Specifications and
dimensions subject to
change without notice.
Eaton
11
21 Highway 74 South
Peachtree City, GA 30269
P: 770-486-4800
www.eaton.com/lighting
HR SERIES
technicaL Data
Heads
The lamp housing is constructed of flame- and
impact-resistant injection molded thermoplastic
with matching finish. The three dimensional
swivel assembly permits approximate aiming
adjustment from 80° vertical and 358° rotation.
The placement is secured with a lockable pivot
mounted on a rotating base ring.
Lamps
Designed specifically for emergency lighting
applications, the PAR 36 sealed beam type
design insures optimum glare-free trapezoidal
light distribution along with horizontal and
vertical adjustment by rotating the lens within
the housing.
Housing
The rugged 18-gauge die-formed steel housing
is finished with an attractive white corrosion-
resistant polyester powder coat paint. Cabinet
has keyhole mounting slots, universal mounting
pattern, and knockouts in rear and side for AC/
DC wiring connections and accessory cord set.
Up to three lighting heads can be mounted on
the cabinet.
Line-Latched
Sure-Lites’ line-latched electronic circuitry
makes installation easy and economical. A labor
efficient AC-activated load switch prevents
the lamps from turning on during installation
to a non-energized AC circuit. Line-latching
eliminates the need for a contractor’s return
to a job site to connect the batteries when the
building’s main power is permanently turned
on.
Solid-State Charger
Supplied with a 120/277 VAC, voltage
regulated solid-state charger. Immediately
upon restoration of AC current after a power
failure, the charger provides a high charge
rate. The charge circuit reacts to the condition
of the battery and alters the rate of charge in
order to maintain peak battery capacity and
maximize battery life. Solid-state construction
recharges the battery following a power failure
in accordance with UL 924.
Overload and Short-Circuit Protection
The solid-state overload monitoring device in
the DC circuit disconnects the lamp load from
the battery should excessive wattage demands
be made and automatically resets when the
overload or short-circuit is removed. This
overload current protective feature eliminates
the need for fuses or circuit breakers for the DC
load.
Brownout Circuit
The brownout circuit in Sure-Lites’ units
monitors the flow of AC current to the unit and
activates the emergency lighting system when
a predetermined reduction of AC power occurs.
This dip in voltage will cause most ballasted
fixtures to extinguish causing loss of normal
lighting even though a total power failure has
not occurred.
Solid-State Transfer
The unit incorporates a solid-state switching
transistor which eliminates corroded and pitted
contacts or mechanical failures associated with
relays. The switching circuit is designed to
detect a loss of AC voltage and automatically
energizes the lamps. Upon restoration of the
AC power, the emergency lamps will switch off
and the charger will automatically recharge the
battery.
Low-Voltage Disconnect
When the battery’s terminal voltage falls below
80% of the rated voltage, the low-voltage
circuitry disconnects the lighting load. The
disconnect remains in effect until normal utility
power is restored, preventing deep battery
discharge.
Test Switch/Power Indicator Light
Conveniently located Test Switch allows for
manual verification of proper operation of the
transfer circuit and emergency lamps. The
Power Indicator Light provides visual assurance
that the AC power is on.
Sealed Lead Calcium Battery
The fully sealed, long-life, maintenance-free
lead calcium battery is ideal for emergency
lighting applications. These recombinant cycle
batteries typically provide eight to ten years of
life and may be operated in any position.
Warranty
All Sure-Lites’ units are backed by a firm one-
year warranty against defect in material and
workmanship (excluding lamps). Maintenance-
free, long-life, sealed lead calcium batteries
carry a five-year pro-rata warranty.
10
FEET
LEFT
FEET
RIGHT
10
01020304050 60
FEET FROM LAMP (Measured on axis)
LAMP
AXIS
1FC 0.5 0.3 0.2 0.1
70
0
LAMP
AXIS
10
FEET
LEFT
FEET
RIGHT
10
01020304050 60
FEET FROM LAMP (Measured on axis)
1FC 0.5 0.3 0.2 0.1
70
0
Vertical Distribution
Lamp No. 29-84
Initial Lumens – 29-84 @ 132
Lamp No. 29-84
photometricS