AS-i / IO-Link Module,
IO-Link Master with 4 IO-Link Ports
Bihl+Wiedemann GmbH · Floßwörthstr. 41 · D-68199 Mannheim · Phone: (+49) 621/33996-0 · Fax: (+49) 621/3392239 · eMail: mail@bihl-wiedemann.de
page 2 Mannheim, 24.9.18 We reserve the right to change any data www.bihl-wiedemann.de
Article no. BWU2853 BWU3020
Connection
AS-i/AUX connection profile cable and piercing
Periphery connection M12
Length of connector cable I/O: max. 20 m
IO-Link
Number 4 ports Class A 4 ports Class B
Data rate COM1 / COM2 / COM3
IO-Link revision 1.1
AS-i
Profile slave 1: S-7.5.5 (ID1=F default)
slave 2: S-7.5.5 (ID1=E default)
Address 2 single slaves
Operating voltage 30 V (18 … 31.6 V)
Required master profile ≥M4
Since AS-i specification 3.0
Max. current consumption 50 mA 200 mA
Max. current consumption
without
sensor / actuator supply
50 mA 80 mA
AUX
Voltage 24 V (18 … 30 V)
Max. current consumption 4 A
(1)
Input
Number 4 (via IO-Link port) +
4x electronic
4 (via IO-Link port)
Power supply out of AUX out of AS-i
Supply of attached
sensors
up to
+25 °C
500 mA per port,
∑(sensors + outputs) max. 1000 mA
(2)
∑(sensors + outputs) max. 120 mA
(5)
at +40 °C 500 mA per port,
∑(sensors + outputs) max. 833 mA
(2)
at +55 °C 500 mA per port,
∑(sensors + outputs) max. 666 mA
(2)
∑(sensors + outputs) max. 100 mA
(5)
at +70 °C 500 mA per port,
∑(sensors + outputs) max. 500 mA
(2)
∑(sensors + outputs) max. 80 mA
(5)
Switching threshold U<5 V (low)
U>15 V (high)
Output
Number 4 (via IO-Link port)
Power supply out of AUX output voltage out of AS-i;
actuator supply out of AUX
Max.
output current
up to
+25 °C
500 mA per port,
∑(sensors + outputs) max. 1000 mA
(2)
∑(sensors + outputs) max. 120 mA
(5)
at +40 °C 500 mA per port,
∑(sensors + outputs) max. 833 mA
(2)
at +55 °C 500 mA per port,
∑(sensors + outputs) max. 666 mA
(2)
∑(sensors + outputs) max. 100 mA
(5)
at +70 °C 500 mA per port,
∑(sensors + outputs) max. 500 mA
(2)
∑(sensors + outputs) max. 80 mA
(5)