LMR PLUS Electric Fire Pump Controllers with Transfer Switch
Features
1 - 1
For more information visit: www.ch re.com
BR05805059K/L
January 2012
FT40 Reduced Voltage - Part Winding
The Automatic Transfer Switch Option may be
added to any FD type Fire Pump Controller
whenever automatic transfer from normal to
alternate power is required.
The automatic Transfer Switch and Fire Pump
Controller are mounted in the same enclosure
or in separate enclosures to form one unit and
interwired - depending on the horsepower and
voltage required.
Product Description
Product Features
Engine Test Button
Logic Controller Board
Power I/O Board
Electrically and Mechani-
cally Interlocked
ATC-300 Plus
Automatic Transfer
Voltage and Frequency Sensing
Alarm Relay
Keypad Programming
LED Status Indication
An engine test button is provided on the ATC-
300 controller that can be used to test the
Source 2 (generator) engine. The operator can
select the engine run test time (0-600 minutes).
As well, a silence pushbutton is provided which
de-energizes the alarm bell.
The FT Series transfer switch operating mecha-
nisms are mechanically interlocked to prevent
the normal and alternate source from connect-
ing at the same time.
The switch operates upon signals received from
the ATC-300 Plus controller.
The panel mounted,
multi-function, micropro-
cessor based ATC-300
Plus controller accurately
monitors two power
sources and provides the
necessary intelligence
to reliably operate the
transfer switch through
a series of programmed
sensing and timing func-
tions.
The ATC-300 Plus controller membrane is
equipped with seven keypad input buttons
which are used to program the controller as well
as set operating parameters.
Five LED’s indicate the status of the power
sources.
Source 1 Available Source 1 Connected
Source 2 Available Source 2 Connected
Unit Status
The FT Series Transfer Switches
will perform an automatic
transfer from Normal to Alter-
nate source when the Voltage
drops to 85% of normal, or
there is a loss of any phase
and/or Phase Reversal.
The ATC-300 Plus continuously monitors the
normal source for out of range setpoint values.
When the source is outside the dropout set-
points, the source will become unavailable.
This prompts a transfer to the alternate source.
Retransfer occurs when the normal source’s
frequency and/or voltage return within pickup
setpoints.
The alarm relay is de-energized to indicate an
absence of an alarm state and energized to
indicate the presence of an alarm condition.
Alarm conditions include:
Improper Circuit Breaker Operation
Motor Operator Failure
Lockout
Failsafe Condition
Aborted Engine Test
Aborted Plant Exerciser
Unsuccessful in-phase Transition
The FT40 Transfer Switch Controllers are a full
service, part winding reduced voltage controller.
A part winding re pump controller reduces the
starting current by up to 40% while maintaining
up to 50% motor starting torque. The FT40 is
the most economical method of reduced volt-
age starting, however, requires a special motor
wound for part winding starting. The FT40 can
be programmed for either fully automatic or
semi-automatic operations.
Communication
The controller can be ordered with the option to
display and output current values and status,
on command, from various software protocols
through the appropriate port(s).
Embedded Web Page
The web page is a multifunction tool that allows
the user to view the controller’s current status,
data values, programmed set points and history.
It is accessed using the optional ethernet port.
USB Port / USB Drive
The logic controller board is equipped with a
USB port that can be used to transfer data to
and from a portable USB Drive device (memory
stick).
Ethernet Port
An optional ethernet port is used for direct con-
nection to a computer for data transfer.
RS485 Serial Port
An optional RS485 serial port can be provided
for communication to various external software
programs.
Buzzer
A buzzer is mounted on the logic board which
will operate if Fail to Start, Hardware Malfunc-
tion or any Common Alarm condition exists.
Transformers
Incoming line voltage is run directly to the I/O
board from the incoming lines. The three trans-
formers mounted on the I/O board will accept
voltage inputs between 100 and 600V.
Customer Connection Terminals
Connection terminals for external customer
connections, are located on the top of the
Power I/O board.
Output Relays
Seven socket mount,
8 Amp, 2 Form - C
(DPDT) output relays
are provided standard
on each power I/O board.
They are designated for:
Common Alarm,
Phase Failure,
Phase Reversal,
Pump Run,
Startup,
Acceleration
and Future # 1.
Each socket has an LED mounted on the I/O
board which indicates each relay’s coil status.
Optional Output Relay Boards
There is provision to add up to eight additional
relay outputs, via optional relay output boards.
Each board contains a maximum of 2 addi-
tional relays. The Power I/O Board will accept a
maximum of 4 optional boards which mount in a
snap-on con guration.
Each board provides an area for the user to
label the terminal number and relay name.
LMR PLUS Electric Fire Pump Controllers with Transfer Switch
Features
1 - 2
For more information visit: www.ch re.com
BR05805059K/L
January 2012
FT40 Reduced Voltage - Part Winding
Door Mount
The membrane keypad is accessible from the
front door of the controller.
NEMA Rating
The standard membrane keypad is rated for
NEMA 2, 3R, 4, 4X and 12.
LCD Display
The Logic Control Board contains a 4 Line by 40
Characters wide, backlit, LCD display which is
capable of generating multiple languages.
Alarm & Status LED’s
A total of 20, ( 10 Status - 10 Alarm ) LED’s
provide indication on the membrane keypad.
Power On
Pump Running
Local Start
Remote Start
Deluge Valve
Emergency Start
Interlock On
Low Pressure
Auto Shutdown Enabled
Programmable LED # 1
Phase Reversal
Phase Failure
Fail To Start
Undervoltage
Overvoltage
Low Room Temperature
Locked Rotor Trip
Low Suction Pressure
Source 2 Disconnected
Programmable LED # 2
Status LED’s Alarm LED’s
Silence Button
A silence pushbutton on the membrane can
be used to silence the buzzer. When an alarm
condition exists, the alarm buzzer will sound. If
the Silence Alarm button is pressed, the alarm
buzzer will turn off. If a subsequent alarm con-
dition occurs after the silence button is pressed,
the buzzer will re-sound. Pressing the Silence
Alarm button again, will silence the buzzer.
Motor Test Button
The motor test button on the membrane can be
used to simulate an automatic start.
Automatic Shutdown Enabled
When the Automatic Shutdown function is en-
abled, a Green LED will indicate on the control-
ler membrane.
MAIN DISPLAY
General
The main display will show the current system
pressure, time and date, voltage and amps
reading for all three phases, the system fre-
quency and any custom messages, alarms or
timers.
Programmed Set-Point
The set-point display will show programmed
pressure start point, pressure stop point and
weekly test timer setting.
Statistics
The statistics display will allow the user to scroll
through all of the measured statistics stored in
memory. Refer to LMR Plus operation manual
IM05805020K for speci c details.
Diagnostics
The diagnostics display will allow the user to
scroll thorough eleven diagnostic points to assist
with troubleshooting the system.
Message History
The user will be able to scroll through all of
the messages stored in the memory of the
controller with the most recent message being
displayed rst.
PRINT Menu
Description
All fault and alarm information is sent to the
USB and Printer ports on demand, as well as
the status of each output. The LMR Plus will
store up to 10K events which are time and date
stamped. All information can also be retrieved
and displayed on the LCD display.
Saving to USB Drive
The controller will save four separate text les,
one CSV le and the embedded webpage to the
USB external drive. The les, at maximum size,
can be saved multiple times on one 128MB USB
drive.
Files to be saved are: Status Report, Diagnostics
Report, Statistics Report, Con guration File and
Last 10K Messages.
Print Menu
The printer menu is accessed in order to select
the desired print function.
Functions include: Print Messages, Last XX Mes-
sages, Date & Time, Status Report, Diagnostics
Report and Statistics Report.
Custom Messages
When this item is selected, custom messages
can be cleared from memory or downloaded
from the USB external drive.
Firmware Update
Firmware revisions are updated from an ex-
ternal USB drive. All previously programmed
settings will remain intact when updating is
completed. Should there be an update failure,
the controller will automatically revert back to
the previous version of rmware.
Embedded Webpage
General
The embedded webpage is a multifunction tool
that will allow the user to view the current sta-
tus of the controller as well as display all current
readings, set points, and history. An external
computer can be connected via the optional Eth-
ernet port to access the page. When connected,
the controller set points can be programmed via
the webpage.
Multiple Pages
There are 5 viewable pages that show the Main
Display, Statistics, Diagnostics, History and
Programmed Set Points.
Pressure Points
The pressure reports recorded in memory can
be graphed and/or sorted based on date and
time.
Programmed Set Points
All of the programmed set points and their cur-
rent status can be viewed via the webpage.
Custom Messages
Users can create custom messages on a
computer and upload to the controller using a
USB Drive (memory stick). Up to 10 custom
messages of up to 100 characters each, will
continuously scroll across the fourth line of the
LCD display once uploaded.
Trigger Points
The message can be programmed to appear at
speci c trigger points such as speci c date and
time, speci c number of operations, speci c
number of hours run or at any individual alarm
point.
All of the trigger points can be selected as And/
Or values.