Features
Built-in Web Server
Web HMI
Support for both Modbus TCP and Modbus UDP Protocols
Communication Security
Dual Watchdog
Wide Operating Temperature Range: -25 to +75°C
I/O Pair Connection
Built-in I/O
Thermistor Input: 8 Channels
DO: 4 Channels
Ethernet I/O Module with 8-channel Thermistor Inputs,
4-channel DO
Model ET-7005 PET-7005
Software
Built-in Web Server Yes
Web HMI Yes
I/O Pair Connection Yes
Communication
Ethernet Port 10/100 Base-TX with Auto MDI/MDI-X
PoE - Yes
Protocol Modbus TCP, Modbus UDP
Security ID, Password and IP Filter
Dual Watchdog Yes, Module (0.8 seconds), Communication (Programmable)
LED Indicators
L1 (System Running) Yes
L2 (Ethernet Link/Act) Yes
L3 (Ethernet 10/100 M Speed) Yes
PoE Power - Yes
2-Way Isolation
Ethernet 1500 V
DC
-
I/O 2500 V
DC
2500 V
DC
EMS Protection
ESD (IEC 61000-4-2) ±4 kV Contact for Each Terminal and ±8 kV Air for Random Point
EFT (IEC 61000-4-4) ±4 kV for Power Line
Power
Reverse Polarity Protection Yes
Powered from Terminal Block Yes, 10 ~ 30 V
DC
Yes, 12 ~ 48 V
DC
Powered from PoE - Yes, IEEE 802.3af, Class1
Power Output
- -
Consumption 2.1 W (Max.) 3.0 W (Max.)
Mechanical
Dimensions (L x W x H) 123 mm x 72 mm x 35 mm
Installation DIN-Rail or Wall Mounting
Environment
Operating Temperature -25 to +75°C
Storage Temperature -30 to +80°C
Humidity 10 to 90% RH, Non-condensing
Introduction
System Specifi cations
ET-7005/PET-7005 is used for measuring temperature by the thermistor. It supports many kinds of thermistors and features individual channel
configuration which means that eight of its input channels can individually be configured with different kind of thermistor and supports
user-defined types by specifying the Steinhart coefficients to add other thermistors, if necessary. Besides, ET-7005/PET-7005 also has
4-channel digital outputs for alarm output with Short-circuit protection and overload protection. Adding 2500 V
DC
intra-module isolation
and 110 V
DC
/V
AC
overvoltage protection for thermistor on ET-7005/PET-7005 makes itself running with higher reliability.
ET-7005 PET-7005
ICP DAS CO., LTD Website: http://www.icpdas.com Vol.
2/2
2020.08
Thermistor Input
Channels 8 (Diff erential)
Sensor Type
(thermistor)
Precon ST-A3, Fenwell U, YSI L100, YSI L300,
YSI L1000, YSI B2252, YSI B3000, YSI B5000,
YSI B6000, YSI B10000, YSI H10000,
YSI H30000, User-defi ned
Individual Channel Confi guration Yes
Resolution 16-bit
Sampling Rate 10 Sample/Second (Total)
Accuracy +/-0.1% or better
Zero Drift +/-20 μV/°C
Span Drift +/-25 ppm/°C
Overvoltage Protection 110 V
DC
/V
AC
Common Mode Rejection 86 dB
Normal Mode Rejection 100 dB
Open Wire Detection Yes
Digital Output
Channels 4
Type Isolated Open Collector
Sink/Source (NPN/PNP) Sink
Max. Load Current 700 mA/Channel
Load Voltage 5 V
DC
~ 50 V
DC
Overvoltage Protection 60 V
DC
Overload Protection 1.4 A
Short-circuit Protection Yes
Power-on Value Yes, Programmable
Safe Value Yes, Programmable
I/O Specifi cations
Pin Assignments
ET-7005 CR Ethernet I/O Module with 8-ch Thermistor Inputs, 4-channel Digital Output (RoHS)
PET-7005 CR PoE Ethernet I/O Module with 8-ch Thermistor Inputs, 4-channel Digital Output (RoHS)
Ordering Information
Thermistor Input
Digital Output
ON State
Readback as 1
OFF State
Readback as 0
Open Collector (Sink)
Wire Connections
ON State
Readback as 1
OFF State
Readback as 0
Thermistor Input
Thermistor Input
Thermistor Input
ON State
Readback as 1
Readback as 1
OFF State
OFF State
Readback as 0
Readback as 0
PET-7005: PoE
ET-7005: +10 ~ +30 V
DC
PET-7005: +12 ~ +48 V
DC