Electronics
Dual-voltage input of 120/277VAC. Precision controlled
motor and cam system ensures smooth and reliable
opening and closing of light source. LED indicator provides
visible fault detection and AC-On indication. Test switch
provides manual activation of a 30-second diagnostic te st.
Standard Features Include:
• Self-test, self-diagnostics monitors lamp load transfer circuit,
battery capacity, operation and motor drive. 28 day self-te st.
• Brownout protection
• Low voltage disconnect prevents deep discharge of the battery
• Voltage polarity protected by use of polarized connector
• 15 minute time delay re-transfer
• Fused remote leads for units with remote capacity
Optional Accessories
CLRT- Remote IR Testing Transmitter. Selectable 30-second or
90-minute remote testing. Only one required for multiple units.
CLRI- Remote Diagnostic Indicator Display.
Operating Temperature Range
Lead Calcium Battery: 16
°
C to 32
°
C (60
°F
to 90
°
F)
Nickel Cadmium Battery: 0
°C
to 38
°
C (32
°F
to 100
°
F)
Overall Size: 16”L X 13.5”W X 4”D
Weight: 23-31 lbs. depending upon capacity
Dual-Lite • www.dual-lite.com
A Hubbell Lighting, Inc. brand with representatives’ offices in principal cities throughout North America.
Copyright© Hubbell Lighting, Inc., All Rights Reserved • Specifications subject to change without notice. • Printed in U.S.A. 0603443AB 8/16
DIMENSIONS
SPECIFICATIONS
CL Series
Concealed Recessed Emergency Luminaire
Part Number Run Time
1
Remote Capacity Remote Watts
2
CL50H12 3.0 Hours Ye s 26
CL50NH12 3.0 Hours Ye s 26
CL50H20 2.0 Hours No
--
CL50NH20 2.0 Hours No
--
CL100H12 6.0 hours Ye s 76
CL100NH12 6.0 Hours Ye s 76
CL100H20 4.0 Hours Ye s 60
CL100NH20 4.0 Hours Ye s 60
CL100H35 2.0 Hours Ye s 30
CL100NH35 2.0 Hours Ye s 30
CL100H50 1.5 Hours No
--
CL100NH50 1.5 Hours No
--
CL150H12 9.0 Hours Yes 126
CL150NH12 9.0 Hours Yes 126
CL150H20 6.0 Hours Yes 110
CL150NH20 6.0 Hours Yes 110
CL150H35 4.0 Hours Yes 80
CL150NH35 4.0 Hours Yes 80
CL150H50 2.0 Hours Ye s 50
CL150NH50 2.0 Hours Yes 50
CL150H75 1.5 Hours No
--
CL150NH75 1.5 Hours No
--
REMOTE CAPACITY CHART
Univeral, Adjustable
Mounting Rails
2 per unit
13½" to 30"
Depth Behind Wall
3¼"
Total Depth 4"
Rough In Opening
13½"
Back Box and
Mounting Dimensions
Rough In Opening
6¾"
Lamp sockets can be adjusted
to optimize light pattern for wall
or ceiling mounting.
7⁄"
Mounted Dimensions (door open)
Mounting Rails
2 per unit
13½" to 30"
Depth Behind Wall
3¼"
Total Depth 4"
13½"
Back Box and
Mounting Dimensions
Rough In Opening
6¾"
Lamp sockets can be adjusted
to optimize light pattern for wall
or ceiling mounting.
7⁄"
14⁄"
Mounted Dimensions (door open)
16"
SUGGESTED CENTER-TO-CENTER SPACING
Lamp Type
Ceiling Height
10' 12' 16' 20'
H12 12W Halogen 17' 17' 16' 16'
H20 20W Halogen 36' 36' 34' 34'
H35 35W Halogen
65' 65' 58' 64'
H50 50W Halogen
70' 70' 70' 70'
H75 75W Halogen
130 140' 134' 140'
Based on minimum illuminance of 0.1FC and average
illuminance of 1.0FC. Assumes fixture is ceiling mounted in
a 200' W X 200' L open space with reflectance of 80/50/20.
1
Unit battery run time for integral lamps only (no remote lamps connected).
2
Max. watts available for connection of remote lamps at 1.5 Hour unit
minimum run time.