Product Bulletin
Belden Expands Its
ControlBus Cable Line
With a Continuously
Corrugated Aluminum
Armored Product
About ControlNet
ControlNet is a high-speed, serial communication
system that provides for a time-critical exchange
of information between complex control devices
such as programmable logic controllers, HMIs
and PC-based controllers. ControlNet operates
in a totally deterministic and predictable
manner, allowing the various devices and
controllers on the network to communicate
at a precise and pre-determined point in time.
ControlNet Features
A ControlNet network can support up to 48
nodes at a bus speed of 5Mb/s on a total end-
to-end distance of 250m. The bus topology can
be star, tree, bus, or any combination of the
three. The time delay throughout the system
and a maximum end-to-end distance of 30+ km,
represent the only limiting factors on the
number of repeaters that can be used.
Although ControlNet uses a larger bandwidth
than other automation and control networks, it
does not function as a traditional “broadband”
network. In a ControlNet system, the network
devices and controllers are expected to
communicate/operate at a pre-determined
point in time and for a specific length of
time. Broadband communication networks
differ in that their communication efforts
take place when the network has room
for the communication.
Because ControlNet is deterministic, it is
robust and capable enough for industrial time-
critical applications. This core philosophy of the
system also requires that signal transmission be
uncorrupted and high speed. Therefore, choosing
an approved, tested and conformant Low-loss
RG-6 made especially for ControlNet systems
from Belden is truly important for maximum
system performance.
Quad-shielded ControlBus
Coaxial Cables
Belden ControlBus Low-loss coax cables
for ControlNet applications incorporate
a Duobond® IV Quad Shield for maximum
signal integrity and run length. All products
are sweep tested, ensuring that Return Loss,
and other critical performance features, meet
the requirements of the ControlNet physical
layer specification. New to the line is 183092A
—with continuously corrugated aluminum
armoring for added protection in harsh
environments. ControlBus cables can be
supplied with a CPE jacket and/or aluminum
or steel interlocked armoring. Belden also
manufactures variations of the cable for
different applications, environments, and
identification purposes.
Belden
®
ControlBus cables
are Low-loss RG-6/U Type
Coaxes. They meet the
high-speed, time-critical
requirements necessary for
the operation of ControlNet
TM
factory-floor systems.
PB 241
ControlBus
®
Cables
Be Certain with Belden
ControlBus Quad Shielded Coax for ControlNet Applications
RG-6/U Type • 18 AWG Solid Bare Copper-covered Steel • Duobond IV* Quad Shield
Foam PE Insulation PVC Jacket (Black, Red, or Intrinsically Safe Blue)
75°C 3092A NEC: 500 152.4 22.0 10.0 18 AWG .180 4.57 Duobond IV .298 7.57 75 82% 16.2 53.1
CL2R CMR 1000
u
304.8 42.0 19.1 (solid) Quad
CEC: 2000
609.6 80.0 36.3 .040” Shield
CMG FT4 2500
s
762.2 97.5 44.3 BCCS 3.6Ω/Mʹ
28.0Ω/Mʹ 11.8Ω/km
91.8Ω/km
Allen-Bradley P/N 1786
u
Red available as standard in 1000 ft. only.
s
2500 ft. put-up available in Black only.
Plenum Foam FEP Insulation Fluorocopolymer Jacket (Black or Intrinsically Safe Blue
u
)
High Temp 3093A NEC: 1000
u
304.8 40.0 18.2 18 AWG .170 4.32 Duobond IV .274 6.96 75 82% 16.3 53.5
150°C CMP 2000
609.6 80.0 36.3 (solid) Quad
CEC: 2500
762.0 95.0 43.1 .040” Shield
CMP FT6 BCCS 3.6Ω/Mʹ
28.0Ω/Mʹ 11.8Ω/km
91.8Ω/km
Allen-Bradley P/N 1786
u
Blue available as standard in 1000 ft. only.
Suitable for Outdoor and Direct Burial applications.
Aluminum Interlocked Armor Foam PE Insulation PVC Inner and PVC Sunlight-resistant Outer Jacket (Black)
Aluminum 123092A NEC: 1000
††
304.8 180.0 81.7 18 AWG .180 4.57 Duobond IV Inner Jacket: 75 82% 16.2 53.1
Interlocked CM (solid) Quad .298 7.57
Armor CEC: .040” Shield
75°C CMG FT4 BCCS 3.6Ω/MʹOverall:
HL 28.0Ω/Mʹ 11.8Ω/km .620 15.75
(Haz. Loc.)
91.8Ω/km
Allen-Bradley P/N 1786
††
Final put-up length may vary ±5% from length shown.
Sequentially marked at 1 meter intervals.
Continuously Corrugated AL Armor Foam PE Insulation PVC Inner and PVC Sunlight-resistant Outer Jacket
(Black)
Continuous 183092A NEC: 2000
s
609.6 350.0 158.9 18 AWG .180 4.57 Duobond IV Inner Jacket 75 82% 16.2 53.2
Armor u CL2, CM (solid) Quad .298 7.57
75°C .040” Shield Overall:
BCCS 3.6Ω/Mʹ .570 14.48
28.0Ω/Mʹ 11.8Ω/km
91.9Ω/km 
Allen-Bradley P/N 1786
s
Final put-up length may vary ±10% from length shown.
Jacket sequentially marked at 2 ft. intervals.
RG-6/U Type 20 AWG Stranded (105x40) Bare Copper Duobond IV* Quad Shield
Foam PE Insulation PVC Jacket (Black)
High-Flex 3092F NEC: 1000 304.8 44.0 20.0 20 AWG .183 4.65 Duobond IV .303 7.70 75 79% 17.0 55.8
CL2R CMR 5000
1524.0 225.0 102.2 (105x40) Quad
CEC: .040” Shield
CMG FT4 Bare 3.6Ω/Mʹ
Copper 11.8Ω/km
10.5Ω/Mʹ
34.4Ω/km
Allen-Bradley P/N 1786 
IEEE 802.4 MAP/IEEE 802.7 Mini-MAP.
For Rockwell authorized Flexible ControlNet order YR28890 (Tinned Copper Braid version).
AL = Aluminum • BCCS = Bare Copper-covered Steel • DCR = DC Resistance • FEP = Fluorinated Ethylene-propylene • PE = Polyethylene
* Duobond IV Quad Shield = Duobond II Foil + 60% aluminum braid + Duofoil + 40% aluminum braid.
Final put-up length may vary -0% to +10% from length shown.
1 .36 1.2
2 .47 1.5
5 .80 2.6
10 1.20 3.9
20 2.00 6.6
50 3.20 10.5
100 4.60 15.1
200 6.50 21.3
300 8.00 26.2
400 9.30 30.5
1 .35 1.1
2 .38 1.2
5 .45 1.5
10 .59 1.9
20 .86 2.8
50 1.37 4.5
100 1.97 6.5
200 2.82 9.3
300 3.48 11.4
400 4.04 13.3
1 .36 1.2
2 .38 1.2
5 .50 1.6
10 .65 2.1
20 .95 3.1
50 1.50 4.9
100 2.12 7.0
200 2.99 9.8
300 3.66 12.0
400 4.23 13.9
Sweep tested 5 MHz to 400 MHz.
123092F — Aluminum
Interlocked Armor
133092F — Steel Interlocked Armor
CPE Jacket Optional.
Sweep tested 5 MHz to 50 MHz.
CPE Jacket Optional.
1 .35 1.2
2 .38 1.3
5 .45 1.5
10 .59 1.9
20 .86 2.8
50 1.37 4.5
100 1.97 6.5
200 2.82 9.3
300 3.48 11.4
400 4.04 13.3
Sweep tested 5 MHz to 50 MHz.
133092A — Steel Interlocked Armor
CPE Jacket Optional
Sweep tested 5 MHz to 50 MHz.
Shielding
Materials
Nom. DCR
Nom.
Imp.
(Ω)
Nominal
Core OD
Nominal OD
Inch mm Inch mm
Conductor
(stranding)
Diameter
Nom. DCR
Standard
Unit Weight
Standard Lengths
Lbs. kgFt. m
UL NEC/
C(UL) CEC
Type
Part
No.
MHz
dB/
100 Ft.
dB/
100m
Nominal
Attenuation
Nominal
Capacitance
pF/mpF/Ft.
Nom.
Vel.
of
Prop.
Description
Sweep tested 5 MHz to 50 MHz.
1 .35 1.2
2 .38 1.3
5 .45 1.5
10 .59 1.9
20 .86 2.8
50 1.37 4.5
100 1.97 6.5
200 2.82 9.3
300 3.48 11.4
400 4.04 13.3
ControlNet
is a ControlNet International trademark.
Belden Technical Support 1.800.BELDEN.1 (1.800.235.3361) www.belden.com
©Copyright 2011, Belden Inc.