ENGLISH
EATON ATS 30
EATS30N
EATS30H
EATS30P
Installation
and user manual
Copyright © 2014 EATON
All rights reserved.
Service and support:
Call your local service representative
ATS-00_EN
Page 2
ATS-00_EN
SAVE THESE INSTRUCTIONS. This manual contains important instructions
that should be followed during installation and maintenance of the ATS.
The EATON ATS models that are covered in this manual are intended for installation
in an environment within 40°C/104°F (EATS30H, EATS30P) and 35°C/95°F (EATS30N),
free of conductive contaminant.
Certication standards
• Safety: UL (US) (UL 60950) CE (EU) (IEC 60950) PSE (JP)
• EMI: CISPR 22 Class A and FCC Class A
• EMS:
- IEC 61000-4-2
- IEC 61000-4-3
- IEC 61000-4-4
- IEC 61000-4-5
- IEC 61000-4-6
- IEC 61000-4-8
- IEC 61000-4-11
Important safety notes
• Onlyqualiedpersonnelcanservicethisequipment.
• Follow the following precautions when working on this unit.
- Remove watches, rings, or other metal objects.
- Use tools with insulated handles.
- Examine the packing container. Notify the carrier immediately if any damage is present.
- Do not disassemble the unit.
- Do not operate the unit near water or in an area with excessive humidity.
- Keep liquid and foreign objects from getting inside the unit.
-Donotoperatetheunitclosetogasorre.
• Upstream circuit breaker must be added for each input. The recommended breaker is D curve 30A
for EATS30H - EATS30P and D curve 32A for EATS30N.
• Verify whether the branch circuit breaker or fuse on service feed is correct.
• Verify line voltage requirements and the supplied line voltage prior to installation.
Electrical warnings
• When servicing this equipment, you may need to remove its protective covers and connect utility power.
Please observe great caution during these procedures.
• Check that power cords, plugs, and outlets are in good condition.
SAFETY INSTRUCTIONS