Time Delay Relays
Dedicated - HVAC
Rev: 1-A-062116
CT SERIES
L1 N
V = Voltage
FR = Fan Relay
FS = Fan Switch
CR = Compressor Relay
THMS = Wall Thermostat
Delay-on-Make/Delay-on-Break Timer
Description
The CT Series combines a delay-on-make and delay-on-break
time delay into one unit and may be used to control fan delays
in heating and/or cooling equipment. The CT includes bypass
circuitry to allow it to operate with cooling anticipators ≥ 3000
ohms. It is designed to operate in 24VAC control circuits.
Several CT modules may be combined to provide sequencing of
any number of loads and sequencing off of the same loads, such
as electric heating elements.
Operation (Delay-on-Make/Delay-on-Break)
Forced Air Heating or Air Conditioning (as shown): When
the thermostat closes, the compressor relay is immediately
energized. At the end of a fixed delay-on-make delay (T1),
the fan relay is energized. When the thermostat opens, the
compressor relay is de-energized and the delay-on-break delay
is initiated. On completion of the fixed delay-on- break delay
(T2) the fan relay is de-energized. If the thermostat is reclosed
during the delay-on-break delay, the delay-on-break delay is reset
and the fan relay remains energized. If the thermostat is closed
when input voltage is applied, the delay-on-make delay (T1)
begins as normal.
Reset: Removing input voltage resets the output and time delays.
Features & Benefits
FEATURES BENEFITS
Delay-on-Make and
Delay-on-Break in
one unit
Simplifies wiring and installation, and optimizes
efficiency of heating and cooling systems
Totally solid state
and encapsulated
No moving parts to arc and wear out over time and
encapsulated to protect against shock, vibration,
and humidity
Interconnectability with
other CT modules
Combine modules to provide sequencing on of
a number of loads and sequencing off of the
same loads
Accessories
P1015-64 (AWG 14/16)
Female Quick Connect
These 0.25 in. (6.35 mm) female terminals are
constructed with an insulator barrel to provide
strain relief.
P1023-6 Mounting bracket
The 90° orientation of mounting slots makes
installation/removal of modules quick and easy.
P1015-18 Quick Connect to Screw Adapter
Screw adapter terminal designed for use with
all modules with 0.25 in. (6.35 mm) male quick
connect terminals.
Wiring Diagram
Ordering Information
MODEL
DELAY-ON-MAKE
(FIXED SECONDS)
DELAY-ON-BREAK
(FIXED SECONDS)
CT1S30 1 30
CT1S45 1 45
CT1S8 1 8
CT1S90 1 90
CT30S1 30 1
CT45S45 45 45
CT5S300 5 300
If you don’t find the part you need, call us for a custom product 800-843-8848
Time Delay Relays
Dedicated - HVAC
Rev: 1-A-062116
Accessories
C103PM (AL) DIN Rail
35 mm aluminum DIN rail available in a 36 in.
(91.4 cm) length.
P1023-20 DIN Rail Adapter
Allows module to be mounted on a 35 mm DIN
type rail with two #10 screws.
Function Diagram
DELAY-ON-MAKE
DELAY-ON-BREAK
CT SERIES
Specifications
Time Delay
Type Microcontroller
Range 1 - 600s
Repeat Accuracy ±5%
Tolerance
(Factory Calibration) ±20%
Recycle Time ≤ 300ms
Input
Voltage 24VAC
Tolerance ±15%
AC Line Frequency 50/60 Hz
Output
Type Solid state
Form NO
Rating 0.75A steady state, 5A inrush at 5C
Voltage Drop
1.25V
Protection
Circuitry Encapsulated
Dielectric Breakdown ≥ 2000V rms terminals to mounting surface
Insulation Resistance 100 MΩ
Mechanical
Mounting Surface mount with one #10 (M5 x 0.8) screw
Dimensions H 50.8 mm (2”); W 50.8 mm (2”);
D 30.7 mm (1.21”)
Termination 0.25 in. (6.35 mm) male quick
connect terminals
Environmental
Operating/Storage
Temperature -40° to 70°C / -40° to 8C
Humidity 95% relative, non-condensing
Weight 2.4 oz (68 g)
Thermostat Anticipator Resistor: ≥ 3000 Ω
V = Voltage
FS = Fan Switch
FR = Fan Relay
T1 = Delay-on-Make
T2 = Delay-on-Break
R = Reset
= Undefined Time