MGR020-□F/FR Series
Features
Universal AC input/full range
Protections:short circuit/overload/over voltage
Cooling by free air convection
Can be installed on DIN rail TS-35/7.5 or 15
Built in DC OK active signal
LED indicator for power on
No load power consumption<0.75W
100% full load burn -in test
3 years warranty
Model
Encoding
MGR
-
020
24
F
Model name
Output wattage
Output voltage
Input voltage rating
R
With DC/OK function
MGR020-F/FR Series
Specification
Input
Voltage range 85-264VAC 120-370VDC
AC current 0.55A/115VAC 0.35A/230VAC
Frequency range 47-63Hz
Inrush current (max) Cold start20A/115VAC 40A/230VAC
Output
DC voltage (V) 5V 12V 15V 24V
Efficiency 76% 80% 80% 83%
Rated Current (A) 3A 1.67A 1.34A 1A
Rated power(W) 15W 20W 20W 24W
Voltage ADJ.range 4.75-5.5V 10.8-13.2V 13.5-16.5V 21.6-26.4V
Ripple & noise(max ) Note.2 80mVp-p 120mVp-p 120mVp-p 150mVp-p
Voltage tolerange Note.3 ±2% ±1% ±1% ±1%
Line regulation ±1% ±1% ±1% ±1%
Load regulation ±1% ±1% ±1% ±1%
Setuprise time Note.4 500ms 30ms/230VAC 1000ms 30ms/115VAC(at full load)
Hold up time 50ms/230VAC 20ms/115VAC(at full load)
Status indicator Green LED
Protection
Overload
110%-150% rated output power
Protection type: Hiccup mode ,recovers automatically after fault condition is removed
Over voltage(V)
5.75-6.75V 13.8-16.2V 17.25-20.25V 27.6-32.4V
Protection type:Shut down O/P voltage ,re-power on to recover
DC OK signal(max.) 3.75-6V/50mA 9-13.5V/40mA 11.5-16.5V/40mA 18-27V/20mA
Safety and EMC
Withstand voltage I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
Isolation resistance I/P-O/P,I/P-FG,O/P-FG :100M Ohms/500VDC/25/70RH
Safety standards Design reference EN IEC 62368-1GB 4943.1
EMC emission
Parameter Standard Test Level/Note
Conducted EN 55032 Class B
Radiated EN 55032 Class B
Voltage Flicker EN 61000-3-3 Design reference Class A
Harmonic Current EN IEC 61000-3-2 Design reference Class A
EMC immunity
Parameter Standard Test Level/Note
ESD EN 61000-4-2 Level 3 8KV air
Radiated Susceptibility EN 61000-4-3 Level 2 3V/m
EFT/Burest EN 61000-4-4 Level 2 1KV/5KHZ
Surge EN 61000-4-5 Level 2 1KV/L-N;Level2 2KV/L-N-FG
Conducted EN 61000-4-6 Level 2 3V
Magnetic Field EN 61000-4-8 Level 2 3A/m
Voltage Dips and interruptions EN 61000-4-11
<5% residual voltage for 0.5 cycles ,70% residual voltage
for 25
cycles ,<5% residual voltage for 250 cycles:
Environmental
Working temperature - 20+70 Refer to "Derating curve "
Storage temperature 40+85
Storage humidity 10-95RH
Vibration Component:10-500Hz,2G 10 min/1cycle 60 min each along X,Y,Z axes
MGR020-F/FR Series