MPS1000-□ Series
Features
��
Applications
Superior performance with small ripple Industrial automation control system
230VAC input Intelligent control system
100% full load burn-in test Electronic instruments and devices
Protections:short circuit/overload/over voltage/over temperature LED control
LED indicator for power on Household appliances
Optional installation accessories, can be installed flat
Compensating output voltage function
Instant overload capability is 105%-130%
Three prooftreatmentsuitable for severe environment
Seismic protection
All aluminum case
Surge protection
2 years warranty
Model Encoding
MPS
1000
24
Model name
Output wattage
Output voltage
-
MPS1000- Series
Specification
Input
Voltage range 176-264VAC 250-370VDC
AC current 10A/230VAC
Frequency range 47-63Hz
Inrush current (max) 90A/230VAC
Output
DC voltage (V) 5V 12V 24V 48V 60V 70V 80V 110V
Voltage ADJ.range ±10%
Rated Current(A) 150A 83.3A 41.7A 20.8A 16.7A 14.3A 12.5A 9A
Rated power(W) 750W 999.6W 1000.8W 998.4W 1002W 1001W 1000W 990W
Ripple & noise(max ) Note.2 150mVp-p 150mVp-p 200mVp-p 360mVp-p 480mVp-p 500mVp-p 600mVp-p 800mVp-p
Voltage tolerange Note.3 ±1% ±1% ±1% ±1% ±1% ±1% ±1% ±1%
Line regulation Note.4 ±0.5% ±0.5% ±0.5% ±0.5% ±0.5% ±0.5% ±0.5% ±0.5%
Load regulation Note.5 ±0.5% ±0.5% ±0.5% ±0.5% ±0.5% ±0.5% ±0.5% ±0.5%
Efficiency 85.00% 85.00% 88.00% 89.00% 89.00% 89.00% 89.00% 89.00%
Setuprise time 1000ms 50ms/230VAC (at full load)
Hold up time 20ms/230VAC (at full load)
Status indicator Green LED
Protection
Overload
105%-130% rated output power
Protection type: 5-48V shut-off mode60-110V Limiting current output
Over voltage(V)
5.75-6.75V 13.8-16.2V 27.6-32.4V 55.2-64.8V 69-81V 80.5-94.5V 92-108V 126.5-148.5V
Protection type: shut down o/p voltage,re power on to recover
Over temperature Protection type:shut down o/p voltage,recovers antomatically after temperature goes down
Safety and EMC
Withstand voltage I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
Isolation resistance I/P-O/P,I/P-FG,O/P-FG:100M Ohms/500VDC/25 /70RH
Safety standards Note.6 Design refer to EN IEC 62368-1GB4943.1
EMC emission
Parameter Standard Test Level
Conducted EN 55032 Class A
Radiated EN 55032 Class A
Voltage Flicker EN 61000-3-3 Design refer to Class A
Harmonic Current EN IEC 61000-3-2 Design refer to Class A
EMC immunity
Parameter Standard Test Level
ESD EN 61000-4-2 Level 3 8KV air;Level 2 4KV contact
Radiated Susceptibility EN 61000-4-3 Level 2 3V/m
EFT/Burest EN 61000-4-4 Level 3 2KV
Surge EN 61000-4-5
Level 3 2KV/Line-Line;Level3 4kV/Line-Line-FG
Conducted EN 61000-4-6 Level 2 3V
Magnetic Field EN 61000-4-8 Level 2 3A/m
Voltage Dips and interruptions EN 61000-4-11
<5% residual voltage for 0.5 cycles ,70% residual voltage for 25
cycles ,<5% residual voltage for 250 cycles:
Environmental
Working temperature - 20+60 (Refer to "Derating curve "
Storage temperature 40+85
Storage humidity 10-95RH
Vibration Component:10-500Hz,2G 10 min/1cycle 60 min each along X,Y,Z axes
MPS1000- Series