SmartOnline SVTX Series 3-Phase 380/400/415V
20kVA 18kW On-Line Double-Conversion UPS,
Tower, Extended Run, SNMP Option
MODEL NUMBER: SVT20KX
Economical, entry-level 3-phase UPS system protects connected mission-critical equipment against
damage, downtime and data loss due to blackouts, brownouts, power surges and line noise.
Description
The SVT20KX SmartOnline® SVTX Series 3-Phase 380/400/415V 20kVA 18kW On-Line Double-
Conversion UPS with IGBT technology provides battery backup and AC power protection against power
disturbances that can damage electronics or destroy data. It’s recommended for critical IT or corporate
infrastructure, telecom, LAN/WAN, security and emergency, financial and light industrial applications.
The SVT20KX’s Voltage and Frequency Independent (VFI) design allows continuous operation at any
supported voltage at either 50 or 60 Hz. Zero transfer time to battery mode ensures no disruption to the
attached loads. Automatic and Manual Bypass keeps connected equipment powered even during
overloads and UPS maintenance.
IGBT inverter technology produces output power with less than 2% total harmonic distortion (THD) to
keep connected equipment functioning at its peak. A 3:1 crest factor safely supports a variety of loads,
even those with wildly fluctuating power demands.
Managing the SVT20KX is simplified through the interactive front-panel LCD interface, which displays
critical operating conditions and diagnostic data, such as load levels, available runtime, alarm status,
battery charge, and voltage and frequency values. Four LEDs indicate bypass, line, battery and fault
modes. A serial port allows connection to Tripp Lite’s free local shutdown agent. A built-in card slot
supports WEBCARDLX or RELAYCARDSV for network interface and remote monitoring and control. The
SVT20KX’s reduced size and small footprint save valuable space.
Features
VFI True On-Line Double-Conversion 3-Phase UPS SystemProvides fully regulated sine wave AC
output for critical telecom, network, security, financial, corporate and light industrial applications+/-1%
output voltage regulation in online and battery modesHigh 0.9 power factor offers 20kVA/18kW output
capacity, allowing for more connected devicesSelectable 380/400/415V output voltageWide input voltage
window (305–478V) minimizes battery use and prolongs battery life
Reliable Battery Backup with Expandable RuntimeSupports half load for 11 min. and full load for 4
min.Zero transfer time suitable for advanced network applicationsExpandable runtime with optional
external battery packs, such as Tripp Lite’s BP240V135Restarts automatically after lengthy power
outages
IGBT Inverter TechnologyProduces output power with less than 2% THD to keep connected equipment
functioning at its peakLow <6% THDi input rating and advanced IGBT rectifier enables 1:1 Generator
Highlights
On-line double-conversion
topology, VFI operation
Automatic and Manual Bypass
for enhanced reliability
Optional ECO mode for high-
efficiency operation
Add optional WEBCARDLX with
latest version of PADM20 for
enhanced remote management
Paralleling for capacity up to 3
units
Package Includes
SVT20KX SmartOnline SVTX
Series 3-Phase 380/400/415V
20kVA 18kW On-Line Double-
Conversion UPS
(2) RS-232 cables
6-pin current sharing cable
Owner’s manual
1 / 6
Specifications
Sizing, eliminating costly oversizing requirements for generators, breakers and cables
Paralleling CapabilityConnect up to 3 units in parallel configuration for increased capacity
Automatic and Manual BypassIncreases system reliabilityAllows maintenance without removing power
from attached loads
ECO ModeOperates at efficiency levels as high as 98.8% when input line conditions are favorable
SNMP/Web CapabilitySlot for WEBCARDLX network interface or RELAYCARDSV relay card for remote
monitoring and control optionsOptional WEBCARDLX (sold separately) with the latest version of
PowerAlert Device Manager firmware (PADM20) provides enhanced remote management
capabilitiesPADM20 and PowerAlert Element Manager (PAEM) form a powerful tool for expanding
maintenance functions in large installations, including firmware update checks and backup and restoration
of device configurations
Communications PortsDB9 and EPO ports offer local monitoring and shutdown options
Small-Footprint Tower DesignReduced-size black tower case saves valuable floor spaceMatching
external battery cabinets enable extended runtime options
OVERVIEW
UPC Code 037332195890
UPS Type On-Line
INPUT
Rated input current (Maximum Load) 34.4A
Nominal Input Voltage(s) Supported 220/380V 3-PH Wye; 230/400V 3-PH Wye; 240/415V 3-PH Wye
Nominal Input Voltage Description 3-Phase Wye, 4 wire plus ground (L1, L2, L3, N, G)
UPS Input Connection Type Hardwire
Input Circuit Breakers 63A (3 pole)
Input Phase 3-Phase
Power Factor (Input) .99PF (100% load)
THDi <6% (100% load)
OUTPUT
Output Volt Amp Capacity (VA) 20000
Output Capacity (kVA) 20
Output Watt Capacity (Watts) 18000
Output kW Capacity (kW) 18
2 / 6