PANDUIT FOR PUBLIC USE | April 20, 2021 | P: 800-777-3300 | Page 1
VeriSafeAVT Sensor Lead Connection Options
NOTE: See VeriSafe AVT Instruction Manual for complete Installation Instructions and Commissioning Checklist
1) Where to Install
The VeriSafe AVT is to be installed at the point in the circuit where you would normally test for voltage. If
there are more than one energy sources within the enclosure, multiple AVTs will be needed to test each
source (each AVT is designed to test one energy source from one to three phases).
2) General Information
The VeriSafe AVT is provided with 14 AWG Class K stranded sensor leads. Ferrules or terminals are
recommended for all sensor lead terminations to ensure reliable connections with stranded wire.
There are four sets of color-coded sensor leads (three conductors and ground). Each set of sensor leads has a
detection lead and a termination lead. The detection lead is used to detect voltage and the termination lead
is used to verify that the detection lead is in contact with a conductor. The termination lead does not detect
voltage. There are no labels distinguishing the detection and termination leads because it is critical that they
are both properly terminated.
Sensor leads for each phase and ground must not be mechanically terminated at the same point for the AVT
to function properly (see Figures 1 and 2). For example, if the termination shown in Figure 2 fails and the
sensor leads remain in contact with each other (yet no longer in contact with the conductor), the installation
test will be defeated for that set of sensor leads which may lead to inaccurate results from the AVT. If the
detection lead is not contacting a conductor, the result of the installation test will prevent the AVT from
returning a green absence of voltage indication.
Figure 1 Example of properly
terminated sensor leads. Leads are
not mechanically connected, and
termination points are insulated.
Figure 2 Terminating both sensor
leads at the same point may result
in inaccurate AVT results.
PANDUIT FOR PUBLIC USE | April 20, 2021 | P: 800-777-3300 | Page 2
There is no maximum distance limitation between the two leads on each phase, however there should not be
any circuit elements (ex. Circuit breaker, fuse, VFD, switch or similar control devices etc.) installed between
each pair of sensor leads. (see diagram below)
Circuit Breaker or any
other circuit elements
should NOT be placed
between each set of
sensor leads
Install BOTH sensor
leads for each phase
on either the line or
load side