PRODUCT INFORMATION
NA2XS(F)2Y
Longitudinally water-tight PE medium voltage cable with aluminium conductor
NA2XS(F)2Y, VDE, PE medium voltage cable acc. VDE 0276-620, with aluminium conductor, longitudinally water-tight, for fixed
installation
Info
3 voltage classes: 6/10 (12) kV, 12/20 (24) kV, 18/30 (36) kV
With aluminium conductor
Suitable for outdoor use
Mechanical resistance
UV-resistant
Waterproof
Application range
Power and control cable for fixed installation in the following applications:
In water, in ground, outdoors and indoors
In cable trays for power stations, industry, and distribution networks
Also suitable for applications where longitudinal water propagation inside the cable should be avoided.
Burial without additional, suitable underground protection according to HD 620/VDE 0276-620 - Part 10-C (point 4): normal
minimum installation depth 0.6 m, but at least 0.8 m under roads
Product features
Suitable for installation or operation under high mechanical stress due to the PE-sheath
Current rating according to HD 620/VDE 0276-620, Part 10-C, Table 7 (buried at +20 °C ground temperature according to HD
620/VDE 0276-620, Part 10-C, point 5) for routing underground and Table 8 (in the air at an air temperature of +30 °C according to
HD 620/VDE 0276-620, Part 10-C, point 5) when used outdoors; but always taking into consideration corrections/reductions to the
Last Update (12.04.2022) 1 / 4
©2022 Lapp Group - Technical changes reserved
Product Management www.lappkabel.de
You can find the current technical data in the corresponding data sheet.
PN 0456 / 02_03.16
PRODUCT INFORMATION
NA2XS(F)2Y
current rating that may be necessary according to VDE 0298-4, and VDE 0298-4 (also refer to the catalogue appendix T12) for
installation in and on buildings
Norm references / Approvals
HD 620/ VDE 0276-620
Product Make-up
Aluminium conductor
Abbreviation "rm":
r = round conductor form;
m = multi-wire conductor
Core insulation: Cross-linked Polyethylen (XLPE)
Screen made of copper wires with one or two copper bond counter spiral
longitudinally water-tight wrapping
Outer sheath: PE, black
Technical Data
Classification ETIM 5: ETIM 5.0 Class-ID: EC001140
ETIM 5.0 Class-Description: Medium voltage power cable
Classification ETIM 6: ETIM 6.0 Class-ID: EC001140
ETIM 6.0 Class-Description: Medium voltage power cable
Conductor stranding: Multi-wire
Minimum bending radius: Fixed installation: 15 x outer diameter
Nominal voltage: U
0
/U: 6/10 (12) kV, 12/20 (24) kV, 18/30 (36) kV
Test voltage: Depending on nominal voltage:
6/10 kV: 15 kV
12/20 kV: 30 kV
18/30 kV: 45 kV
Temperature range: During installation: -40°C to +70°C
Fixed installation: -40°C to +90°C
Note
Unless specified otherwise, the shown product values are nominal values. Detailed values (e.g. tolerances) are available upon
request.
Aluminium price basis: excludes aluminium. Refer to catalogue appendix T17 for the application and definition of "Metal price basis"
and "Metal index".
Please find our standard lengths at: www.lappkabel.de/en/cable-standardlengths
* Trade product, no Lapp product
Photographs and graphics are not to scale and do not represent detailed images of the respective products.
Prices are net prices without VAT and surcharges. Sale to business customers only.
Last Update (12.04.2022) 2 / 4
©2022 Lapp Group - Technical changes reserved
Product Management www.lappkabel.de
You can find the current technical data in the corresponding data sheet.