Bulletin 24-00 A
2
Port Size
Capacity
Plugs
Flow Coefficient
[1]
Connections Weight
mm inch Kv Cv SW, BW ANSI BW Metric (DIN) kg lbs
20
3
⁄4
Full
70%
6.1
4.3
7.0
5.0
3
⁄4”, 1", 1
1
⁄4” 20, 25, 32 5.4 11.8
25 1
Full
40%
11.2
4.3
13.0
5.0
3
⁄4”, 1", 1
1
⁄4” 20, 25, 32 5.4 11.8
32 1
1
⁄4 Full 14.1 16.3 1
1
⁄4", 1
1
⁄2” 32, 40 10.8 23.9
40 1
1
⁄2 Full 26.9 31.1 1
1
⁄2”, 2" 40, 50 10.8 23.9
Table of Contents
Technical Data ...............................................2
Application ..................................................2
Function and Design .........................................3
Material List .................................................3
User Interface Guide .........................................3
Installation Instructions ......................................4
Electrical ....................................................5
Quick Start Instructions ......................................6
Menu and Level Navigation Guide .............................7
Technical Data
Liquid Temperature Range ....... -60°C to 120°C (-76°F to 248°F)
Ambient Temperature Range ...... -40°C to 50°C (-40°F to 122°F)
Maximum Rated Pressure (MRP) ............... 52 bar (754 psig)
Maximum Operating Pressure Differential (MOPD)
20mm (
3
⁄4") to 25mm (1") ................. 52 bard (754 psid)
32mm (1
1
⁄4") to 40mm (1
1
⁄2") ............... 28 bard (406 psid)
Operating Pressure
Range ............500 mm Hg to 52 bar (20in. Hg to 754 psig)
Electrical Specification .......................24 VDC @ 1.3 Amp
Enclosure Specification ......................... IP67 / NEMA 6
Rated Seat Leakage. . . . . . . . . . . . . . . . . . ANSI/ FCI 70-2 2006 Class II
Software Parameters .........................................8
Alarm List ...................................................9
Dimensional Information .....................................9
Nameplate Information .....................................10
Manual Opening Operation ..................................11
Maintenance and Service ....................................11
Parts Kit Reference .........................................13
Appendix ..................................................14
PEV Backup Module (PBM)
HBLT-C1 Liquid Level Controller
Application Example
Strainer
(100 Mesh)
Receiver
PEV
HBLT-C1-ENC
LLSS
HBLT-A1
3
2
1
Electronic Valve
1
Backup Module
2
Liquid Level Controller
3
Pump
Pump separator installed with an HBLT-A1
analog liquid level transmitter probe for
continuous level control of the vessel.
The transmitter probe is connected to the
HBLT-C1 controller which modulates the PEV
to maintain a constant level in the receiver.
PBM
Liquid Level Transmitter
4
4
Low Pressure (LP) Liquid Level Control