2 of 6
Littelfuse.com/SB5000
©2024 Littelfuse, Inc.
Specifications are subject to change without notice.
Revised: 04/16/2024
Shock Block - GFCI / SPGFCI / EGFPD
SB5000 Series
Features & Benefits
FEATURES BENEFITS
UL 943 inverse time trip curve
Inverse time detection circuit protects people while also reducing the
probability of nuisance tripping
DFT (Discrete Fourier Transform) filtering algorithm Eliminates nuisance trips due to harmonics
Minimum trip time <20 msec Reduces the risk of ventricular fibrillation for leakage current of 250 mA and above
Fixed 6 mA (UL 943) or 20 mA (UL 943C) trip level
UL Listed GFCI and Special-Purpose GFCI personnel protection for industrial
and commercial loads up to 100 A (GFCI versions)
Selectable trip levels 6–100 mA
Settings below 20 mA provide extra safety. The settings above 20 mA can
reduce nuisance tripping on systems with high-leakage current (EGFPD versions)
Two-stage ground monitor with Zener termination
that meets UL 943C, CSA M421
Proactively protects from shock by tripping if continuity of ground wire
between SB5000 and equipment is compromised
Flexible configuration
Selectable manual reset or auto-reset for brownout, power-up, and ground
monitor interruptions to fit plant safety protocols
Conformal coating
Equipped with conformally coated circuit boards to protect against corrosion and
moisture
Auxiliary contact Alerts your SCADA system if the SB5000 is energized or tripped
Automatic self-test The SB5000 will continuously test itself and will trip if there is an internal failure
GFCI Class A, C, D, and EGFPD options in one series Simplified planning and operator familiarity for multiple applications/requirements
Applications
• For applications where people,
electrical equipment, and water
are present
• Agriculture
• Amusement parks
• Commercial kitchens
• Construction
• Food and beverage
• Horticultural lighting
• Maintenance shops
• Manufacturing
• Mining
• Oil and gas
• Pools, spas, fountains, water
features
• Vehicle service centers
• Water/wastewater
Specifications
Voltage Rating 208 V, 240 V, 480 V, 600 V
Current Rating 32, 60, 80, or 100 A
System Type Three-phase, 3-wire (no neutral), 60 Hz; Single-phase, 2-wire (no neutral), 60 Hz;
Single-phase, 3-wire (with neutral), 60 Hz for EGFPD versions only
Short-Circuit Current Rating 10,000 A (for SB5032 and SB5060); 50,000A (for SB5080 and SB5100)
Trip Level Settings Fixed at 6 mA (Class A models); Fixed at 20 mA (Class C/D models)
Selectable 6, 10, 20, 30, 40, 50, 60, 70, 80, 90, 100 mA (EGFPD models)
Trip Time Setting Inverse time curve according to UL 943
Ground Monitoring Circuit Selectable short or Zener termination; Fail-safe; CSA M421 compliant
Enclosure Polycarbonate: IP 69K and NEMA 4X (Outdoor), Polycarbonate, Lockable
Stainless Steel: IP 69K and NEMA 4X, AISI 304 steel, FDA compliant blue silicone gasket
Stainless Steel: Class II, Division 2, Groups E, F, G for Hazardous Locations and T6 Temperature Code
Operating Temperature -35 °C (-31 °F) to 40 °C (104 °F), up to 66 °C (151 °F) with derating
Dimensions H 285.6 mm (11.25 in.); W 244.4 mm (9.62 in.); D 119.6 mm (4.71 in.) – for Polycarbonatate 32 A and 60 A
H 358.2 mm (14.10 in.); W 250.5 mm (9.86 in.); D 170 mm (6.69 in.) – for Stainless Steel 32 A and 60 A
H 383.4 mm (15.09 in.); W 327.1 mm (12.88 in.); D 137.4 mm (5.5 in.) – for Polycarbonate 80 A and 100 A