Pressure sensor SPAU
Festo AG & Co. KG
Postfach
73726 Esslingen
Germany
+49 711 347-0
www.festo.com
Operating instructions 8001199
1410NH
[8041211]
Original: de
Pressure sensor SPAU English..........................................
1 Product description
The operating instructions describe the entire function range. The function range is
limited, depending on the product variant.
Note
You can find detailed specifications for the product, the device description file
(IODD) with a description of the IO-Link parameters and the declaration of
conformity at: è www.festo.com.
1.1 Overview
Display variant without front panel mounting
1)
1
2
3
456
1 Display
2 Pneumatic port
3 Electrical connection
4 B key
5 Edit button
6 A key
1) Representation of other variants can deviate
from this.
Fig. 1
1.2 Characteristics
Characteristic Code Specification
Type SPAU Pressure sensor
Pressure
measuring range
-B2, -B11, -P025, -P05, -P1, -P2,
-P6, -P10, -P12, -P16, -V025,
-V05, -V1
è Technical data
Supply port R Relative pressure
Type of mounting -T
-H
-W
-A
-F
Threaded mounting
H-rail mounting
Wall mounting
Mounting bracket
Front panel mounting
Characteristic Code Specification
Pneumatic port -G18, -R18, N18, -R14, -M5, -M7
-Q4,-Q6,-T532
Thread Gx, Rx, NPTx , R¼, M5, M7
Plug connector 4mm, 6mm, Â
Thread type
M
F
None
Male thread
Female thread
Outlet direction
D
Rear
Underneath
Display
-L
None
LCD, backlit
Electrical output 1 -PNLK
-LK
Switching output PNP / NPN / IO-Link
IO-Link
Electrical output 2 -PNVBA
-V
-B
-A
PNP / NPN / 0…10 V / 1…5 V / 4…20 mA
0…10 V
1…5 V
4…20 mA
Electrical
connection
-M8
-M12
M8 plug
Plug M12, A-coded
Electrical outlet
direction D
U
Rear
Underneath
On top
Electrical
accessories
+2.5A
+2.5S
+5A
+5S
None
Angled socket, 2.5 m cable
Straight socket, 2.5 m cable
Angled socket, 5 m cable
Straight socket, 5 m cable
Protective
devices G
None
Safety guard
Certificate
T
None
Test report
Fig. 2
2 Function and application
The pressure sensor SPAU is intended for monitoring pressure in the piping. The
sensor converts pneumatic pressure values (relative pressure) into electrical sig
nals, which can be used for control or regulating functions. Measurements are
carried out using a piezoresistive sensor element with a following electronic evalu
ation unit. Interfacing to the higher-level system is provided by 1 or 2 switching
outputs, an analogue output and/or an IO-Link interface.
The switching outputs can be configured for monitoring of a threshold value, a
pressure range or a differential pressure. For each output, PNP or NPN and nor
mally open (NO) or normally closed (NC) can optionally be set. Via the IO-Link inter
face, process values can be read out and parameters changed and transmitted to
additional devices.
2.1 Operating statuses
Operating status Function
RUN mode Initial status after switching on the operating voltage
Display of the current measured value
SHOW mode Display of the current settings
EDIT mode Setting or modification of parameters
TEACH mode Acceptance of the current measured value to determine switching points
Fig. 3
2.2 Switching functions
Threshold value comparator for monitoring of a pressure threshold
Function NO (normally open) NC (normally closed)
Switching function:
1 Switching point (SP)
TEACH mode:
2 teach-in points (TP1, TP2)
SP = ½ (TP1+TP2)
TP1 TP2
HY
1
0
Out
p
SP
TP1 TP2
SP
HY
1
0
Out
p
Fig. 4
Window comparator for monitoring of a pressure range
Function NO (normally open) NC (normally closed)
Switching function:
2 Switching points (SP.Lo, SP.Hi)
TEACH mode
1)
:
2 teach-in points (TP1, TP2)
TP1 = SP.Lo, TP2 = SP.Hi
HY HY
TP1=SP.Lo TP2=SP.Hi
1
0
Out
p
HY HY
TP1=SP.Lo TP2=SP.Hi
1
0
Out
p
1) SP.Lo = smaller pressure/vacuum value, SP.Hi = larger pressure/vacuum value, dependent on the
Teach sequence
Fig. 5
Auto difference monitoring
With the auto difference monitoring function, a change in pressure from a refer
ence value is detected. As a result, a maximum permissible pressure drop can be
monitored, for example.
If the input variable is in the work range between [SP.Hi] and [SP.Lo] and is con
stant, its value is set automatically as the reference value P
Ref
. The output
switches.
A constant input variable is present if the signal change is less than 0.2 % FS dur
ing the set observation time [t.obs].
The parameter [d.SP] establishes the permissible deviation of pressure from the
reference value and thus the monitoring range. If pressure exceeds or falls below
[d.SP], the output switches back.
Function NO (normally open) NC (normally closed)
Switching function:
2 switching points (SP.Lo,
SP.Hi) for setting the valid
work range
TEACH mode
1)
:
2 teach-in points (TP1, TP2)
TP1 = SP.Lo, TP2 = SP.Hi
SP.Lo P
Ref
SP.Hi
d.SP
1
0
Out
p
1
SP.Lo P
Ref
SP.Hi
d.SP
0
Out
p
1) SP.Lo = smaller pressure value, SP.Hi = larger pressure value, independent of the Teach sequence
Fig. 6
3 Requirements for product use
Only use the product in original status, without any unauthorised modifications.
The product is intended for use in industrial environments. Measures may need
to be implemented in residential areas for radio interference suppression.
Take into consideration the ambient conditions at the location of use.
Operate the product only with compressed air of the specified air quality class
(è Technical data).
Remove all transport packaging. The material used in the packaging has been
specifically chosen for its recyclability.
Accessories è www.festo.com/catalogue.
Range of applications and certifications
In combination with the UL mark on the product, the information included in this
section is also applicable for compliance with the certification requirements of
Underwriters Laboratories Inc. (UL) for USA and Canada. Observe the following
English-language remarks from UL:
UL approval information
Product category code QUYX, QUYX7
File number E322346
Considered standards UL 610101, CAN/CSAC22.2 No. 610101
UL mark
Fig. 7
Only for connection to an NEC/CEC Class 2 supply.
Raccorder uniquement a un circuit NEC/CEC Classe 2.
Electrical and environmental ratings
Input voltage max. 30 V DC, Class 2
Input current max. 0.24 A
Power max. 7.2 W
Pressure differential max. 1.6 MPa
Ambient temperature max. 50 °C /122 °F
Pollution degree 3
Humidity range 93 %
Only for indoor use.
Altitude up to 2000 m. Altitude up to 2000 m or above 2000 m if specified by the manufacturer.
Fig. 8
Warning
Unit shall be supplied by a power source which complies with the requirements
of a limitedenergy circuit in accordance with IEC/EN/UL/CSA 610101 or a Lim
ited Power Source (LPS) in accordance with IEC/EN/UL/CSA 609501 or IEC/EN/
UL/CSA 623681 or a Class 2 circuit in accordance with NEC or CEC.
4 Installation
Note
Installation and commissioning are to be carried out only by qualified personnel
in accordance with the operating instructions.
4.1 Mechanical and pneumatic
Note
An unfavourable mounting position can impair the function of the product.
Mount the sensor so that no condensation from the compressed air lines can
gather in the device.
Install the sensor so that it cannot be heated above the maximum permissible
operating temperature (plan for convection possibilities).
SPAU-...-T
Seal connecting thread.
Max. 10 Nm
Max. 7 Nm
For example, with double
nipple x
Fig. 9 Fig. 10
SPAU-...-H SPAU-...-A
Mounting bracket hole pattern
è Fig. 29
M3
max. 0.5 Nm
Fig. 11 Fig. 12
SPAU-...-W
Wall mounting hole pattern è Fig. 30
1.
2.
Fig. 13
SPAU-...-F
Size of the front panel cut-out in mm è Fig. 14
Guide sensor from the front into the cut-out on the front panel.
Attach the clamping plate and press until the fastening slide clips in.
34
±
0.3
61
±
0.3
M3
max. 0.7 Nm
s
s < 2 mm: remove 1 washer
s < 1 mm: remove 2 washers
Fig. 14 Fig. 15