3933 US RO
UTE 11, CORTLAND, NEW YORK 13045
Phone Number: 1-800-345-3851 Fax Number: 607-758-3648
This report i s for the exclusive use of Intertek's Client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are
limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss,
expense or damage occasioned by the use of this report. Only the Client is authorized to copy or distribute this report and then only in its entirety. Any use of the Intertek
name or one of its marks for the sale or advertisement of the tested material, product or service m ust first be approved in writing by Intertek. The observations and test results
in this report are relevant only to the sample tested. This report by itself does not imply that the material, product, or service is or has ever been under an Intertek cert ification
program.
REPORT OF TEST
Panduit Corporation
10500 167th Street
Orland Park, IL 60467
The products described in this Report were tested for compliance to the standard(s) listed below. The products listed below are not
part of an Intertek Verification Program and the results are provided to the client as a o ne time performance test.
Reference Intertek Report
No.:
101816182CRT-001 Date: September 2
3, 2014
Test:
Electrical performance testing of a cabling configuration to the requirements of ANSI/TIA-568-C.2 for Category 6 channel.
Component Id
Manufacturer Description Part number
1 Panduit Equipment Cord UTPSP15Y
2, 5 Panduit Wall Outlet CJ688TG**
3 Panduit Zone Cord UJPBU15BLY
4 Panduit UTP CMP Horizontal Cable PUP6004**
6 Panduit Cross Connect Cord UTPSP7Y
7 Panduit Equipment Cord UTPSP9Y
Standard and sections use
d:
ANSI/TIA-568-C.2-2009: Balanced Twisted-Pair Telecommunications Cabling and Components Standards, dated August 2009
(Sections 6.2.1 to 6.2.26)
Conclusion:
The channel cabling configuration, as described above, was tested in accordance with the ANSI/TIA-568-C.2-2009 standard,
and did comply with the indicated applicable transmission requirements. The testing was performed at Intertek located in
Cortland, New York.
Reviewed and approved by:
John Cash Antoine Pelletier
Associate Engineer Engineer
Global Cabling Products Testing Global Cabling Products Testing