Φ16x18.2mm
Gas Discharge Tubes H5R16-600L
1: Applications
AC Power line L-N applications
Class I and Class II Surge protection
2: Dimension in mm
2: Dimension
in mm
Specification of H5R16-600L
Nominal Dc spark-over voltage @ 100V/s
A-B >450V
A-C >450V
Maximum impulse spark-over voltage @ 1.2/50μs,6KV
A-B 1500V
A-C(Add MOV) 1500V
Response time
50ns
Insulation resistance @250V
1GΩ
Class I according to IEC 61643-11
Max continuous operating voltage at 50/60 Hz Uc
Nominal discharge current 8/20μs In
Impulse current 10/350μs Iimp
Follow Current at 50/60Hz at 255V If
255V
30KA
12KA
500A
Class II according to IEC 61643-11
Max continuous operating voltage at 50/60 Hz Uc
Nominal discharge current 8/20μs In
Maximum discharge current 8/20μs Imax
Follow Current at 50/60Hz at 255V If
255V
30KA
60KA
500A
Weight
~ 21g
Delivery time
25days
Voltage protection level
2KV
Quantity of electric charge
7.5As
Quantity of electrodes
5PCS
Marking, Green
600 YY
600 - Nominal voltage
YY - Year of production
Φ16x18.2mm
3:Application Figure
`
ShenZhen HuaXingAn Electronics CO.,LTD 2 Tel: +86-755-27465585
HUAAN LIMITED www.huaandz.com Email: sales@huaandz.com
What can we do for our GDT?
1:We Can customize voltage: 500V,800V...etc
2:We Can developed low impulse GDT
3: We Can customize Uc,In, Imax , limp ,If,TOV.
4: We Can developed cut off follow current 100A within 1
cycle when passing zero under AC260V(50Hz)
5:We Can customize multi-gap GDT used in DC or AC(L-N)
over voltage protection
6:We Can customize GDT shape, marking, special Lead
wire
7: We Can surpass our GDT competitors,help you pass the
GDT test project & improve the GDT you currently use.
8:We can provide fast GDT delivery,Solve your GDT
delivery time problem
9:We can help you analyze the competitor’s parameters
and tell you our perfect replacement GDT part number.