EDR050-□ Series
Features
TS35 DIN rail installation
Compact size, easy installation with accessory
Compliance to ROHS certificate
Power On LED indicator
Protections:short circuit/overload/over voltage
Compact size/High efficiency/High reliable
100% full load burn -in test
3 years warranty
Model encoding
EDR
050
-
24
Series
Output power
Output Voltage
EDR050-□ Series
Specification
Input
Voltage range 200240VAC/280370VDC
AC current 1A Max. Vi=200240VAC
Frequency 4763Hz
Inrush current (max) 45A/230VAC
Output
Ratedf voltage 24V
Efficiency(Typ) 85%
Voltage ADJ.range ±10
Rated Current (A) 2.1A
Rated power(W) 50W
Ripple & noise(max ) Note.2 150mVp-p
Voltage tolerange Note.3 ±1%
Line regulation ±1%
Load regulation ±1%
Setuprise time Note.4 1000ms 10ms/230VAC
Hold up time 30ms/230VAC
Status indicator Green LED
Protection
Overload
150%-250% of rated output power
Protection mode: Hiccup mode, recovers automatically after fault condition is removed
Over voltage(V)
28.535V
Protection type: Hiccup, recovers automatically after fault condition is removed
Safety and EMC
Withstand voltage I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
Isolation resistance I/P-O/P,I/P-FG,O/P-FG:100M Ohms/500VDC/25/70RH
Safety standards Design refer to EN IEC 62368-1GB 4943.1
EMC Emission
Parameter Standard Test level
Conducted EN 55032 Class A
Radiated EN 55032 Class A
Voltage Flicker EN 61000-3-3 Design refer to Class A
Harmonic Current EN IEC 61000-3-2 Design refer toClass A
EMC Immunity
Parameter Standard Test level
ESD EN 61000-4-2 Level 3 8KV air
Radiated Susceptibility EN 61000-4-3 Level 2 3V/m
EFT/Burest EN 61000-4-4 Level 3 2KV
Surge EN 61000-4-5 Level 3 2KV/L-N;Level3 4kV/L-N-FG
Conucted EN 61000-4-6 Level 2 3V/m
Magnetic Field EN 61000-4-8 Level 2 3A/m
Voltage Dips and interruptions EN 61000-4-11
>95% dip 0.5 periods, 30% dip 25 periods,
>95% interruptions 250 periods
EDR050-□ Series