CONTACT INFO:
prysmianoilandgas@prysmiangroup.com
www.prysmiangroup.com/contact-us
1
LV&C Marine - 09/2017
DESIGN & CONSTRUCTION
CONDUCTOR
Cu
Tinned (or plain) annealed copper conductor
according to IEC 60228 cl. 2 (or cl.5 on request)
INSULATION
XLPE
HF-XLPE according to IEC 60092-351
thickness according to IEC 60092-353
BEDDING/INNER SHEATH
LSZH
Halogen free thermoplastic compound,SHF1
according to IEC 60092-360
ARMOURING
TCWB
Tinned copper wire braid
GSWB
Galvanized steel wire braid
OUTER SHEATH
LSZH
Halogen free thermoplastic compound,SHF1
according to IEC 60092-360
Oil & Gas - Cable Solutions
IEC - Marine FPSO
Exploration & Production - Oshore
Low Voltage & Control Cables
Cu/XLPE/LSZH/TCWB or GSWB/LSZH 0,6/1 kV
Low Voltage cables, fire retardant, low smoke, halogen free. Armoured.
Available also in Fire Resistant version.
APPLICATION
Low Voltage & Control cables are used for fixed
installations on ships and oshore platforms
in a wide range of power supply and control
applications. Prysmian oers a wide range of
LV & Control cables with diverse design options
depending on the reference standards and
customer requirements.
STANDARDS & APPROVALS
IEC 60092-350 Design guidelines
IEC 60092-352 Choice and installation of electric cables
IEC-60092-353 Design guidelines
IEC 60092-360 Insulating and sheathing materials
IEC 60332-1-2 Flame retardance
IEC-60332-3-22 Fire retardance
IEC-60754-1 Halogen free properties
IEC-61034-2 Smoke emission properties
Det Norske Veritas-Germanischer Lloyd (DNV-GL)
American Bureau of Shippings (ABS)
Lloyds Register of Shipping (LRS)
Bureau Veritas (BV)
RINa (Registro Italiano Navale)
1
2
3
4
5
or
1
2
3
4
5
CONTACT INFO:
prysmianoilandgas@prysmiangroup.com
www.prysmiangroup.com/contact-us
2
LV&C Marine - 09/2017
Oil & Gas - Cable Solutions
IEC - Marine FPSO
Exploration & Production - Oshore
Low Voltage & Control Cables
This product information sheet is provided for reference only.
Please consult the factory or your representative to confirm all engineering information or refer to the related catalogues available in the local countries website.
QUALITY & TESTING
Prysmian has a built-in multi-step quality assurance program, covering the production process from cable design and raw material
purchases to final inspection and testing documentation.
The ISO 9001 quality system of Prysmian Group (together with ISO 14001 and OHSAS 18001) has been assessed, approved and is currently
audited by SGS.
PERFORMANCES/RATINGS
VERY GOOD
CHEMICAL
RESISTANCE
IEC 60332-1-2
IIEC 60332-3-22
FIRE
BEHAVIOUR
GOOD
IMPACTS
low
LOW EMISSION
SMOKE DENSITY,
CORROSIVITY
AND TOXICITY
+90 °C
MAX
OPERATING
TEMPERATURE
-5 °C
MIN. PERMISSIBLE
AMBIENT TEMPERATURE
DURING LAYING
250
°C
+250 °C
SHORT
CIRCUIT
TEMPERATURE
low
GOOD
UV
RESISTANCE