COMPUTING
APPLICATION NOTE
This document covers aspects of tting the SharpStreamer
PCIE-7207 media
processing accelerator card into a Dell PowerEdge R730 server.
THE DELL POWEREDGE R730 SERVER
The Dell PowerEdge R730 server is a new generation 2U rack mount server
based on the E5-26xx v3 Intel
®
Xeon
®
technology (Codename Haswell). The
server is available in several congurations. However, this application note only
covers integration within R730 conguration.
For more details, visit the DELL website.
THE SHARPSTREAMER PCIE-7207 HARDWARE INSTALLATION
In a dual Intel Xeon conguration, the Dell R730 server can support up to four
SharpStreamer PCIE-7207 cards. Cards should be installed in PCI Express slots
#4, 5, 6 and 7 found on PCIe riser #2 (PN: 330-BBCO) and PCIe riser #3 (PN:
330-BBCQ). Dual CPU conguration can also accommodate for an additional
three low prole slots located on PCIe riser #1.
In a single CPU conguration, the server can support up to three full length full
height PCI Express cards. The SharpStreamer PCIE-7207 card could potentially
be installed in PCIe slots #5, 6 and 7.
When installing SharpStreamer cards, mid-card guides and auxiliary power
cabling must be used. Auxiliary power cabling and low prole CPU heatsinks can
be purchased as part of the R730 GPU Installation Kit (PN: 331-8803). See
photos for reference. Low prole CPU heatsink installation is not required but can
be used for improve internal chassis thermal environment
INSTALLING THE SOFTWARE PACKAGE
Software Installation Dependencies:
Server running CentOS 7.x
Tftp-server, syslinux and dhcp
Firewall (ie. rewalld, iptables, etc) congured to allow system to run above
services
Unzip and install SharpStreamer Host-side utilities
Unzip and install SharpStreamer Centos 7 reference image
Proceed with software installation as documented in each software package as
“readme” le. Artesyn SharpStreamer PCIE-7207 documentation, and software
packages can be obtained SWORDS portal or through your Artesyn Field
Application Engineer.
So You Want to...
Install Artesyn SharpStreamer
PCIE-7207 cards
into a Dell PowerEdge R730 Server?
PCI Express Card Guides
Dell R730 Server
COMPUTING
APPLICATION NOTE
SYSTEM OPERATION AND THERMAL OPTIMIZATION
The Dell R730 system fans produce direct air within the system to cool the PCI
Express cards. There is a black plastic bafe that channels the air from six hot
swappable fans. This also ensures air ows across the rest of the motherboard
components and through the PCIe section once it has gone through the CPU
heatsinks. We highly recommend monitoring both the SharpStreamer PCIE-7207
microprocessor subsystem temperatures. This can be done using the
temperature tool provided in the PCIE-7207 host side server utilities package (ex:
pci7207 –s1 –n1 –ct). If any of temperature sensors reports a temperature of
higher than 80°C, you may want to check whether anything mechanically is
disrupting the system air ow or your system environment conditions have
changed. If neither situation has occurred, then you should consider adjusting the
system fan prole.
The Dell R730 has three thermal proles (default, maximum performance and
minimum power) and four fan speed offsets (low, medium, high and maximum)
which control the system fans’ behavior. These proles can be found under
iDRAC Settings under the “thermal” section.
In room temperature (22°C ambient) with the thermal prole set to default and fan
speed offset set to off, Artesyn testing indicates the PCIE-7207 should operate
properly under these conditions. During normal operation, you can expect the
microprocessor subsystem temperature readings to be anywhere between 30°C
and 65°C. If any temperature reading should go above 80°C, you should set the
fan speed offset to High (+71%) and/or install low prole CPU heatsinks. Please
ensure air ow is such that microprocessor subsystem temperature sensors
reading do not go above 95°C as these high temperatures may cause damage to
the board and will result in lower lifespan. In extreme cases, the board will shut
itself off to prevent damage.
If you should run into any questions or issues using the SharpStreamer PCIE-
7207 card with the Dell R730 system, please contact your local Artesyn Field
Application Engineer (FAE).
Artesyn Embedded Technologies, Artesyn, SharpMedia and the
Artesyn Embedded Technologies logo are trademarks and service marks
of Artesyn Embedded Technologies, Inc. Intel and Xeon are trademarks
of Intel Corporation in the U.S. and/or other countries. PCI Express (PCIe)
is a registered trademark of PCI-SIG. HP is a registered trademark of
Hewlett-Packard © 2014 Artesyn Embedded Technologies, Inc.
PCIE-7207-DELL-R730-AN1 22Jul2015
Four SharpStreamer Card Installation
Auxiliary Power Cables