FOR INSTALLATION BY A QUALIFIED ELECTRICIAN IN
ACCORDANCE WITH NATIONAL AND LOCAL ELECTRICAL
CODES AND THE FOLLOWING INSTRUCTIONS. THE
SUITABILITY OF THIS TYPE OF TERMINATION MUST BE
EVALUATED BY UNDERWRITERS’ LABORATORIES, INC.
AND CANADIAN STANDARDS ASSOCIATION FOR THE
END USE APPLICATION.
X
SB
®
175 THREE-POLE
175 Ampere Connector - (with two-piece housings)
Assembly Instructions
Please Note:
Instructions are included with each crimp tool for terminating
specic contacts. Strip cable to dimensions in Table A. Crimp
or solder contact to cable following Tables B.
TABLE A
Cable Stripping Dimensions
Connector series “X” inches “X” mm
SB175 1 1/8 29
1. Attach contact to cable by soldering or crimping.
TABLE B
Suggested Crimping Tools
Catalog Cable Size Hydraulic Pneumatic
Series AWG Tool Tool
6316 all group 4 through 1/0 1368 1387G1*
Catalog Number 6316 Series Reducing Bushing
Cable Size AWG Part Number
1 5687
2 5690
4 5693
6 5663
10 5648
Recommended Soldering Techniques
Use rosin ux solder only. Wrap cable strands. Melt solder into well,
heat, and insert stripped cable. Continue heating well until solder ows
into wire, being careful not to over ow onto contact surfaces. Do not
solder-dip contacts.
WARNING: UTMOST CAUTION SHOULD BE USED WHEN WORKING ON LIVE
CONNECTOR CONTACTS. UL AND CSA REFERENCE - This equipment is an
Underwriters’ laboratories Inc. recognized component, File 26226 it also is listed
by the Canadian Standards Association as certified, Report LR25154.
Products covered by one or more of the following patents: U.S. Patents: 2,838,739;
3,091,746; 3,218,599; 3,654,586 Canadian Patents: 598,493; 651,109; 744,469
British Patents: 781,606; 931,658; 965,073 Other Patents Pending.
“SB®”, “APP®” and “Anderson Power Products®” are registered US and foreign
trademarks of Anderson Power Products®. HEADQUARTERS: Anderson
Power Products®, 13 Pratts Junction Road, Sterling, MA 01564-2305 USA
www.andersonpower.com
1S1036 Rev 5, 14866
* For appropriate crimping die and locator see catalog or consult
the factory. When crimping, use appropriate reducing bushing for
contact well.
2. Assemble housing with screws and nuts provided.
3. Observing proper polarity, place contact in housing with notched side
of tongue next to spring (see cross section).
4. Push contact and cable into housing until it snaps over end of
spring, then a slight tug will conrm that the contact is locked in place.