For product data sheets, visit www.cooperbussmann.com/datasheets/ulcsa
275
Fuse
Holders
& Blocks
Fuse Holders and Blocks
Modular Fuse Blocks
Specifications
Description: For use with Cooper Bussmann
®
high speed fuses.
Ratings:
SCCR: — 200kA RMS Sym. or fuse IR, whichever
is lower.
Agency Information: CE, UL Recognized, Guide EZLT2,
File No. E14853 up to 700V, CSA Certified, Class 6225-01,
File No. 47235 up to 700V.
BH Series Features and Benefits
• BH fuse blocks provide a wide range of mounting
configurations for Cooper Bussmann high speed fuses.
• BH fuse blocks have a Short-Circuit Current Rating of any
installed fuse up to 200kA RMS Sym.
Typical Applications
• Solid State Control Circuits
• VFDs
• UPS Systems
Catalog Numbers
BH-0001 BH-0122 BH-2001 BH-3004
BH-0002 BH-1001 BH-2002 BH-3033
BH-0003 BH-1002 BH-2003 BH-3144
BH-0111 BH-1003 BH-2031 BH-3145
BH-0112 BH-1131 BH-2032
BH-0113 BH-1132 BH-2033
BH-0121 BH-1133 BH-3003
Data Sheet: (BH-0) 1200; (BH-1) 1201; (BH-2) 1202;
(BH-3) 1203
Refer to the data sheet numbers below for the catalog code
description information.
Figure 1 Figure 2
BH Series Modular Type Fuse blocks for Class H &
J Fuses
Specifications
Description: 3-Pole only, modular type fuse blocks for
Class H & J fuses with standard reinforced retaining clips.
Ratings:
Volts: — 250V (0-60A See Catalog Numbers table)
— 600V (35-60A See Catalog Numbers table)
Amps: — 0-60A @ 250Vac/dc (See Catalog Numbers table)
— 35-60A@600V (See Catalog Numbers table)
SCCR: — Class J 200kA, Class H 10kA
Agency Information: CE, UL Recognized, Guide IZLT2,
File E14853, CSA Certified, Class 6225-01, File 47235.
Class H & J Features and Benefits
• H & J modular fuse blocks provide three pole 30 and 60
amp ratings for specific client requirements for separate line
and load fuse clip configurations.
Typical Applications
• Up to 60A, space confined, control circuits
CCaattaalloogg NNuummbbeerrss
FFuussee FFiigg..
SSccrreeww PPrreessssuurree PPllaattee CCllaassss VVoollttss AAmmppss NNoo..
11241-3SR* 11241-3PR* H 250 60 1
11242-3SR 11242-3PR 2
11241-3SR 11241-3PR 600 35 1
11242-3SR** 11242-3PR** 2
11239-3SR 11239-3PR 60 1
11240-3SR** 11240-3PR** 2
11241-3SR 11241-3PR J 600 35 1
11239-3SR* 11239-3PR* 60 1
Note: Order two blocks per fuse (matched or mixed.)
*11239 and 11241 have wire terminals and mounting holes located under fuse. (Figure 1)
**11240 and 11242 have wire terminals and mounting holes located at end of fuse. (Figure 2)
H
J
250
60
60
35
600