MLR015-□F Series
Features Applications
Ultra slim design with 17.5mm(1SU) width
Building automation
Pass LPS(Limited power source)
Household control system
No load power consumption0.3W
Industrial control system
DIN rail TS-35/7.5 or15 mountable
Factory automation
Full range AC input 85~264VAC(277VAC operational)
Electro-mechanical equipment
Isolation Class
Cooling by free air convection(Operation Temp.-30~+70°C)
LED indicator for power ON
Over voltage classIII
ProtectionsShort circuit/Over load/Over voltage
3 years warranty
Model encoding
MLR
Series
-
015
Output
Wattage
24
Output
Voltage
F
Input Voltage
rating
MLR015-□F Series 2023/03/16
Specification
Input
Input voltage range 85~264VAC(277VAC Operational) 120~370VDC(390VDC Operational)
Frequency range 47~63Hz
AC current(Typ.) 0.5A/115VAC 0.25A/230VAC
Inrush current (Typ.) Cold start 25A/115VAC 45A/230VAC
Output
Model MLR015-05F MLR015-12F MLR015-15F MLR015-24F MLR015-48F
Output Voltage 5V 12V 15V 24V 48V
Efficiency(Typ.) 80.0% 85% 85.5% 86% 87%
Voltage ADJ range 4.55.5V 10.813.8V 13.518V 21.629V 43.255.2V
Rated current 2.4A 1.25A 1A 0.63A 0.32A
Current range 02.4A 01.25A 01A 00.63A 00.32A
Rated power 12W 15W 15W 15.2W 15.4W
Ripple & Noise(Max)*2 80mVp-p 120mVp-p 120mVp-p 150mVp-p 240mVp-p
Voltage tolerance *3 ±2.0% ±1.0% ±1.0% ±1.0% ±1.0%
Line Regulation ±1.0% ±1.0% ±1.0% ±1.0% ±1.0%
Load Regulation ±1.0% ±1.0% ±1.0% ±1.0% ±1.0%
Setup, Rise time 2000ms,80ms/230VAC 2000ms,80ms/115VAC(@Full load)
Holdup time (Typ.) 30ms/230VAC 12ms/115VAC(@Full load)
Indicator Green LED
Protection
Over load
110%145% of rated output power
Hiccup mode when output voltage50%, recovers automatically after fault condition is removed
Constant current limiting when output voltage between 50%100%, recovers automatically after fault condition is removed
Over voltage
5.756.75V 14.216.2V 18.822.5V 3036V 56.564.8V
Shut down output voltage, clamping by zener diode
Safety & EMC
Withstand Voltage I/P-O/P:4KVAC
Isolation resistance I/P-O/P:100M Ohms/500VDC/25/70% RH
Safety standards Design refer to EN IEC 62368-1GB4943.1
EMC Emission
Parameter Standard Test Level/Note
Conducted EN 55032 Class B
Radiated EN 55032 Class B
Voltage Flicker EN 61000-3-3 Design refer to Class A
Harmonic Current EN IEC 61000-3-2 Design refer to Class A
EMC Immunity
Parameter Standard Test Level/Note
ESD EN61000-4-2 Level 3 8KV air
Radiated Susceptibility EN61000-4-3 Level 3 10V/m
EFT/Burest EN61000-4-4 Level 3 2KV
Surge EN61000-4-5 Level 3 2KV/L-N
Conducted EN61000-4-6 Level 2 3V/m
Magnetic Field EN61000-4-8 Level 2 3A/m
Voltage Dips and interruptions EN 61000-4-11
>95% dip 0.5 periods, 30% dip 25 periods,
>95% interruptions 250 periods
Environment
Operating Temp. -30~+70℃(Refer to "Derating Curve")
Operating Humidity 20~90% RH,non-condensing
Starage Temp. &
Humidity
-40~+85℃,10~95% RH,non-condensing
Temp. coefficient ±0.03%/℃ (0~50℃)
Vibration 10~500Hz, 2G 10min/1 cycle, period for 60 min. each along X, Y, Z axes;Mounting: Compliance to IEC60068-2-6
Operating Altitude 2000m(*4)
Over Voltage Category ⅡI;According to EN61558, EN50178,EN60664-1, EN62477-1; Altitude up to 2000m