www.panduit.com/verisafe
specifications
Insulation piercing connector for copper wire with two mechanically isolated taps. Optimized for use
with VeriSafe
™
AVT sensor leads when prepared with Panduit ferrules, P/N F80-12.
VeriSafe
™
Insulation Piercing Connector
SPECIFICATION SHEET
applications
The VeriSafe
™
Insulation Piercing Connector provides a fast,
secure, and reliable way to terminate AVT sensor leads. The
compact connector design accommodates up to two taps in a
single housing that fully insulates both connections. The patent
pending connector allows taps to be made without compromising
the integrity of conductors and includes integrated strain relief.
Installation is fast and easy without the need to remove insulation.
Ideal for new and retrofit applications, connections can be made
without modifying existing conductor runs.
key features and benefits
Compact and
space saving:
Terminate two taps with a single connector
Fewer parts, less space needed for each installation
Optimized for use with VeriSafe
™
Absence of Voltage Tester sensor
leads
Fast installation: Insulation piercing design allows for installation without the need to
strip insulation from conductors
Easily retrofit existing cable runs without modifying conductors
Fully insulated design: Safe and reliable connections
Secure connections: Taps are made without compromising the integrity of conductors
Housing includes integrated strain relief
Flexible design: Family of connectors covers a wide range of cable runs
Suitable for new or retrofit applications
technical information
Cable run: AWG 14 - 3/0: Copper conductors, Solid or stranded Class B & C,
except 3/0 STR only.
AWG 4/0 - 500 MCM: Copper conductors, Stranded Class B & C.
Not rated for flexible strand classes.
Taps: (2) 14 – 16 AWG stranded Class K
For VeriSafe AVT sensor leads prepared with F80-12 ferrules
Connector materials: Housing – polyamide
Insulator – elastomeric polymer
Operating temperature: Up to 90°C (194°F)
Voltage range: 14 - 3/0 AWG: 600V maximum
AWG 4/0 - 500 MCM: 1000V maximum
Insulation Piercing Connectors
VS-CKP14-6
VeriSafe
™
Insulation
Piercing Connection Kit
for Tapping 14 to 6 AWG
conductors. Kit includes
3 connectors for
installation of 1 AVT.
VS-CKP4-000
VeriSafe
™
Insulation
Piercing Connection Kit
for Tapping 4 to 3/0 AWG
conductors. Kit includes
3 connectors for
installation of 1 AVT.
VeriSafe™ Insulation
Piercing Connection Kit
for Tapping AWG 4/0 to
500MCM conductors.
Rated for 1KV installa-
tions. Kit includes 3 con-
nectors for installation of
1 AVT.
VS-CKP1K4/0-500