Document No. D209-00-201-IS-SC Issue C 25-09-19 Sheet 1 of 6
INSTRUCTION MANUAL
E2xB05 & E2xB10 Xenon Beacons
For use in Hazardous Locations
1) Warnings
DO NOT OPEN WHEN AN EXPLOSIVE
ATMOSPHERE IS PRESENT
DO NOT OPEN WHEN ENERGISED
POTENTIAL ELECTROSTATIC CHARGING
HAZARD - CLEAN ONLY WITH A DAMP
CLOTH
HIGH VOLTAGE SHOCK HAZARD. WAIT 5
MINUTES AFTER REMOVING POWER
BEFORE OPENING THE ENCLOSURE
Avertissement:
NE PAS OUVRIR UN PRESENCE
D’ATMOSPHERE EXPLOSIVE
NE PAS OUVRIR ENERGIE
DANGER POTENTIEL CHARGE
ÉLECTROSTATIQUE - NETTOYER
UNIQUEMENT AVEC UN CHIFFON HUMIDE
HAUT TENSION, RISK DE CHOC.
ATTENDEZ 5 MINUTES APRES AVOIR
DEBRANCHE L’ALIMENTATION AVANT
D’OUVRIR LA BOITIER
2) Rating & Marking Information
2.1 ATEX / IECEx certification
The E2xB05 and E2xB10 xenon beacons comply with the
following standards:
EN60079-0:2012+A11:2013 / IEC60079-0: ed. 6.0 (2011-06)
EN60079-15:2010 / IEC60079-15: ed. 4.0 (2010-01)
EN60079-31:2014 / IEC60079-31:2013 ed. 2.0 (2013-11)
Certificate No. DEMKO 06ATEX 0421554X
IECEx ULD 14.0012X
The E2xB05 Xenon Beacon is rated as follows:
The E2xB10 Xenon Beacon is rated as follows:
CE Marking
Zones, Gas / Dust Groups and Temperature
Classification
When connected to an approved system the E2X alarm horn
may be installed in:
Zone 2 explosive gas air mixture not likely to occur
in normal operation, and if it does, it will only exist
for a short time.
Zone 22 explosive dust air mixture not likely to occur
in normal operation, and if it does, it will only exist
for a short time.
May be used with gases in groups:
Group IIA propane
Group IIB ethylene
Group IIC hydrogen / acetylene
Having a temperature classification
(for Gas applications) of:
T1 450ºC
T2 300ºC
T3 200ºC
T4 135ºC
May be used with Dust types:
Group IIIA combustible flyings
Group IIIB non-conductive dust
Group IIIC conductive dust
Maximum Surface Temperature for Dust Applications:
120ºC
105ºC (E2xB10 only up to 40ºC ambient)
100ºC (E2xB05 only)
85ºC (E2xB05 up to 40ºC ambient only)
Installation must be carried out in compliance with the latest
issue of the following standards:
EN60079-14 / IEC60079-14: Explosive atmospheres -
Electrical installations design, selection and erection
EN60079-10-1 / IEC60079-10-1: Explosive atmospheres -
Classification of areas. Explosive gas atmospheres
0518
II 3G Ex nA IIC T3 Gc Ta -20°C to +40°C
II 3G Ex nA IIC T2 Gc Ta -20°C to +55°C
II 3D Ex tc IIIC 85°C Dc Ta -20°C to +40°C
II 3D Ex tc IIIC 100°C Dc Ta -20°C to +55°C
II 3G Ex nA IIC T2 Gc Ta -20°C to +55°C
II 3D Ex tc IIIC 105°C Dc Ta -20°C to +40°C
II 3D Ex tc IIIC 120°C Dc Ta -20°C to +55°C
_______________________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH sales@e-2-s.com Tel: +44 (0)208 743 8880
www.e-2-s.com Fax: +44 (0)208 740 4200
Document No. D209-00-201-IS-SC Issue C 25-09-19 Sheet 2 of 5
EN60079-10-2 / IEC60079-10-2: Explosive atmospheres
Classification of areas. Explosive dust atmospheres
2.2 NEC Class / Zone ratings US
The E2xB05 and E2xB10 Xenon beacons comply with the
following standards:
UL 60079-0-2013
UL 60079-15-2013
UL 60079-31-2015
The E2xB05 Xenon Beacon is rated as follows:
Class I Zone 2 AEx nA IIC T3 Gc Ta -20°C to +40°C
Class I Zone 2 AEx nA IIC T2 Gc Ta -20°C to +55°C
Zone 22 AEx tc IIIC 85°C Dc Ta -20°C to +40°C
Zone 22 AEx tc IIIC 100°C Dc Ta -20°C to +55°C
The E2xB10 Xenon Beacon is rated as follows:
Class I Zone 2 AEx nA IIC T2 Gc Ta -20°C to +55°C
Zone 22 AEx tc IIIC 105°C Dc Ta -20°C to +40°C
Zone 22 AEx tc IIIC 120°C Dc Ta -20°C to +55°C
Installation must be carried out in compliance with the
National Electric Code.
2.3 CEC Class / Zone ratings Canada
The E2xS1 alarm horn complies with the following standards:
CAN/CSA C22.2 No. 60079-0:2015
CAN/CSA C22.2 No. 60079-15:2016
CAN/CSA C22.2 No. 60079-31:2015
The E2xB05 Xenon Beacon is rated as follows:
Class I Zone 2 Ex nA IIC T3 Gc Ta -20°C to +40°C
Class I Zone 2 Ex nA IIC T2 Gc Ta -20°C to +55°C
Zone 22 Ex tc IIIC 85°C Dc Ta -20°C to +40°C
Zone 22 Ex tc IIIC 100°C Dc Ta -20°C to +55°C
The E2xB10 Xenon Beacon is rated as follows:
Ex nA IIC T2 Gc Ta -20°C to +55°C
Ex nA IIC T2 Gc Ta -20°C to +55°C
Ex tc IIIC 105°C Dc Ta -20°C to +40°C
Installation must be carried out in compliance with the
Canadian Electric Code
2.4 NEC & CEC Class / Division Ratings for US / Canada
The E2xS1 alarm horn complies with the following standards:
ANSI/ISA 12.12.01-2015
CSA C22.2 No. 213-16
The E2xB05 Xenon Beacon is rated as follows:
Class I, Div 2, ABCD T2D Ta -20°C to +55°C
Class I, Div 2, ABCD T3 Ta -20°C to +40°C
Class II, Div 2, FG T5 Ta -20°C to +55°C
Class II, Div 2, FG T6 Ta -20°C to +40°C
Class III, Div 1&2 Ta -20°C to +55°C
The E2xB10 Xenon Beacon is rated as follows:
Class I, Div 2, ABCD T2C Ta -20°C to +55°C
Class I, Div 2, ABCD T2D Ta -20°C to +40°C
Class II, Div 2, FG T5 Ta -20°C to +55°C
Class II, Div 2, FG T6 Ta -20°C to +40°C
Class III Ta -20°C to +55°C
Installation must be carried out in compliance with the
National Electric Code / Canadian Electric Code
2.5 Ingress Protection Ratings
The product is rated for ingress Protection as follows:
IP rating per EN60079-0: IP64
IP rating per EN60529: IP66
Type rating per UL50E / NEMA250: 4 / 4X / 13
To maintain the ingress protection rating, the two off cable
entries must be fitted with suitably rated, certified cable entry
and/or blanking devices during installation.
2.6 electrical Ratings
Model No.
Voltage
Current
E2xB05DC012
12Vdc
520mA
E2xB05DC024
24Vdc
275mA
E2xB05DC048
48Vdc
145mA
E2xB05AC115
115Vac
80mA
E2xB05AC230
230Vac
30mA
E2xB10DC024
24Vdc
560mA
E2xB10DC048
48Vdc
260mA
E2xB10AC115
115Vac
185mA
E2xB10AC230
230Vac
107mA
It is important that a suitable power supply is used to run the
equipment. The power supply selected must have the
necessary capacity to provide the input current to all the
units.
The input current will vary according to the voltage input
level. The current levels shown above are for the worst-case
input voltage resulting in max. current.
3) Special Conditions of Use
When used for a Group III application, the surface of the
enclosure may store electrostatic charge and become a
source of ignition in applications with a low relative humidity
<~30% relative humidity where the surface is relatively free of
surface contamination such as dirt, dust, or oil.
Guidance on protection against the risk of ignition due to
electrostatic discharge can be found in EN TR50404 and IEC
TR60079-32.
End user shall adhere to the manufacturer’s installation and
instruction when performing housekeeping to avoid the
potential for hazardous electrostatic charges during cleaning,
by using a damp cloth.
To maintain the ingress protection rating and mode of
protection, the cable entries must be fitted with suitably rated,
certified cable entry and/or blanking devices during