CONTACT INFO:
prysmianoilandgas@prysmiangroup.com
www.prysmiangroup.com/contact-us
1
LV&C BS FR - 09/2017
DESIGN & CONSTRUCTION
CONDUCTOR
Cu
Tinned annealed copper conductor according
to IEC 60228 cl. 2 (or cl.5 on request)
INSULATION
EPR
Mica tapes (s) + EPR GP4 according
to BS 7655-1.2
BEDDING/INNER COVERING
(only armoured versions)
EVA
Flame retardant, halogen free
thermoset compound, SW4 BS 7655-2.6
ARMOURING
(only armoured versions)
GSWB
Galvanized steel wire braid
TCWB
Tinned copper wire braid
TPBWB
Tinned Phosphorous bronze wire braid
(single core cable)
OUTER SHEATH
EVA
Flame retardant, halogen free thermoset
compound, SW4 BS 7655-2.6
Oil & Gas - Cable Solutions
BS 7917
Exploration & Production - Oshore
Low Voltage & Control Cables
Cu/MGT/EPR/EVA 0,6/1 kV
Cu/MGT/EPR/EVA/GSWB or TCWB or TPBWB/EVA 0,6/1 kV
Low Voltage cables, fire retardant, fire resistant, low smoke, halogen free.
Unarmoured/Armoured.
APPLICATION
Low Voltage & Control cables are used for fixed
installations on ships and oshore platforms
in a wide range of power supply and control
applications. Prysmian oers a wide range of
LV & Control cables with diverse design options
depending on the reference standards and
customer requirements.
STANDARDS & APPROVALS
BS 7917 Design guidelines
IEC 60092-352 Choice and installation of electric cables
BS 7655-1.2 Insulating materials
BS 7655-2.6 Sheathing materials
IEC 60332-1-2 Flame retardance
IEC-60332-3-22 Fire retardance
IEC 60331-1,-2,-21 Fire Resistance
IEC-60754-1 Halogen free properties
IEC-61034-2 Smoke emission properties
Lloyds Register of Shipping (LRS)
American Bureau of Shippings (ABS)
Bureau Veritas (BV)
Russiam Maritime Register of Shipping (RMRS)
Det Norske Veritas-GermanischerLloyd (DNV-GL)
RINa (Registro Italiano Navale)
1
2
3
4
5
or
or
1
2
3
4
5
CONTACT INFO:
prysmianoilandgas@prysmiangroup.com
www.prysmiangroup.com/contact-us
2
LV&C BS FR - 09/2017
Oil & Gas - Cable Solutions
BS 7917
Exploration & Production - Oshore
Low Voltage & Control Cables
This product information sheet is provided for reference only.
Please consult the factory or your representative to confirm all engineering information or refer to the related catalogues available in the local countries website.
QUALITY & TESTING
Prysmian has a built-in multi-step quality assurance program, covering the production process from cable design and raw material
purchases to final inspection and testing documentation.
The ISO 9001 quality system of Prysmian Group (together with ISO 14001 and OHSAS 18001) has been assessed, approved and is currently
audited by SGS.
PERFORMANCES/RATINGS
GOOD
CHEMICAL
RESISTANCE
IEC 60332-1-2
IIEC 60332-3-22
IEC 60331-1,-2,-21
FIRE
BEHAVIOUR
GOOD
IMPACTS
low
LOW EMISSION
SMOKE DENSITY,
CORROSIVITY
AND TOXICITY
+90 °C
MAX
OPERATING
TEMPERATURE
-20 °C
MIN. PERMISSIBLE
AMBIENT TEMPERATURE
DURING LAYING
250
°C
+250 °C
SHORT
CIRCUIT
TEMPERATURE
low
GOOD
UV
RESISTANCE