ASi Module with integrated IO-Link
Master with 4 Ports, IP67, M12
Bihl+Wiedemann GmbH · Floßwörthstr. 41 · D-68199 Mannheim · Phone: (+49) 621/33996-0 · Fax: (+49) 621/3392239 · eMail: mail@bihl-wiedemann.de
www.bihl-wiedemann.de We reserve the right to change any data Mannheim, 21.7.21 page 1
ASi Module with integrated IO-Link Master
with 4 Ports, IP67, M12
fourfold IO-Link Master
2 single addresses in one housing
Power supply of IO-Link ports out of AUX (or ASi)
(Figure similar)
Figure Type Inputs
digital
Outputs
digital
M12
wiring
(1)
(1)
M12 wiring
Port Class A: In this type Pin2 is assigned with an additional digital input.
Port Class B: This type provides an additional power supply and is suitable for the connection of devices that have an increased power
demand. In this case, pins2 and 5 are used to provide the additional power supply.
Input voltage
(sensor
supply)
(2)
(2)
Input voltage (sensor supply)
Inputs are supplied by ASi or by AUX (auxiliary 24 V power). If supplied by ASi, inputs can neither be connected to earth nor to external
potential.
Output voltage
(actuator
supply)
(3)
(3)
Output voltage (actuator supply)
The supply of the outputs is made by ASi or by AUX (auxiliary 24 V power). By supply out of ASi there is no connection to earth or external
potential allowed.
ASi
connection
(4)
(4)
ASi connection
The connection to ASi as well to AUX (auxiliary 24 V power) is made via yellow or black ASi profile cable with piercing technology or via
M12 socket (in IP20 via clamps).
ASi
address
(5)
(5)
ASi address
AB addresses (max. 62 AB addresses/ASi network), 2 AB addresses (max. 31 modules with 2 AB addresses), Single addresses (max. 31
Single addresses/ASi network), mixed use allowed. Upon request, ASi-3 nodes are available with specific ASi node profiles. For modules
with two ASi-3 nodes the 2nd ASi-3 node is turned off as long as the 1st ASi-3 node is addressed to address "0".
Max.
output
current
Art. no.
IP67
8 x M12
4 x IO-Link port
+
4 x electronic
4 x
IO-Link port
IO-Link port
class A
out of AUX out of AUX
ASi
profile cable
2 single
addresses
500 mA BWU2853
IP67
8 x M12
4 x IO-Link port
+
4 x electronic
4 x
IO-Link port
IO-Link port
class A
out of ASi out of ASi
ASi
profile cable
2 single
addresses
120 mA
BWU2945
(6)
(6)
Only on request.
IP67
8 x M12
4 x IO-Link port
4 x
IO-Link port
IO-Link port
Class B
out of ASi
output voltage
out of ASi;
actuator supply
out of AUX
ASi
profile cable
2 single
addresses
120 mA BWU3020
ASi Module with integrated IO-Link
Master with 4 Ports, IP67, M12
Bihl+Wiedemann GmbH · Floßwörthstr. 41 · D-68199 Mannheim · Phone: (+49) 621/33996-0 · Fax: (+49) 621/3392239 · eMail: mail@bihl-wiedemann.de
page 2 Mannheim, 21.7.21 We reserve the right to change any data www.bihl-wiedemann.de
Article no. BWU2853 BWU3020
Connection
ASi/AUX connection profile cable and piercing
Periphery connection M12
Length of connector cable I/O: max. 20 m
IO-Link
Number 4 ports Class A 4 ports Class B
Data rate COM1 / COM2 / COM3
IO-Link revision 1.1
ASi
Profile Node 1: S-7.5.5 (ID1=F default)
Node 2: S-7.5.5 (ID1=E default)
Address 2 single addresses
Operating voltage 30 V (18 31.6 V)
Required master profile ≥M4
Since ASi specification 3.0
Max. current consumption 50 mA 200 mA
Max. current consumption
without
sensor / actuator supply
50 mA 80 mA
AUX
Voltage 24 V (18 30 V)
Max. current consumption 4 A
(1)
Input
Number 4 (via IO-Link port) +
4 x electronic
4 (via IO-Link port)
Power supply out of AUX out of ASi
Supply of attached
sensors
up to
+25 °C
500 mA per port,
∑(sensors + outputs) max. 1000 mA
(2)
∑(sensors + outputs) max. 120 mA
(6)
at +40 °C 500 mA per port,
∑(sensors + outputs) max. 833 mA
(2)
at +55 °C 500 mA per port,
∑(sensors + outputs) max. 666 mA
(2)
∑(sensors + outputs) max. 100 mA
(6)
at +70 °C 500 mA per port,
∑(sensors + outputs) max. 500 mA
(2)
∑(sensors + outputs) max. 80 mA
(6)
Switching threshold U<5 V (low)
U>15 V (high)
Output
Number 4 (via IO-Link port)
Power supply out of AUX output voltage out of ASi;
actuator supply out of AUX
Max.
output current
up to
+25 °C
500 mA per port,
∑(sensors + outputs) max. 1000 mA
(2)
∑(sensors + outputs) max. 120 mA
(6)
at +40 °C 500 mA per port,
∑(sensors + outputs) max. 833 mA
(2)
at +55 °C 500 mA per port,
∑(sensors + outputs) max. 666 mA
(2)
∑(sensors + outputs) max. 100 mA
(6)
at +70 °C 500 mA per port,
∑(sensors + outputs) max. 500 mA
(2)
∑(sensors + outputs) max. 80 mA
(6)