Translation:
ATEX Type Examination Certificate
Directive 2014 / 34 / EU
Equipment or Protective systems intended for use
in potentially explosive atmosphere
Number: TURCK Ex-10002M X Issue no.: 1
Equipment: Sensoren Typenreihe uprox® und uprox®+:
DBi/Bi..U-……/3D, Ni..U-……/3D
DBi/Bi..U-……/3GD, Ni..U-……/3GD
Manufacturer: Hans Turck GmbH & Co KG
Address: Witzlebenstr. 7 45472 Mülheim an der Ruhr
This equipment and any acceptable variation thereto is specified in the schedule to this
certificate.
Hans Turck GmbH & Co. KG certifies that this product has been found to comply with
the Essential Health and Safety Requirements of the Directive 2014 / 34 / EU by
compliance with:
EN 60079-0:2012/A11:2013 EN 60079-15:2010 EN 60079-31:2014
If the sign “X” is placed after the certificate number, it indicates that the equipment or
protective system is subject to special conditions for safe use specified in the schedule
to this certificate.
Marking:
Hans Turck GmbH & Co. KG
Mülheim an der Ruhr, date 4/20/2016 (i.A. W. Dick)
Representative
II 3 G Ex nA IIC T4 Gc
II 3 D Ex tc IIIC T110°C Dc
Translation:
Schedule to
Type Examination Certificate No. TURCK Ex-10002M X Issue no.: 1
Description of device:
The use of inductive sensors is allowed in zone 2 resp. zone 22 depending on the marking. The
sensors are suitable for contactless and wear-free detection of metallic objects and conversion
into a digital output signal.
Internal test report no.:
Zone2+22_1_D_PB_~_Turck Ex-10002M X
Normengenerationswechsel_Turck Ex-10002M X
Zone2+22_A1_D_NGW_~_Turck Ex-10002MX
Special conditions for safe use:
The device must be supplied from power supply units with secure separation according
to IEC 60364 which ensure that the rated voltage of the equipment is not exceeded by
more than 40% by transient distrubances.
The sensor with Q80 or CP40 housing must be protected against static charge, e.g. by
conductive fastening with connection to protective ground potential.
Plug-in devices or connection cables may only be connected or disconnected in a de-
energized state.
Fix a warning in the near of connector permanently in suitable form with following text:
DO NOT SEPARATE WHEN ENERGIZED.
The device connectors have to be secured against accidentally disconnecting; use the
included safety clip SC-M12 / 3GD.
The IP protection degree of the connectors is given only in conjunction with matching O-
rings.
Do not open the terminal compartment of the sensor under voltage or make sure that no
explosive atmosphere is present.
Use only EX-approved cable gland (II 3 G; II 3 D).
Protect the device against any mechanical damage.
The device shall be protected against ultraviolet radiation.
Essential health and safety requirements:
no additional ones
Ambient temperature range:
-25°C … + 70°C
Electrical data:
Operating voltage / voltage range:
10…30V DC
10…55V DC
10…65V DC
Output current:
≤ 150 mA or ≤ 200 mA