Assembly instructions (Original instructions)
8068856
2017-05
[8068858]
†‡
Connecting cable
VMPAL-KM...-S-SD...-IP67
Festo AG & Co. KG
Ruiter Straße 82
73734 Esslingen
Germany
+49 711 347-0
www.festo.com
1. Applicable documents
All available documents for the product www.festo.com/pk
2. Intended use
Connection of the multi-pin plug connection of valve terminal MPA-L
to a controller.
3. Structure
18435d_1
1 Cable
Field device side:
2 Socket strip
Sub-D socket
25-pin/44-pin
3 Screw
Controller side:
(1x)
(1x)
(4x)
4 Wire end
1)
(25x/36x)
1
)
Cut off bluntly
4. Not in scope of delivery
18435d_2
5 Valve terminal
MPA-L
(1x)
5. Safety
Switch off power supply and compressed air before mounting work.
Do not touch the contact surfaces of the plug connectors.
Observe the handling specifications for electrostatically sensitive
components.
Comply with tightening torques.
6. Contact allocation
Socket strip 2 (25-pin) Socket strip 2 (44-pin)
009
956
42
009
956
46
1)
Wire ends must be shortened and pre-assembled as needed.
7. Pin allocation
25-pin 44-pin
Colour code
2
)
Pin Colour code
2)
Pin
WH 1 WH 1
GN 2 GN 2
YE 3 YE 3
GY 4 GY 4
PK 5 PK 5
BU 6 BU 6
RD 7 RD 7
VT 8 VT 8
GYPK 9 GYPK 9
RDBU 10 RDBU 10
GNWH 11 GNWH 11
BNGN 12 BNGN 12
YEWH 13 YEWH 13
BNYE 14 BNYE 14
GYWH 15 GYWH 15
BNGY 16 BNGY 16
WHPK 17 WHPK 17
BNPK 18 BNPK 18
BUWH 19 BUWH 19
BNBU 20 BNBU 20
RDWH 21 RDWH 21
BNRD 22 BNRD 22
BKWH 23 BKWH 23
BN 24 BN 24
BK 25 BKBN 25
GNGY 26
YEGY 27
GNPK 28
YEPK 29
GNBU 30
YEBU 31
RDGN 32
33 ... 40
RDYE 41
BKGN 42
BKYE 43
BK 44
2)
Colour code according to IEC 60757:1983-01
8. Technical data
VMPAL KM-S-SD25 KM-S-SD44 KMSK
Cable composition [mm²] 25x0.34 36x0.25 25x0.34
Current rating [A] 2.62 1.44 2.62
Operating voltage range
AC/DC
U
B
[V] 0 … 30
Surge resistance [kV] 2.4
Cable diameter D [mm] 10.2 ± 0.25 9.6 ± 0.2 11.2 ± 0.2
Cable bending radius
Fixed cable installation R [mm] 41 38 38
Flexible cable installation R [mm] 122 115 112
Suitable for energy chains No No Yes
Mounting space A [mm] 224
Degree of protection in mounted status
Field device side IP67
Ambient temperature
Field device side [°C] 5 … +50
Fixed cable installation [°C] 5 … +80 40 … +80 40 … +70
Flexible cable installation [°C] 40 … +80 5 … +80 5 … +70
Cable sheath material PVC PVC TPE-U(PUR)
9. Mounting
18435d_3
Plug the socket strip 2
onto the contact strip (A).
Tighten screws 3.
10. Mounting suitable cables in energy chains
1. Lay the chain out lengthwise.
2. Place the cables in the chain, making sure they are not twisted.
3. Separate cables from each other through separators/drill holes.
4. Do not connect cables together.
5. Comply with space X. X , 10 % of the cable diameter D.
In case of a vertically suspended chain, enlarge the clearance X.
7435d_3
6. Align chain in the operating position.
The bending radius of the cables is at least R
Cables are freely movable in the bending radius KR of the energy chain
Cables are not forced through the chain.
7435d_4
7. Mount chain ( Corresponding assembly instructions).
8. Fasten cables:
At both ends of the chain in case of short energy chains ( Fig. 1)
Only at the driver end in the case of long, sliding energy chains ( Fig. 2).
9. Do not move cables up to the fastening point.
Mounting space A between the fastening point and bending movement
is observed.
Fig. 1
7435d_2
Fig. 2
7435d_1
Note
Chain break.
Damage to cables.
Replace cables.
Note
Malfunction and material damage due to vertically suspended cables.
The cables stretch.
Regularly check the length of the cables.
Readjust the cables if required.
1.2 Nm _ 20 %
2
3
1
4
2
3
A