Canadian
safety standards for tile and terrazzo. Includes the new
UL requirements under UL514A and UL 514C for the scrub
water exclusion test for carpet and wood covered floors.
O
Multiple
service capability. RC7, AV3, and RC4 Series
provide
power and communication services. The AV3 and RC4
Series
provide for use of flush or recessed fiber optic devices.
Eliminates
the cost of a second poke-thru to accommodate
additional services.
O
Provides flexibility with a single poke-thru unit. 20A duplex
receptacle in the AV3, and the RC7 Series can be wired as
standard or isolated ground receptacle. Two 20A duplex power
receptacles in the RC4 Series are wired with a 6-wire system
with individual neutral and ground wires, and can be wired for
standard or isolated ground. RC9 quad 15A receptacle can
also be wired as standard or isolated ground receptacle.
O
Individual slide covers. Protects power and communication
devices. Power slide covers snap back into place when
receptacle is not in use. Activate either power or communication
services, simultaneously or individually. RC9AMD and AMD8
Series Poke-Thru Devices are the only all communication poke-
thru devices available with slide cover protection.
O
Datacom connectivity options. Accepts industry standard
and proprietary devices from a wide range of manufacturers
to provide a seamless and aesthetically pleasing interface for
voice, data, audio, and video applications at the point-of-use.
O
“Step-on-it” installation. Quick and easy installation without
the need for additional fasteners or a second installer.
O
Suitable for use in air handling plenums. In accordance with
Sec 300-22(C) of the National Electrical Code.
O
Meets ADA Accessibility Guidelines. Wide trim flange on the
product is designed to meet the ADA Accessibility Guidelines
as it pertains to ADA Standard 4.5 which addresses changes
in floor and ground surface levels. The poke-thru trim flanges
are beveled so the slope is no greater than 1:2 ratio.
O
Fire rated for up to 2-hour rated floors. Maintains the fire
classification of the floor.
ED1215R13 Updated April 2016 For latest specs visit www.legrand.us/wiremold
RC7 Series
AV3 Series
RC4 Series
AMD8 Series
Protection from
water, dirt,
and debris.
2
Flush Poke-Thru Device Specifications
MAXIMUM
COPPER FILL
FEED
CHANNELS
RC7 Series
Minimum: 3 1/16" (78mm)
Maximum: 3 1/8" (79mm)
1-, 1 1/2- & 2-hrs
2 Gangs (1) 20A Duplex
Receptacle, (2) Ports of
Communication Devices
(3) #12 AWG
.01536 Sq. in. (9.91 sq. mm)
(1) Cat 6A/Channel
.004 Sq. in. (2.58 sq. mm)
3/4" Trade Size
1/2" Trade Size/Channel
(2) Channels per unit
7" (178mm)
Black, Brass, Aluminum,
Gray, Ivory
Carpet, Tile & Wood
Minimum:
1/8" (3.2mm)
Maximum:
3/4" (19.1mm)
Minimum: 3 1/16" (78mm)
Maximum: 3 1/8" (79mm)
1-, 1 1/2- & 2-hrs
2 Gangs (1) 15A Quad
Receptacle, (2) Openings for
Communication Pass-Through
(3) #12 AWG
.01536 Sq. in. (9.91 sq. mm)
(1) Cat 6A/Channel
.004 Sq. in. (2.58 sq. mm)
3/4" Trade Size
1/2" Trade Size/Channel
(2) Channels per unit
7" (178mm)
Black, Brass, Aluminum,
Gray, Ivory
Carpet, Tile & Wood
Minimum:
1/8" (3.2mm)
Maximum:
3/4" (19.1mm)
Minimum: 3 1/16" (78mm)
Maximum: 3 1/8" (79mm)
1-, 1 1/2- & 2-hrs
2 Gangs (4) Ports of
Communication Devices
N/A
(4) Cat 6A/Channel
.01600 Sq. in. (10.324 sq. mm)
N/A
2" Trade Size
7" (178mm)
Black, Brass, Aluminum,
Gray, Ivory
Carpet, Tile & Wood
Minimum:
1/8" (3.2mm)
Maximum:
3/4" (19.1mm)
RC9 Series RC9AMD Series
3" Diameter Hole
POKE-THRU SERIES
HOLE SIZE
UL FIRE CLASSIFICATION
CAPACITY
POWER*
COMMUNICATIONS*
POWER
COMMUNICATIONS
COVER SIZE
COVER COLORS
APPROVED CONCRETE
FLOOR COVERINGS
FLOOR COVERING
THICKNESS
MAXIMUM
COPPER FILL
FEED
CHANNELS
AV3 Series
Minimum: 4" (102mm)
Maximum: 4 1/8" (105mm)
1-, 1 1/2- & 2-hrs
2 Gangs (1) 20A Duplex
Receptacle, (3) Single Width
Extron MAAP Devices or (4)
Ports of Communications
(3) #12 AWG
.01536 Sq. in. (9.91 sq. mm)
(6) Cat 6A/Channel
.01938 Sq. in. (12.503 sq. mm)
3/4" Trade Size
1 1/4" Trade Size/Channel
8 1/4" (210mm)
Black, Brass, Aluminum,
Gray, Ivory
Carpet, Tile & Wood
Minimum:
1/8" (3.2mm)
Maximum:
3/4" (19.1mm)
Minimum: 4" (102mm)
Maximum: 4 1/8" (105mm)
1-, 1 1/2- & 2-hrs
1 Gang All Communications,
(8) Ports for Communication
Devices
N/A
(10) Cat 6A/Channel
.03474 Sq. in. (22.412 sq. mm)
3/4" Trade Size
1 1/4" Trade Size/Channel
8 1/4" (210mm)
Black, Brass, Aluminum,
Gray, Ivory
Carpet, Tile & Wood
Minimum:
1/8" (3.2mm)
Maximum:
3/4" (19.1mm)
Minimum: 4" (102mm)
Maximum: 4 1/8" (105mm)
1-, 1 1/2- & 2-hrs
2 Gangs (2) 20A Duplex
Receptacles, and (4) ports of
Communication Devices
(6) #12 AWG
.03072 Sq. in. (19.82 sq. mm)
(2) Cat 6/Channel
.008 Sq. in. (5.16 sq. mm)
3/4" Trade Size
3/4" Trade Size (Equivalent)
Oval Shaped Opening
8 1/4" (210mm)
Black, Brass, Aluminum,
Gray, Ivory
Carpet, Tile & Wood
Minimum:
1/8" (3.2mm)
Maximum:
3/4" (19.1mm)
AMD8 Series
RC4 Series
4" Diameter Hole
POKE-THRU SERIES
HOLE SIZE
UL FIRE CLASSIFICATION
CAPACITY
POWER*
COMMUNICATIONS*
POWER
COMMUNICATIONS
COVER SIZE
COVER COLORS
APPROVED CONCRETE
FLOOR COVERINGS
FLOOR COVERING
THICKNESS
Minimum: 4" (102mm)
Maximum: 4 1/8" (105mm)
1-, 1 1/2- & 2-hrs
2 Gangs (1) 20A Duplex
Receptacle, and (4) Ports for
Communication devices
(3) #12 AWG
.01536 Sq. in. (9.91 sq. mm)
(2) Cat 6/Channel
.008 Sq. in. (5.16 sq. mm)
3/4" Trade Size
3/4" Trade Size (Equivalent)
Oval Shaped Opening
7 1/2" (191mm)
Black, Brass, Aluminum,
Gray, Ivory
Carpet, Tile & Wood
Minimum:
1/8" (3.2mm)
Maximum:
3/4" (19.1mm)
RC3 Series
* The above maximum copper fill values are the maximum amount of copper to maintain fire classification and are for each
individual power and communication compartments. Do not add values together for any one compartment.
TopGuard
TopGuard
TopGuard
UL SCRUBWATER
PROTECTION
TopGuard
TopGuard
TopGuard
UL SCRUBWATER
PROTECTION
TopGuard