Changeover & Bypass Switches
Changeover & Bypass Sw itches
Haridwar, Noida Ph-I
& Noida Ph-II Plant
State of the art Manufacturing Facilities
Load
Load
Load
I
O
II
On Load Changeover Switches
(with & without Fuses)
Salient Features
Function
Accessories
These changeover switches are used to control &
disconnect any kind of circuit-disconnection feeders both
resistive & inductive loads
By means of manual operation, changeover performs
circuit switching between two independent circuits -I & II
Auxillary contact (early break type) 1NO + 1NC or
2NO + 2NC is available
Key & Castle lock facility
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
Modular design in 3 & 4 pole (63A ~3150A), suitable for
utilization category AC-23A
Easy maintenance as each pole can be replaced easily
due to modular construction, saving cost of entire Switch
in case of single pole being burnt or damaged.
Available in open execution & in sheet steel enclosure.
Provision for defeating door interlock
Complies with the latest requirements of IEC-60947-1&3 /
13947-1&3 standards.
Unique self cleaning contact construction with special
knife type (200A~1800A), double break switching
contacts (63~160A & 1000~1800A) & single break
(200A~800A). Positive opening operation, with quick
make - break and effective arc splitting plates guarantee
reliability and long electrical life of the Switch.
Excellent tracking resistance of isolation material in switch
frame prevents flashover between phases even in the
most trying & difficult locations.
Adjustable telescopic shaft
Compact construction
Window for visual contact inspection
Suitable for capacitor switching and as a Main switch
Handle with in-built padlockable facility in-off position
Individual phase barrier can be incorporated without
tools, between two terminals. Fully protected frame for
safe operation in case of (200A~800A)
Compact On-Load By Pass Switch
Salient Features
Range 63A ~ 1800A, 4 Pole.
Complies with the latest requirement of IEC 60947-1&3
and IS/13947-1&3
By-pass Switch is designed to customers specific need
in IT industries and sites where UPS and Servo stabilizer
provides main source of supply
All other features are same as of On Load Changeover
Switches
AC23A utilization ratings available.
C&S Compact On-Load By-pass switch is operated
manually with single handle comfortably. It provides three
stable positions :
O Loads are open circuited
I Loads are connected to the stabilized
supply
II Loads are connected to the normal supply
Auxiliary contact (early break type) 1NO +1NC or 2NO+2NC
When By-pass switch is selected at position ‘O’ all the
contacts of isolator are open circuited and provide total
isolation.
In position ‘I both isolator I & III are closed and stabilized
supply is connected to the load. At position II only isolator II is
closed & isolators I & II are open thus bypassing UPS &
connecting normal supply directly to load
Operation
Auxiliary Contacts
Single Line Diagram
Position Operation
+
+
+
+
+
Regulator
Load Load Load
SW I SW I
SW I
SW III
II
I
SW III SW III
SW IISW IISW II
Regulator Regulator
C&S pioneered the concept of positive isolation in case of
welding of contacts. In the event of extremely high current
leading to welding of contacts, the handle will not turn
beyond 45 from the ON position, clearly indicates that the
supply is ON and contacts get welded.
Convenience of easy contacts visibility, permits contact
inspection, without removing the switch from installation,
thus saving down time.
Self extinguishing fibre glass re-inforced insulating body of
poles has very high tracking index. Large gap between fixed
and moving contacts in OFF position, make them suitable
for isolation function.
o
Door interlocking prevents opening in the ON position,
guarding the operator against any accidental mishap. As a
standard upto 3 padlocks are provided in the OFF position to
prevent closing the circuit during maintenance work. They
can also be provided in the ON position. Using a suitable
gasket alongwith handle enhances ingress protection
level to IP 54.
III
UPS/Servo
Stabilizer
Normal Supply
(EB/Generator)
LOAD
II
I
SW
SW
SW
Safety Built-inSwitch Construction
OFF
ON
Max. 45
o
Introduction
02 03
Visible Contacts