Electrical Fire
Monitoring System
Product Features
System Sensor electrical Fire Monitoring System includes SSDH-J610R & SSDH-J620 electrical fire monitoring system controller, SSDH-S612
residual current detector, SSD-C6 15 thermal detector, SSDH-C1 terminal thermal probe and SSDH-SY 30~1600 mutual inductance device. The system
uses magnetic current field effect and temperature effect of the electrical current lines and temperature changes transmitted to the monitoring
equipment, when current or the temperature suddenly changes, the detector carries on the analysis to the change peak-to-peak value and compares with
the warning setting value, and then transmits alarm signal and warning address to the monitoring equipment.
Fire Warning Function: After the monitoring equipment receives the fire alarm signals transmitted from detectors, the monitoring equipment will
make a fire alarm sound an d light, while LCD shows first follow-up warning alarm detector addre ss, sensor type, alarm type, alarm value, and takes
down the first alarm time.
Malfunction Alert Function : When the sensors detect the loss of equipmen t or detectors, or mo nitoring equipment connecting to a short circuit or
open circuit failure. The system will make voice and light alarm. At the same time the LCD displays the total number of failures, the address of the first
alarm as well as the address of the following alarms.
Linkage Output Function: After the monitoring equipment receives the fire alarm, if monitoring equipments control selection switch is in
automatically position, monitoring equipment automatically starts 8 groups of relays, if monitoring equipments control selection switch is in
manual position, the user may operate on the f acial mask manually to start or stop 8 groups of relays.
Network Joint Function: The system is capable of network connection, carrying on the information with the superior machine (PC) to be interactive,
centralized control bench demonstration.
Event Logging Function: The main recorder records up to 25 6 events occurred recently, includ ing fire warning, malfunction alert, replacement
operation and so on.
Printing Function: The printer may print the warning event and the time, the breakdo wn events and the time, the replacement operatio ns.
SSDH-J610R
SSDH-J620
SSDH-C615 SSDH-S612
SSDH-C1
SSDH-SY 30~1600
Agency Listing
CNTC
OrderingModelNumber ProductDescriptio n UOM
SSDHJ610R Electricalfiremonitoringsystemcontroller ea.
SSDHJ620 Electrical firemonitoringsystemcontroller ea.
SSDHC 615 Thermaldetector ea.
SSDHC1 TerminalThermalProbe ea.
SSDHS612 Residualcurren tdetector ea.
SSDHSY30~1600 MutualInductancedevice ea.
SSDHJKSOFT Electricalfiremonitoringandmanagementsoftware ea.
Installation Diagrams
System Sensor Headquarters
3825 Ohio Avenue
St. Charles, IL 60174
Ph: 630-377-6580
Fx: 630-377-6495
Free Phone: 800-736-7672
Web: www.systemsensor.com
System Sensor China
28 Tuan Jie South Road,
Hi-Tech Development Zone
Xi'an, 710075, China
Ph: +86 29 88320119
Fx: +86 29 88325110
Web: www.systemsensor.com.cn
System Sensor Canada
Ph: 905-812-0767
Fx: 905-812-0771
System Sensor Europe
Ph: 44 (0) 1527 406700
Fx: 44 (0) 1527 406699
System Sensor Italy
Ph: 39 040 949 0111
Fx: 39 040 382 137
System Sensor Mexico
Ph: 54 11 4324-1909
Fx: 54 11 4324-5999
System Sensor Far East Ltd
Ph: 852 21919003
Fx: 852 27366580
System Sensor Singapore
Ph: 65 6273 2230
System Sensor India
Ph: 91 124 2371770-270
Fx: 91 124 2373118
System Sensor Australia
Ph: 61-3-5428 1142
Fx: 61-3-5428 1172
Monitoring Equipment Capacity: 128 detectors, 8 SPST relay outputs ( SSDH-J610R )
1536 detectors, 8 SPST relay outputs ( SSDH-J620 )
Communication Distance: Up to 1200 meters
Response Time: 30 seconds (from detected value hitting threshold value to audible/visible, LCD alarm emitted)
Relay Electronic Contact Capacity: AC 120V/1A, DC 24V/1A
Outputs Power Supply Capacity: 24V/1A, if higher is needed, please use other independent power supply
Event Records Capacity: Recent 256 events ( warning, breakdown, replacement )
Controller Operating Power Supply: AC 220V/50HZ
Working Conditions: Temperature range 0-55℃( 32-131℉), Humidity95%
Backup Power Supply: DC 24V, 4Ah
Power Of Controller: Inspecting Mode 30W, Warning Condition 60WSSDH-J610R & SSDH-J620
External Dimensions: 600×372×130mm ( wall-mounting type )
Weight: 10Kg ( backup power supply included )
SSDH-J610R alarm and control units for electrical fire
prevention (wall-mounting type) installation diagram
Current leakage and heat measurement detectors
use the IEC35mm standard installation kit
Ordering Information